Plan Review Details - Permit 02011115
Plan Review Stops For Permit 02011115
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-01-29 Cont ID  
Sent By mamini Date 2002-01-29 Time 09:44 Rev Time 0.00
Received By mamini Date 2002-01-29 Time 09:44 Sent To  
Notes
2002-01-29 00:00:00PASSED WITH PROVISOS:
 1. A SEPARATE PERMIT FROM F.D.O.T FOR
 CONSTRUCTION OF RIGHT TURN LANE ON
 OKEECHOBEE BLVD. BY GC WILL BE REQUIRED.
 2. GC TO CALL RODNEY COMPO FOR
 INSTALLATION/ INSPECTION OF WATER/GREASE
 SEPARATORS, 837-4051 EXT. 4074
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-29 Cont ID  
Sent By mcarsill Date 2002-01-29 Time 09:22 Rev Time 0.00
Received By mcarsill Date 2002-01-29 Time 09:22 Sent To  
Notes
2002-01-29 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
 2) FIRE HYDRANTS ARE REQUIRED BETWEEN
 300-500 FEET APART.
 3) A FIRE HYDRANT IS REQUIRED UPON
 APPROACH TO THE CLUBHOUSE.
 4) CLEARANCES OF 7 1/2 FEET TO THE SIDES
 AND FRONT OF FIRE HYDRANTS ARE
 REQUIRED. A MINIMUM OF AT LEAST 4 FEET
 ARE REQUIRED TO THE REAR OF THE FIRE
 HYDRANTS.
 5) THE ENTRYWAY NEAR THE CLUBHOUSE DOES
 NOT MEET MINIMUM FIRE CODE REQUIREMENTS.
 A MINIMUM WIDTH OF 20 FEET IS TO BE
 PROVIDED. VERTICAL CLEARANCES FOR FIRE
 APPARATUS TO PASS UNDERNEATH MUST BE
 AT LEAST 13 FEET 6 INCHES HIGH. FIRE
 DEPARTMENT ACCESS IS TO BE PROVIDED
 THRU ANY SECURITY FEATURES PLANNED.
 PLEASE INDICATE HOW THIS WILL BE
 ACCOMPLISHED.
 6) ELECTRONIC SWITCHES WILL BE REQUIRED
 ON THE OS&Y VALVES FOR SUPERVISION
 PURPOSES.
 7) ALL BUILDINGS SHALL HAVE AT LEAST
 ONE ELEVATION ACCESSIBLE TO FIRE AND
 PARAMEDICAL EQUIPMENT AND PROVIDE A
 LOAD OF AT LEAST 32 TONS.
 8) VALVES ON THE FIRE LINE SHALL BE
 POST INDICATOR TYPE VALVES EXCEPT VALVES
 USED FOR SECTIONING.
 9) PORTACACHERE FOR THE ALF MUST PROVIDE
 A VERTICAL CLEARANCE OF AT LEAST 13 FEET
 6 INCHES HIGH.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910