Plan Review Details - Permit 02011286
Plan Review Stops For Permit 02011286
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-07-05 Cont ID  
Sent By jwitmer Date 2002-07-05 Time 09:18 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-06-07 Cont ID  
Sent By jwitmer Date 2002-06-07 Time 07:56 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2002-06-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02011286
 ADD: 4925 N MILITARY TRAIL
 CONT: TRANSEASTERN
 TEL: 333-4541
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE DESIGN
 PROFESSIONAL OF RECORD. THE FENESTATION
 TESTING LAB REPORT FALLS INTO THIS CATA-
 GORY,(PAIR OF FRENCH DOORS/ SIDELIGHTS)
  
 2) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-03-30 Cont ID  
Sent By jwitmer Date 2002-03-30 Time 12:33 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-30 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02011286
 4925 N MILITARY TRAIL
 CONT: TRANSEASTERN
 TEL: 753-5531
  
 SBC =1997 STANDARD BUILDING CODE
 SECOND REVIEW
 1)- MISSING SOILS REPORT
 2)- SHEET A-3 FRONT ELEVATION INDICATES
 THE FRONT ELEVATION WITH (2) FRENCH
 DOORS ELEVATION 8'-0" THE PRODUCT TEST-
 ING REPORT IS GOOD UP TO7'-0".
 3)- THE SAME SHEET THE REAR ELEVATION IN
 DICATES THE FRENCH DOORS AT THE SAME
 8'-0" ELE. AND THE ADDITION OF SIDELITES
 THE PRODUCT TESTING REPORT NOT ONLY IS
 GOOD FOR THE 7'-0" HEIGTH BUT DOES NOT
 INCLUDE SIDELITES EITHER!
 4)- FAIR HOUSING AS FL ACCES CODE, AT
 LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT
 ACCESSIBLE BUILDINGS, FACILITIES,
 ELEMENTS AND OTHER SPACES THAT ARE ON
 THE SAME SITE.
 FL ACC CODE 4.3.3.2(2)THEFRONT AND
 REAR ELEVATIONS INDICATE CHANGE OF GRADE
 GREATER THAN 1/2".
 THERE APPEARS TO BE A SIDEWALK ON THE
 SITEPLAN THAT CONNECTS THE VOLLEYBALL
 COURT, ALSO THE POOL DECK BUT NOT THE
 TOTLOT.
 5)-COUNTY IMPACT FEES ARE TO BE ASSESS
 ED BEFORE ISSUANCE OF THE PERMIT.
 6)- RADON FEES DUE BEFORE ISSUANCE.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-04 Cont ID  
Sent By jwitmer Date 2002-02-04 Time 12:21 Rev Time 2.50
Received By jwitmer Date 2002-02-04 Time 12:21 Sent To  
Notes
2002-02-04 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02011286
 4925 N MILITARY TRL
 CONT: TRANSEASTERN PROP
 TEL: NOT LISTED
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, THE PLANS DO NOT INDICATE
 UNDER WHAT CODE CRITERIA THEY ARE DESIGN
 ED TO?
 2)- THE DESIGN CRITERIA, PARAMETERS &
 ASSUMPTIONS, MEAN ROOF HEIGTH, BASIC
 WIND VELOCITY PRESSURE, ROOF DEAD LOADS
 MINIMUM SOIL BEARING AND IF ARCH. REVIEW
 ED FOR SHEAR WALLS.
 3)- MISSING SOILS REPORT.
 4)- SHEET A-2 DOORS 1 & 1-A INDICATE
 (W)6'-0"X(H)8'-0", THE PRODUCT APPROVAL
 REPORT IS APPROVED UP TO (H)7'-0".
 5)-DOOR 1-A PRODUCT REPORT IS NOT APPROV
 ED FOR SIDE LITE INSTALATION.
 6)- SHEET A-4 THE GABLE END DETAIL INDI-
 CATES A DETAIL 8/D-1? MISSING.
 7)- WIND PRESSURES TO BE SHOWN ON ELEVAT
 IONS FOR DOORS / WINDOWS (EXTERIOR).
 8)- SHEET A-4 FRONT FRENCH DOORS, SHOULD
 THERE BE A L-1 BETWEEN THE TRANSOM &
 DOOR.
 9)- A-5 KITCHEN: PUBLIC & COMMON USE
 KITCHENS MUST BE USABLE AND MEET THE
 REQUIREMENTS IN THE GUIDELINE FOR KITCH-
 ENS IN ANSI 4.32 COULD BE FOLLOWED.
 FL .ACC. REACH RANGES 4.2.6.
 10)- FAIR HOUSING AS WELL AS FL ACC CODE
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CON-
 NECT ACCESSIBLE BUILDINGS, FACILITIES,
 ELEMENTS AND OTHER SPACES THAT ARE ON
 THE SAME SITE. FL ACC 4.3.2(2).
 THE FRONT AND REAR ELEVATIONS INDICATE
 CHANGE OF GRADE GREATER THAN 1/2".
 THERE APPEARS TO HAVE A SIDEWALK THAT
 CONNECTS THE VOLLEYBALL COURT, ALSO THE
 POOL DECK BUT NOT THE TOT LOT.
 11) COUNTY IMPACT FEESARE TO BE PAID
 BEFORE ISSUANCE OF PERMIT.
 12) RADON FEES ALSO DUE BEFORE ISSUANCE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2002-12-19 Cont ID  
Sent By dpalmer Date 2002-12-19 Time 08:36 Rev Time 0.50
Received By dpalmer Date 2002-12-19 Time 08:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2002-12-03 Cont ID  
Sent By dpalmer Date 2002-12-03 Time 10:16 Rev Time 0.75
Received By dpalmer Date 2002-12-03 Time 08:30 Sent To  
Notes
2002-12-03 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE, NOW AHU HAS BEEN
 ADDED TO PANEL "A" BUT IS STILL SHOWN
 ON PANEL "C"? PLEASE CLARIFY.PLEASE ALSO
 NOTE, OCP IS SHOWN AT 2-P 60 FOR 5KW
 HEAT. PLEASE VERFIY MAX OCP FOR 5KW.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 LOAD SHOWN AND LOAD SHOWN ON LOAD CALCS
 FOR PANEL "C".PANEL "C" SHOWS 31.04KVA?
  
