Plan Review Stops For Permit 02011165 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-01-29 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-29 |
Time |
07:58 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-01-29 |
Time |
07:40 |
Sent To |
|
|
Notes |
2002-01-29 00:00:00 | | | | | PROVISO: | | | | ATTIC ACCESS SHALL BE NO LESS THAN 22" X | | 36" CONTINUOUS FROM THE OPENING TO THE | | EQUIPMENT AND ITS CONTROLS. (1997 SMC | | 304.4.1) | | | | AHU SHALL HAVE AN ACCESSIBLE DISCONNECT | | SWITCH, A 110-120 VOLT A/C GROUNDING | | TYPE CONVIENCE OUTLET, AND A LIGHT | | LOCATED ON THE SERVICE SIDE OF THE | | EQUIPMENT CONTROLLED BY A SWITCH AT THE | | ACCESS OPENING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
|