Plan Review Stops For Permit 02011286 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2002-07-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-07-05 |
Time |
09:18 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2002-06-07 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-06-07 |
Time |
07:56 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-06-07 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 02011286 | | ADD: 4925 N MILITARY TRAIL | | CONT: TRANSEASTERN | | TEL: 333-4541 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1) SITE SPECIFIC ENGINEERING (PRODUCT | | APPROVAL) REQUIRES THE WET SIGNATURE, | | DATE AND EMBOSSED SEAL OF THE ENGINEER | | CERTIFYING THE PRODUCT AND OF THE DESIGN | | PROFESSIONAL OF RECORD. THE FENESTATION | | TESTING LAB REPORT FALLS INTO THIS CATA- | | GORY,(PAIR OF FRENCH DOORS/ SIDELIGHTS) | | | | 2) BEFORE A PERMIT TO CONSTRUCT CAN BE | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | BEACH CO.,THE PERMIT PLANS STAMPED BY | | THEM AND THE RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. | | | | ANY QUESTIONS PLEASE CALL, | | JIM WITMER | | BUILDING PLAN REVIEW | | DEPARTMENT OF CONSTRUCTION SERVICES | | CITY OF WEST PALM BEACH | | (561) 659-8096 EXT. 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-03-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-03-30 |
Time |
12:33 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-30 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 02011286 | | 4925 N MILITARY TRAIL | | CONT: TRANSEASTERN | | TEL: 753-5531 | | | | SBC =1997 STANDARD BUILDING CODE | | SECOND REVIEW | | 1)- MISSING SOILS REPORT | | 2)- SHEET A-3 FRONT ELEVATION INDICATES | | THE FRONT ELEVATION WITH (2) FRENCH | | DOORS ELEVATION 8'-0" THE PRODUCT TEST- | | ING REPORT IS GOOD UP TO7'-0". | | 3)- THE SAME SHEET THE REAR ELEVATION IN | | DICATES THE FRENCH DOORS AT THE SAME | | 8'-0" ELE. AND THE ADDITION OF SIDELITES | | THE PRODUCT TESTING REPORT NOT ONLY IS | | GOOD FOR THE 7'-0" HEIGTH BUT DOES NOT | | INCLUDE SIDELITES EITHER! | | 4)- FAIR HOUSING AS FL ACCES CODE, AT | | LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT | | ACCESSIBLE BUILDINGS, FACILITIES, | | ELEMENTS AND OTHER SPACES THAT ARE ON | | THE SAME SITE. | | FL ACC CODE 4.3.3.2(2)THEFRONT AND | | REAR ELEVATIONS INDICATE CHANGE OF GRADE | | GREATER THAN 1/2". | | THERE APPEARS TO BE A SIDEWALK ON THE | | SITEPLAN THAT CONNECTS THE VOLLEYBALL | | COURT, ALSO THE POOL DECK BUT NOT THE | | TOTLOT. | | 5)-COUNTY IMPACT FEES ARE TO BE ASSESS | | ED BEFORE ISSUANCE OF THE PERMIT. | | 6)- RADON FEES DUE BEFORE ISSUANCE. | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096X8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-02-04 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-02-04 |
Time |
12:21 |
Rev Time |
2.50 |
Received By |
jwitmer |
Date |
2002-02-04 |
Time |
12:21 |
Sent To |
|
|
Notes |