 3)NOTE: PLEASE NOTE, IF LOADS ARE
 FIGURED AT ALL CONNECTED LOADS THEN
 IT WILL TAKE IT OVER 400A'S.
 PLEASE SEE ART 220 FOR METHODS AND
 DERATING FACTORS PERMITTED.
  
 4)NOTE: PLEASE SEE 1/2" CONDUITS SHOWN
 FROM METER TO PANEL "A' AND METER TO FPL
  
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-11-21 Cont ID  
Sent By dpalmer Date 2002-11-21 Time 15:03 Rev Time 0.50
Received By dpalmer Date 2002-11-21 Time 15:03 Sent To  
Notes
2002-11-21 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, PER 700-12E,
 EM/EX LTS NEED TO BE ON THE SAME
 CIRCUITS AS NORMAL LIGHTING IN THOSE
 AREAS.
 PLEASE CORRELATE CIRCUITS AND PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE NOTE, ONLY ONE AHU IS
 SHOWN ON PANEL "A".
 TWO AIR COMP #1`S SHOWN.
  
 3)NOTE: PLEASE NOTE KW LOAD SHOWN FOR
 COND UNITS. PLEASE VERIFY LOADS AND
 CORRELATE OCP PER 424-3.
  
 4)NOTE: PLEASE LABEL PANELS ACCORDING TO
 PANEL SCHEDULES. "A,B,C".
  
 5)NOTE: PLEASE VERIFY 2-SD`S SHOWN
 OUTSIDE MECH CLOSET? FIRE REVIEW COMMENT
 .
  
