2002-01-29 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| TO,DURING AND AFTER CONSTRUCTION. |
| 2) FIRE HYDRANTS ARE REQUIRED BETWEEN |
| 300-500 FEET APART. |
| 3) A FIRE HYDRANT IS REQUIRED UPON |
| APPROACH TO THE CLUBHOUSE. |
| 4) CLEARANCES OF 7 1/2 FEET TO THE SIDES |
| AND FRONT OF FIRE HYDRANTS ARE |
| REQUIRED. A MINIMUM OF AT LEAST 4 FEET |
| ARE REQUIRED TO THE REAR OF THE FIRE |
| HYDRANTS. |
| 5) THE ENTRYWAY NEAR THE CLUBHOUSE DOES |
| NOT MEET MINIMUM FIRE CODE REQUIREMENTS. |
| A MINIMUM WIDTH OF 20 FEET IS TO BE |
| PROVIDED. VERTICAL CLEARANCES FOR FIRE |
| APPARATUS TO PASS UNDERNEATH MUST BE |
| AT LEAST 13 FEET 6 INCHES HIGH. FIRE |
| DEPARTMENT ACCESS IS TO BE PROVIDED |
| THRU ANY SECURITY FEATURES PLANNED. |
| PLEASE INDICATE HOW THIS WILL BE |
| ACCOMPLISHED. |
| 6) ELECTRONIC SWITCHES WILL BE REQUIRED |
| ON THE OS&Y VALVES FOR SUPERVISION |
| PURPOSES. |
| 7) ALL BUILDINGS SHALL HAVE AT LEAST |
| ONE ELEVATION ACCESSIBLE TO FIRE AND |
| PARAMEDICAL EQUIPMENT AND PROVIDE A |
| LOAD OF AT LEAST 32 TONS. |
| 8) VALVES ON THE FIRE LINE SHALL BE |
| POST INDICATOR TYPE VALVES EXCEPT VALVES |
| USED FOR SECTIONING. |
| 9) PORTACACHERE FOR THE ALF MUST PROVIDE |
| A VERTICAL CLEARANCE OF AT LEAST 13 FEET |
| 6 INCHES HIGH. |
| |