Plan Review Details - Permit 02011348
Plan Review Stops For Permit 02011348
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-02-07 Cont ID  
Sent By lsmith Date 2002-02-07 Time 09:33 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2002-02-07 00:00:00**************PROVISO***************
  
 1. ELECTRIC NEEDS SEPARATE PERMIT &
 DRAWINGS.
  
 2. FENCE NEEDS SEPARATE PERMIT WITH
 EASEMENT RELEASE FORM APPROVED BY
 UTILITIES.
  
 3. SEE NOTES ON PLUMBING REVIEW.
  
 4. HURRICANE PANELS FOR 2 WINDOWS ALL
 OTHERS ARE EXISTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-31 Cont ID  
Sent By pkrauss Date 2002-02-07 Time 08:58 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2002-01-31 00:00:00*************BUILDING UNSAT*************
  
 SBC 104.2.2
  
 1. SUBMIT PRODUCT APPROVALS FOR STORM
 PANELS WITH INSTALLATION SCHEDULE FOR
 EACH WINDOW OPENING.
 2. SUBMIT PRODUCT APPROVALS FOR EXTERIOR
 DOORS.
 3. A/C CONTRACTOR TO SUBMIT ENERGY CALCS
 AND PLANS FOR CENTRAL SYSTEM.PERMIT
 APPLICATION MUST BE APPLIED FOR SEPARATE
 4. ELECTRIC CONTRACTOR MUST PROVIDE
 DRAWINGS & APPLY FOR SEPARATE ELECTRICAL
 PERMIT.
 5. SURVEY/PLOT PLAN REQUIRED FOR FENCE
 SHOWING AREA TO BE FENCED. FENCE MUST
 BE APPROVED BY ZONING.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2002-02-07 Cont ID  
Sent By dpalmer Date 2002-02-07 Time 08:47 Rev Time 0.00
Received By dpalmer Date 2002-02-07 Time 08:47 Sent To  
Notes
2002-02-07 00:00:00SEPARATE PLANS AND PERMIT APPLICATION

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-29 Cont ID  
Sent By dpalmer Date 2002-01-29 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2002-01-29 Time 07:48 Sent To  
Notes
2002-01-29 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE, NOTHING WAS
 SUBMITTED FOR REVIEW?
 PLEASE SUBMIT A RISER DIAGRAM SHOWING
 NEW SERVICE DETAILED ON SHEET.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-02-07 Cont ID  
Sent By pkrauss Date 2002-02-07 Time 08:56 Rev Time 0.35
Received By pkrauss Date 2002-02-07 Time 08:56 Sent To B
Notes
2002-02-07 00:00:00 
 MECH PERMIT 02011618
  
 SEE NOTES ON MASTER PREMIT 00100505

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-01-30 Cont ID  
Sent By pkrauss Date 2002-01-30 Time 07:15 Rev Time 0.25
Received By pkrauss Date 2002-01-30 Time 07:15 Sent To B
Notes
2002-01-30 00:00:00 
 PERMIT APPLICATION APPEARS TO BE FOR
 DEMO.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-01-26 Cont ID  
Sent By pschmitz Date 2002-01-26 Time 13:00 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-26 00:00:00REPLACE KITCHEN SINK AND BATH TUB,
 FAUCETS WITH PIPING, H20, WASTE.

Review Stop Z ZONING
Rev No 1 Status N Date 2002-02-07 Cont ID  
Sent By lsmith Date 2002-02-07 Time 09:32 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
2002-02-07 00:00:00NEED SEPARATE PERMIT FOR FENCE WITH
 EASEMENT RELEASE FORM APPROVAL.