 6)NOTE: PLEASE RE-CONFIGURE LOAD
 CALCULATIONS PER NEC220-3,220-10,
 220-11,220-13 ETC. PLEASE NOTE, LOADS
 SHOWN FOR PANEL "C" SHOWN AT 4.29AMPS.
 IF LOADS ARE ADDED AS SHOWN, SERVICE
 LOAD COMES UP TO 450.875 WHICH EXCEEDS
 SERVICE SIZE/WIRE ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-11-21 Cont ID  
Sent By dpalmer Date 2002-07-24 Time 05:55 Rev Time 0.00
Received By dpalmer Date 2002-07-24 Time 05:55 Sent To  
Notes
2002-07-24 00:00:00********** NOTE ********
  
 PLANS NEED TO HAVE ALL OLD SHEETS TAKEN
 OUT OF SETS AND ONLY HAVE SHEETS NEEDED
 FOR PERMITTING.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-07-24 Cont ID  
Sent By dpalmer Date 2002-07-24 Time 05:54 Rev Time 0.00
Received By dpalmer Date 2002-07-23 Time 19:05 Sent To  
Notes
2002-07-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE NECESSARY CHANGES ON THE
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE SERVICE ENTRANCE CONDUCTORS IN TH
 E 2 1/2"CONDUIT EXCEED PERMISSIBLE CONDU
 IT FILL PER APPENDIX "C",CHAPTER 9.THIS
 IS THE SAME COMMENT THAT WAS ON THE NOTE
 S FROM THE PREVIOUS REVIEW,IF THERE IS A
 QUESTION ON THIS ,PLEASE CALL.
  
 2} THE RISER DIAGRAM SHOWS 3/0,S FROM 30
 0 AMP MAIN,PLEASE CLARIFY.SAME NOTE AS P
 REVIOUS REVIEW.
  
 3} MISSING EQUIPMENT GROUND CONDUCTOR BE
 TWEEN BOTH MAIN DISCONNECTS AND PANELS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-06-05 Cont ID  
Sent By dpalmer Date 2002-06-05 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2002-06-05 Time 14:47 Sent To  
Notes
2002-06-05 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE NOTE SERVICE ENTRANCE
 CONDUCTORS HAVE NOW CHANGED, PLEASE NOTE
 CONDUIT FILL IN NEC TABLE, 6 350MCM IN
 A 2 1/2 CONDUIT. CHAPTER 9
  
 2)NOTE: PLEASE CLARIFY 350MCMS GOING
 THROUGHT 300A DISC AND FEEDING 100A
 DISC. PLEASE VERFIY 350MCM FOR 100AMPS??
 YET RISER SHOWS 3/0`S FROM 300MAIN BRKR
 TO 100A MAIN?? PLEASE CLARIFY HOW
 WIRE SIZES APPEAR TO CHANGE FROM 350MCM
 TO 3/0`S? IN 300A DISC.
 PLEASE ALSO NOTE 3/0`S OR 350MCM BEING
 ABLE TO FIT UNDER 100A MCB?240-6/310-
 -16.215-5 ETC.
 3)NOTE: PLEASE NOTE STILL MISSING
 EQUIPMENT GROUNDING BETWEEN BOTH MAIN
 DISC`S AND PANELS. 250-122
  
 4)NOTE: PLEASE SEE ATTACHMENT OF FS/FAC
 553-79 (2)(B) IN REFERENCE TO PLANS
 BEING REVIEW FOR THE SAME COMMENTS AFTER
 3RD REVIEW. SEE ATTACHED.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-04-05 Cont ID  
Sent By dpalmer Date 2002-04-05 Time 07:03 Rev Time 0.00
Received By dpalmer Date 2002-04-05 Time 07:03 Sent To  
Notes
2002-04-05 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT CONDUCTOR SIZE
 IS STILL NOT CORRECT. PLEASE NOTE THAT
 RISER DIAGRAM IS SHOWING 1/0`S FOR A
 200AMP SERVICE. PLEASE SEE 310-16 FOR
 CORRECT SIZING.
  
 2)NOTE: PLEASE NOTE THAT MISSING/CLARIFY
 EQUIPMENT GROUNDING METHOD/CONDCUTOR
 BETWEEN MAIN AND PANEL. SIZE PER 250-122
  
 3)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT-
 -ING #`S ARE TO BE SHOWN ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE.
  
