Plan Review Details - Permit 02010625
Plan Review Stops For Permit 02010625 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-01-23 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-01-23 |
Time |
13:18 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
N |
Date |
2002-01-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-23 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-01-23 |
Time |
09:10 |
Sent To |
|
|
Notes |
2002-01-23 00:00:00 | *********** NOTE************* | | | | PLEASE NOTE THAT ALL ELECTRICAL INTERIOR | | AND EXTERIOR WERE SUBMITTED UNDER | | SEPARATE PERMITS FROM VANS ELECTRIC AND | | HAVE BEEN ISSUED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-01-23 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-01-23 |
Time |
12:43 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-01-23 |
Time |
12:43 |
Sent To |
|
|
Notes |
2002-01-23 00:00:00 | 1) NO COOKING THAT PRODUCES SMOKE | | OR GREASE LADEN VAPORS IS PERMITTED | | UNLESS AN APPROVED HOOD,DUCT AND | | EXTINGUISHING SYSTEM ARE PROVIDED. | | SEPARATE PLANS AND PERMITS REQUIRED. | | 2) A PORTABLE FIRE EXTINGUISHER IS | | TO BE PROVIDED. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2002-01-23 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-23 |
Time |
13:33 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2002-01-23 |
Time |
13:32 |
Sent To |
|
|
Notes |
2002-01-23 00:00:00 | HEDRICK BROTHERS CONSTRUCTION REMOVED | | MECHANICAL PLANS....TO HAVE ENGINEER | | RE-DESIGN MECHANICAL PLANS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-01-23 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-23 |
Time |
09:09 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2002-01-23 |
Time |
09:08 |
Sent To |
|
|
Notes |
2002-01-23 00:00:00 | | | MECHANICAL PERMIT 02010352 | | | | AS PER THE FLORIDA ENERGY CODE | | 407.1.ABCD.3.3, THE CONDENSING COIL | | SHALL NOT BE INSTALLED IN THE COOL AIR | | STREAM OF ANOTHER AIR CONDITIONING UNIT. | | | | APPLIANCES LISTED FOR OUTDOOR | | INSTALLATIONS SHALL NOT BE INSTALLED | | INSIDE A BUILDING AS PER 1997 SMC | | 304.2.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 EXT | | 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-01-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-01-23 |
Time |
10:10 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-01-23 |
Time |
10:09 |
Sent To |
|
|
Notes |
2002-01-23 00:00:00 | PASSED/PROVISO | | REFERENCE: SPC-94 | | | | NO HORIZONTAL DRY VENTS. |
|
|
|