Plan Review Details - Permit 02011165
Plan Review Stops For Permit 02011165
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-01-29 Cont ID  
Sent By pkrauss Date 2002-01-29 Time 07:58 Rev Time 0.40
Received By pkrauss Date 2002-01-29 Time 07:40 Sent To  
Notes
2002-01-29 00:00:00 
  
 PROVISO:
  
 ATTIC ACCESS SHALL BE NO LESS THAN 22" X
 36" CONTINUOUS FROM THE OPENING TO THE
 EQUIPMENT AND ITS CONTROLS. (1997 SMC
 304.4.1)
  
 AHU SHALL HAVE AN ACCESSIBLE DISCONNECT
 SWITCH, A 110-120 VOLT A/C GROUNDING
 TYPE CONVIENCE OUTLET, AND A LIGHT
 LOCATED ON THE SERVICE SIDE OF THE
 EQUIPMENT CONTROLLED BY A SWITCH AT THE
 ACCESS OPENING.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.