 4)NOTE: PLEASE CLARIFY MANY LOADS ON
 PANEL SCHEDULE FOR 1-POLE 20A BRKRS
 SHOWN AT 2.4KW? PLEASE NOTE THAT,AT THAT
 LOAD, IT TAKE IT PAST THE NORMAL 80%
 LOADING OF A BRKR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-05 Cont ID  
Sent By dpalmer Date 2002-02-05 Time 12:45 Rev Time 0.00
Received By dpalmer Date 2002-02-05 Time 12:45 Sent To  
Notes
2002-02-05 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THE CONDUCTOR SIZE
 SHOWN FOR BOTH 200AMP MAINS? PLEASE SEE
 310-16 FOR CORRECT WIRE SIZE.
 PLEASE NOTE THAT WITH CONDUCTOR SIZE
 CHANGING THEN CONDUIT SIZE IS REQ`D TO
 BE INCREASED.
  
 2)NOTE: PLEASE NOTE THAT PLANS ONLY
 SHOW ONE MAIN WITH METER ON THE OUTSIDE
 OF BLDG. PLEASE SHOW LOCATION OF SECOND
 DISCONNECT.
  
 3)NOTE: PLEASE NOTE 373-8 FOR USE OF THE
 MAIN AS RACEWAY.
  
 4)NOTE: PLEASE NOTE THAT PANEL "B" IS
 NOT SHOWN ON PLANS "PLEASE CLARIFY/ SHOW
 ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-01-31 Cont ID  
Sent By mamini Date 2002-01-31 Time 16:28 Rev Time 1.00
Received By mamini Date 2002-01-31 Time 16:27 Sent To  
Notes
2002-01-31 00:00:00N/A
 1. SEE PERMIT # 01101791 AND 01101793.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-04-09 Cont ID  
Sent By mcarsill Date 2002-04-09 Time 14:01 Rev Time 0.00
Received By mcarsill Date 2002-04-09 Time 14:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-01 Cont ID  
Sent By mcarsill Date 2002-02-01 Time 09:09 Rev Time 0.00
Received By mcarsill Date 2002-02-01 Time 09:09 Sent To  
Notes
2002-02-01 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 3) MECHANICAL ROOM TO BE SEPARATED BY
 AT LEAST ONE HOUR FROM THE REMAINDER
 OF THE BUILDING.
 4) PLEASE INDICATE LOCATIONS OF FIRE
 HYDRANTS IN RELATION TO THE PROPOSED
 CLUBHOUSE.
 5) DUCT SMOKE DETECTORS ARE REQUIRED
 IN AIR HANDLING SYSTEMS OVER 2000 CFM.
 6) BUILDING SECTION 2 DISPLAYS STORAGE
 AREA BUT THE FLOOR PLAN DOES NOT, PLEASE
 CLARIFY.
 7) PLEASE INDICATE LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-10 Cont ID  
Sent By pkrauss Date 2002-04-10 Time 08:53 Rev Time 0.40
Received By pkrauss Date 2002-04-10 Time 08:53 Sent To  
Notes
2002-04-10 00:00:00PROVISO:(MECHANICAL PERMIT 02011322)
  
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS NFPA 90A
 4-4.4.3.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-13 Cont ID  
Sent By pkrauss Date 2002-02-13 Time 11:49 Rev Time 0.45
Received By pkrauss Date 2002-02-13 Time 11:40 Sent To  
Notes
2002-02-13 00:00:00*******************DENIED***************
  
 1.INDICATE ON THE PLAN WHAT CODE PLANS
 ARE DESIGNED TO.
 1997 STANDARD BUILDING CODE OR THE
 2001 FLORIDA BUILDING CODE
  
 2.ARE CONDENSATE LINES BEING RUN
 INDIVIDUALLY?
  