2002-02-04 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 02011286 | | 4925 N MILITARY TRL | | CONT: TRANSEASTERN PROP | | TEL: NOT LISTED | | | | SBC= 1997 STANDARD BUILDING CODE | | | | 1)- SBC 104.2.2 ADDITIONAL INFORMATION | | REQUIRED, THE PLANS DO NOT INDICATE | | UNDER WHAT CODE CRITERIA THEY ARE DESIGN | | ED TO? | | 2)- THE DESIGN CRITERIA, PARAMETERS & | | ASSUMPTIONS, MEAN ROOF HEIGTH, BASIC | | WIND VELOCITY PRESSURE, ROOF DEAD LOADS | | MINIMUM SOIL BEARING AND IF ARCH. REVIEW | | ED FOR SHEAR WALLS. | | 3)- MISSING SOILS REPORT. | | 4)- SHEET A-2 DOORS 1 & 1-A INDICATE | | (W)6'-0"X(H)8'-0", THE PRODUCT APPROVAL | | REPORT IS APPROVED UP TO (H)7'-0". | | 5)-DOOR 1-A PRODUCT REPORT IS NOT APPROV | | ED FOR SIDE LITE INSTALATION. | | 6)- SHEET A-4 THE GABLE END DETAIL INDI- | | CATES A DETAIL 8/D-1? MISSING. | | 7)- WIND PRESSURES TO BE SHOWN ON ELEVAT | | IONS FOR DOORS / WINDOWS (EXTERIOR). | | 8)- SHEET A-4 FRONT FRENCH DOORS, SHOULD | | THERE BE A L-1 BETWEEN THE TRANSOM & | | DOOR. | | 9)- A-5 KITCHEN: PUBLIC & COMMON USE | | KITCHENS MUST BE USABLE AND MEET THE | | REQUIREMENTS IN THE GUIDELINE FOR KITCH- | | ENS IN ANSI 4.32 COULD BE FOLLOWED. | | FL .ACC. REACH RANGES 4.2.6. | | 10)- FAIR HOUSING AS WELL AS FL ACC CODE | | AT LEAST ONE ACCESSIBLE ROUTE SHALL CON- | | NECT ACCESSIBLE BUILDINGS, FACILITIES, | | ELEMENTS AND OTHER SPACES THAT ARE ON | | THE SAME SITE. FL ACC 4.3.2(2). | | THE FRONT AND REAR ELEVATIONS INDICATE | | CHANGE OF GRADE GREATER THAN 1/2". | | THERE APPEARS TO HAVE A SIDEWALK THAT | | CONNECTS THE VOLLEYBALL COURT, ALSO THE | | POOL DECK BUT NOT THE TOT LOT. | | 11) COUNTY IMPACT FEESARE TO BE PAID | | BEFORE ISSUANCE OF PERMIT. | | 12) RADON FEES ALSO DUE BEFORE ISSUANCE. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096 X 8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
P |
Date |
2002-12-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-12-19 |
Time |
08:36 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-12-19 |
Time |
08:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
F |
Date |
2002-12-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-12-03 |
Time |
10:16 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2002-12-03 |
Time |
08:30 |
Sent To |
|
|
Notes |
2002-12-03 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE, NOW AHU HAS BEEN | | ADDED TO PANEL "A" BUT IS STILL SHOWN | | ON PANEL "C"? PLEASE CLARIFY.PLEASE ALSO | | NOTE, OCP IS SHOWN AT 2-P 60 FOR 5KW | | HEAT. PLEASE VERFIY MAX OCP FOR 5KW. | | | | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE | | LOAD SHOWN AND LOAD SHOWN ON LOAD CALCS | | FOR PANEL "C".PANEL "C" SHOWS 31.04KVA? | | | | 3)NOTE: PLEASE NOTE, IF LOADS ARE | | FIGURED AT ALL CONNECTED LOADS THEN | | IT WILL TAKE IT OVER 400A'S. | | PLEASE SEE ART 220 FOR METHODS AND | | DERATING FACTORS PERMITTED. | | | | 4)NOTE: PLEASE SEE 1/2" CONDUITS SHOWN | | FROM METER TO PANEL "A' AND METER TO FPL | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2002-11-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-11-21 |
Time |
15:03 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-11-21 |
Time |
15:03 |
Sent To |
|
|
Notes |
2002-11-21 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE, PER 700-12E, | | EM/EX LTS NEED TO BE ON THE SAME | | CIRCUITS AS NORMAL LIGHTING IN THOSE | | AREAS. | | PLEASE CORRELATE CIRCUITS AND PANEL | | SCHEDULE. | | | | 2)NOTE: PLEASE NOTE, ONLY ONE AHU IS | | SHOWN ON PANEL "A". | | TWO AIR COMP #1`S SHOWN. | | | | 3)NOTE: PLEASE NOTE KW LOAD SHOWN FOR | | COND UNITS. PLEASE VERIFY LOADS AND | | CORRELATE OCP PER 424-3. | | | | 4)NOTE: PLEASE LABEL PANELS ACCORDING TO | | PANEL SCHEDULES. "A,B,C". | | | | 5)NOTE: PLEASE VERIFY 2-SD`S SHOWN | | OUTSIDE MECH CLOSET? FIRE REVIEW COMMENT | | . | | | | 6)NOTE: PLEASE RE-CONFIGURE LOAD | | CALCULATIONS PER NEC220-3,220-10, | | 220-11,220-13 ETC. PLEASE NOTE, LOADS | | SHOWN FOR PANEL "C" SHOWN AT 4.29AMPS. | | IF LOADS ARE ADDED AS SHOWN, SERVICE | | LOAD COMES UP TO 450.875 WHICH EXCEEDS | | SERVICE SIZE/WIRE ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2002-11-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-07-24 |
