Plan Review Details - Permit 02011150
Plan Review Stops For Permit 02011150 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-05-09 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2002-05-09 |
Time |
16:33 |
Rev Time |
0.25 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-03-18 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2002-03-18 |
Time |
09:13 |
Rev Time |
0.75 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-18 00:00:00 | *************PROVISO************ | | | | THE FOLLOWING ITEMS MUST BE CORRECTED: | | | | 1. ALL DRAWING MUST REFERENCE THE FBC 2 | | 2001. | | | | 2. A DETAIL OF THE CONCRETE SLAB FOR POO | | L EQUIPMENT AND ANCHORING DETAIL SHOWN. | | | | | | ALL FUTURE PERMIT APPLICATIONS FOR POOL | | MUST BE CORRECTED AND SHOW THE CORRECT I | | NFORMATION.WE WILL NO LONGER MAKE CORR | | ECTIONS ON PLANS & ISSUE WITH PROVISO DU | | E TO REFERENCES OF IMPROPER CODES. | | | | ANY QUESTIONS PLEASE CALL: | | LEA SMITH, BUILDING PLANS EXAMINER | | 659-8096 EXT. 8394 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-05-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-05-06 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-05-06 |
Time |
07:55 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-03-18 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2002-03-18 |
Time |
09:18 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
2002-03-04 |
Time |
14:55 |
Sent To |
|
|
Notes |
2002-03-18 00:00:00 | PER WRT 3/4/02 SEE APPLICATION |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-05-04 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-05-06 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-04 |
Time |
09:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-04-12 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-12 |
Time |
19:25 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-12 |
Time |
19:25 |
Sent To |
|
|
Notes |
2002-04-12 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | 1) CHANGES TO A SIGNED AND SEALED SET OF | | PLANS SHALL NOT BE PENNED IN. NEW PLANS | | WITH CHANGES ON THEM REQUIRED. | | 2) GENERAL NOTES #14,PLEASE ADD TO NOTES | | FBC-2001 SEC 424.2.6.1 ENGINEERING | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | ANSI/NSPI-5. | | 3) | | FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | 4) | | FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON | | WATER SERVICE. (ADD TO NOTES) | | 5) | | FBC-2001 SEC 424.2.13.2JOINTS AND CON- | | NECTIONS, FBC PLMG SEC 605.21, PURPLE | | PRIMER REQUIRED ON PVC PIPING. (ADD TO | | NOTES) | | | | ADD ABOVE TO NOTES, GIVE DETAILS, OR | | SUBMITTALS FOR PLAN REVIEW. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-03-03 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2002-03-03 |
Time |
05:56 |
Rev Time |
1.50 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-03 00:00:00 | PLUMBING PLAN REVIEW,FBC 2001, DENIED | | (1) GENERAL NOTES (14) DESIGN IS NOT BY | | WPB SWIMMING POOL CODE, SEE FBC 2001". | | SEC 424.2.6 | | (2) SEC 424.2.6.6.2 SUCTION FITTINGS, | | CLEANING LINE. | | (3) SEC 424..2.7.2 SHOW A DETAIL OF MOUN | | TING AND ANCHORING POOL,SPA EQUIPMENT. | | (4) 424.2.9 WATER SUPPLY,LOCAL ORDINANCE | | #2853-95 BACK FLOW PREVENTER REQUIRED ON | | WATER SERVICE. | | (5) SEC 424.2.13.2 JOINTS, CONNECTIONS, | | PURPLE PRIMER REQUIRED ON PVC PIPING. | | FBC-2001 PLUMBING SEC605.21 | | END OF COMMENTSPAUL SCHMITZ | | QUESTIONS561-659-8096X8233 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2002-02-15 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-02-15 |
Time |
08:29 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2002-01-30 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-01-30 |
Time |
10:45 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|