 3.INDICATE TERMINATION OF CONDENSATE.
 AS PER COUNTYWIDE AMMENDMENTS 1994
 SPC 804.3 #2 & #3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-07-22 Cont ID  
Sent By kstevens Date 2002-07-22 Time 11:24 Rev Time 0.00
Received By kstevens Date 2002-07-22 Time 11:24 Sent To  
Notes
2002-06-17 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) FROM PREVIOUS REVIEW: SHT A-1 FLOOR
 DRAIN STILL NOT VENTED PROPERLY. PLEASE
 RESUBMIT WITH PROPER VENTING.
 2) FROM PREVIOUS REVIEW: SHT A-2 EITHER
 INSTALL A HI-LOW DRINKING FOUNTAIN OR
 SHOW A CUP DISPENSER FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. PLEASE
 ADD TO DETAIL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-06-17 Cont ID  
Sent By kstevens Date 2002-06-17 Time 15:39 Rev Time 0.00
Received By kstevens Date 2002-06-17 Time 15:39 Sent To  
Notes
2002-06-17 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) FROM PREVIOUS REVIEW. FLOOR DRAIN
 STILL NOT VENTED PROPERLY. FLOOR DRAIN
 SHOULD BE TAKEN OFF FROM A VENTED LINE,
 (LAV) NOT BLDG DRAIN.
 2) FROM PREVIOUS REVIEW. PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING SHALL BE MADE. EITHER INSTALL A
 HI/LOW DRINKING FOUNTAIN, OR INSTALL A
 DRINKING CUP DISPENSER. SHOW ON DETAIL
 SHTA-2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-24 Cont ID  
Sent By kstevens Date 2002-04-24 Time 22:03 Rev Time 0.00
Received By kstevens Date 2002-04-24 Time 22:03 Sent To  
Notes
2002-04-24 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) REFERENCE CODE FOR PLUMBING IS STAND-
 ARD PLUMBING CODE 1994, NOT S.F.B.C AS
 INDICATED.
 2) SHT A-1 FROM PREVIOUS REVIEW, FLOOR
 DRAIN NOT VENTED PROPERLY IN WOMENS REST
 ROOM ON THE SANITARY RISER DIAGRAM.
 PLEASE CORRECT AND RESUBMIT.
 3) SHT A-2 FROM PREVIOUS REVIEW, DRINK-
 ING FOUNTAIN, NO REFERENCE TO HI - LOW
 TRAJECTORY IN FACBC-97 SEC 4.1.3(10).
 PLEASE SUBMIT DETAIL FOR COMPLIANCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-11 Cont ID  
Sent By kstevens Date 2002-02-11 Time 17:30 Rev Time 0.00
Received By kstevens Date 2002-02-11 Time 17:30 Sent To  
Notes
2002-02-11 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLEASE SPECIFY ON PLANS WHICH CODE
 PLANS WERE DESIGNED FOR.
 2) SHT A-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT FLOOR PLAN.
 3) SHT A-1 SANITARY RISER DIAGRAM, FLOOR
 DRAIN IN WOMENS RESTROOM IN NOT VENTED
 PROPERLY.
 4) SHT A-1 SANT. RISER DIA. WATER COOLER
 SHOWN ON SANT RISER DIA. BY KITCHEN SINK
 NOT ON FLOOR PLAN?
 5) SHT A-2 PLEASE SHOW CLEAR FLOOR SPACE
 FOR HDCP FIXTURES.
 6) SHT A-2 DOOR CANNOT SWING INTO CLEAR
 FLOOR SPACE OR TURNING RADIUS. FACBC SEC
 4.22.2 & 4.22.3
 7) SHT A-2 DRINKING FOUNTAIN, IF SINGLE
 DRINKING FOUNTAIN, PROVISIONS SHALL BE
 PROVIDED FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING. FACBC SEC 4.1.3(10)
 8) SHT A-1 WATER RISER DIAGRAM DOES NOT
 REFLECT FLOOR PLAN. W/HEATER NOT BY REST
 ROOM BUT BY KITCHEN. PLEASE SUBMIT RISER
 THAT REFLECTS FLOOR PLAN.
 9) SHT A-2 BATHROOM EQUIP. #9 MINIMUM OF
 29" TO BOTTOM OF LAV NOT 28" AS SHOWN.
 10) PLEASE GIVE DETAIL FOR KITCHEN SINK
 SHOW COMPLIANCE FOR FACBC SEC 4.24.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-30 Cont ID  
Sent By sgraham Date 2002-01-30 Time 16:24 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***