Time |
05:55 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-07-24 |
Time |
05:55 |
Sent To |
|
|
Notes |
2002-07-24 00:00:00 | ********** NOTE ******** | | | | PLANS NEED TO HAVE ALL OLD SHEETS TAKEN | | OUT OF SETS AND ONLY HAVE SHEETS NEEDED | | FOR PERMITTING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2002-07-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-07-24 |
Time |
05:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-07-23 |
Time |
19:05 |
Sent To |
|
|
Notes |
2002-07-05 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE MAKE NECESSARY CHANGES ON THE | | PLANS AND RESUBMIT FOR REVIEW. | | | | 1} THE SERVICE ENTRANCE CONDUCTORS IN TH | | E 2 1/2"CONDUIT EXCEED PERMISSIBLE CONDU | | IT FILL PER APPENDIX "C",CHAPTER 9.THIS | | IS THE SAME COMMENT THAT WAS ON THE NOTE | | S FROM THE PREVIOUS REVIEW,IF THERE IS A | | QUESTION ON THIS ,PLEASE CALL. | | | | 2} THE RISER DIAGRAM SHOWS 3/0,S FROM 30 | | 0 AMP MAIN,PLEASE CLARIFY.SAME NOTE AS P | | REVIOUS REVIEW. | | | | 3} MISSING EQUIPMENT GROUND CONDUCTOR BE | | TWEEN BOTH MAIN DISCONNECTS AND PANELS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2002-06-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-06-05 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-06-05 |
Time |
14:47 |
Sent To |
|
|
Notes |
2002-06-05 00:00:00 | ************ UNSAT ************** | | | | 1)NOTE: PLEASE NOTE SERVICE ENTRANCE | | CONDUCTORS HAVE NOW CHANGED, PLEASE NOTE | | CONDUIT FILL IN NEC TABLE, 6 350MCM IN | | A 2 1/2 CONDUIT. CHAPTER 9 | | | | 2)NOTE: PLEASE CLARIFY 350MCMS GOING | | THROUGHT 300A DISC AND FEEDING 100A | | DISC. PLEASE VERFIY 350MCM FOR 100AMPS?? | | YET RISER SHOWS 3/0`S FROM 300MAIN BRKR | | TO 100A MAIN?? PLEASE CLARIFY HOW | | WIRE SIZES APPEAR TO CHANGE FROM 350MCM | | TO 3/0`S? IN 300A DISC. | | PLEASE ALSO NOTE 3/0`S OR 350MCM BEING | | ABLE TO FIT UNDER 100A MCB?240-6/310- | | -16.215-5 ETC. | | 3)NOTE: PLEASE NOTE STILL MISSING | | EQUIPMENT GROUNDING BETWEEN BOTH MAIN | | DISC`S AND PANELS. 250-122 | | | | 4)NOTE: PLEASE SEE ATTACHMENT OF FS/FAC | | 553-79 (2)(B) IN REFERENCE TO PLANS | | BEING REVIEW FOR THE SAME COMMENTS AFTER | | 3RD REVIEW. SEE ATTACHED. | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2002-04-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-04-05 |
Time |
07:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-04-05 |
Time |
07:03 |
Sent To |
|
|
Notes |
2002-04-05 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE NOTE THAT CONDUCTOR SIZE | | IS STILL NOT CORRECT. PLEASE NOTE THAT | | RISER DIAGRAM IS SHOWING 1/0`S FOR A | | 200AMP SERVICE. PLEASE SEE 310-16 FOR | | CORRECT SIZING. | | | | 2)NOTE: PLEASE NOTE THAT MISSING/CLARIFY | | EQUIPMENT GROUNDING METHOD/CONDCUTOR | | BETWEEN MAIN AND PANEL. SIZE PER 250-122 | | | | 3)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT- | | -ING #`S ARE TO BE SHOWN ON PLANS AND | | CORRELATE WITH THE SUBMITTED PANEL | | SCHEDULE. | | | | 4)NOTE: PLEASE CLARIFY MANY LOADS ON | | PANEL SCHEDULE FOR 1-POLE 20A BRKRS | | SHOWN AT 2.4KW? PLEASE NOTE THAT,AT THAT | | LOAD, IT TAKE IT PAST THE NORMAL 80% | | LOADING OF A BRKR. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-02-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-05 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-05 |
Time |
12:45 |
Sent To |
|
|
Notes |
2002-02-05 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THE CONDUCTOR SIZE | | SHOWN FOR BOTH 200AMP MAINS? PLEASE SEE | | 310-16 FOR CORRECT WIRE SIZE. | | PLEASE NOTE THAT WITH CONDUCTOR SIZE | | CHANGING THEN CONDUIT SIZE IS REQ`D TO | | BE INCREASED. | | | | 2)NOTE: PLEASE NOTE THAT PLANS ONLY | | SHOW ONE MAIN WITH METER ON THE OUTSIDE | | OF BLDG. PLEASE SHOW LOCATION OF SECOND | | DISCONNECT. | | | | 3)NOTE: PLEASE NOTE 373-8 FOR USE OF THE | | MAIN AS RACEWAY. | | | | 4)NOTE: PLEASE NOTE THAT PANEL "B" IS | | NOT SHOWN ON PLANS "PLEASE CLARIFY/ SHOW | | ON PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-01-31 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-01-31 |
Time |
16:28 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2002-01-31 |
Time |
16:27 |
Sent To |
|
|
Notes |
2002-01-31 00:00:00 | N/A | | 1. SEE PERMIT # 01101791 AND 01101793. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-04-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-04-09 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-04-09 |
Time |
14:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-02-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-02-01 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-02-01 |
Time |
09:09 |
Sent To |
|
|
Notes |
2002-02-01 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | CODE 3343-00. | | 2) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | 3) MECHANICAL ROOM TO BE SEPARATED BY | | AT LEAST ONE HOUR FROM THE REMAINDER | | OF THE BUILDING. | | 4) PLEASE INDICATE LOCATIONS OF FIRE | | HYDRANTS IN RELATION TO THE PROPOSED | | CLUBHOUSE. | | 5) DUCT SMOKE DETECTORS ARE REQUIRED | | IN AIR HANDLING SYSTEMS OVER 2000 CFM. | | 6) BUILDING SECTION 2 DISPLAYS STORAGE | | AREA BUT THE FLOOR PLAN DOES NOT, PLEASE | | CLARIFY. | | 7) PLEASE INDICATE LOCATIONS OF PORTABLE | | FIRE EXTINGUISHERS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-04-10 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-04-10 |
Time |
08:53 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-04-10 |
Time |
08:53 |
Sent To |
|
|
Notes |
2002-04-10 00:00:00 | PROVISO:(MECHANICAL PERMIT 02011322) | | | | FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | WITH NOTIFICATION TO ALARM/STROBE IN | | NORMALLY OCCUPIED AREAS NFPA 90A | | 4-4.4.3. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-13 |
Time |
11:49 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2002-02-13 |
Time |
11:40 |
Sent To |
|
|
Notes |
2002-02-13 00:00:00 | *******************DENIED*************** | | | | 1.INDICATE ON THE PLAN WHAT CODE PLANS | | ARE DESIGNED TO. | | 1997 STANDARD BUILDING CODE OR THE | | 2001 FLORIDA BUILDING CODE | | | | 2.ARE CONDENSATE LINES BEING RUN | | INDIVIDUALLY? | | | | 3.INDICATE TERMINATION OF CONDENSATE. | | AS PER COUNTYWIDE AMMENDMENTS 1994 | | SPC 804.3 #2 & #3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2002-07-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-07-22 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-07-22 |
Time |
11:24 |
Sent To |
|
|
Notes |
2002-06-17 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) FROM PREVIOUS REVIEW: SHT A-1 FLOOR | | DRAIN STILL NOT VENTED PROPERLY. PLEASE | | RESUBMIT WITH PROPER VENTING. | | 2) FROM PREVIOUS REVIEW: SHT A-2 EITHER | | INSTALL A HI-LOW DRINKING FOUNTAIN OR | | SHOW A CUP DISPENSER FOR THOSE WHO HAVE | | DIFFICULTY BENDING OR STOOPING. PLEASE | | ADD TO DETAIL. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2002-06-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-17 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-06-17 |
Time |
15:39 |
Sent To |
|
|
Notes |
2002-06-17 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) FROM PREVIOUS REVIEW. FLOOR DRAIN | | STILL NOT VENTED PROPERLY. FLOOR DRAIN | | SHOULD BE TAKEN OFF FROM A VENTED LINE, | | (LAV) NOT BLDG DRAIN. | | 2) FROM PREVIOUS REVIEW. PROVISIONS FOR | | THOSE WHO HAVE DIFFICULTY BENDING OR | | STOOPING SHALL BE MADE. EITHER INSTALL A | | HI/LOW DRINKING FOUNTAIN, OR INSTALL A | | DRINKING CUP DISPENSER. SHOW ON DETAIL | | SHTA-2 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-04-24 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-24 |
Time |
22:03 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-24 |
Time |
22:03 |
Sent To |
|
|
Notes |
2002-04-24 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) REFERENCE CODE FOR PLUMBING IS STAND- | | ARD PLUMBING CODE 1994, NOT S.F.B.C AS | | INDICATED. | | 2) SHT A-1 FROM PREVIOUS REVIEW, FLOOR | | DRAIN NOT VENTED PROPERLY IN WOMENS REST | | ROOM ON THE SANITARY RISER DIAGRAM. | | PLEASE CORRECT AND RESUBMIT. | | 3) SHT A-2 FROM PREVIOUS REVIEW, DRINK- | | ING FOUNTAIN, NO REFERENCE TO HI - LOW | | TRAJECTORY IN FACBC-97 SEC 4.1.3(10). | | PLEASE SUBMIT DETAIL FOR COMPLIANCE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-02-11 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-02-11 |
Time |
17:30 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-02-11 |
Time |
17:30 |
Sent To |
|
|
Notes |
2002-02-11 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) PLEASE SPECIFY ON PLANS WHICH CODE | | PLANS WERE DESIGNED FOR. | | 2) SHT A-1 SANITARY RISER DIAGRAM DOES | | NOT REFLECT FLOOR PLAN. | | 3) SHT A-1 SANITARY RISER DIAGRAM, FLOOR | | DRAIN IN WOMENS RESTROOM IN NOT VENTED | | PROPERLY. | | 4) SHT A-1 SANT. RISER DIA. WATER COOLER | | SHOWN ON SANT RISER DIA. BY KITCHEN SINK | | NOT ON FLOOR PLAN? | | 5) SHT A-2 PLEASE SHOW CLEAR FLOOR SPACE | | FOR HDCP FIXTURES. | | 6) SHT A-2 DOOR CANNOT SWING INTO CLEAR | | FLOOR SPACE OR TURNING RADIUS. FACBC SEC | | 4.22.2 & 4.22.3 | | 7) SHT A-2 DRINKING FOUNTAIN, IF SINGLE | | DRINKING FOUNTAIN, PROVISIONS SHALL BE | | PROVIDED FOR THOSE WHO HAVE DIFFICULTY | | BENDING OR STOOPING. FACBC SEC 4.1.3(10) | | 8) SHT A-1 WATER RISER DIAGRAM DOES NOT | | REFLECT FLOOR PLAN. W/HEATER NOT BY REST | | ROOM BUT BY KITCHEN. PLEASE SUBMIT RISER | | THAT REFLECTS FLOOR PLAN. | | 9) SHT A-2 BATHROOM EQUIP. #9 MINIMUM OF | | 29" TO BOTTOM OF LAV NOT 28" AS SHOWN. | | 10) PLEASE GIVE DETAIL FOR KITCHEN SINK | | SHOW COMPLIANCE FOR FACBC SEC 4.24. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-01-30 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-01-30 |
Time |
16:24 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|