Plan Review Details - Permit 02010610
Plan Review Stops For Permit 02010610
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-01 Cont ID  
Sent By btrobaug Date 2002-03-01 Time 10:50 Rev Time 0.00
Received By btrobaug Date 2002-03-01 Time 07:11 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-30 Cont ID  
Sent By btrobaug Date 2002-01-30 Time 18:43 Rev Time 0.00
Received By btrobaug Date 2002-01-30 Time 18:33 Sent To R
Notes
2002-01-30 00:00:00*****************UNSAT!*****************
 1) BEDROOM #1 RECETACLE SPACING PER
 210-52(A).
  
 2) SMOKE DETECTORS PER NFPA-72 2-5.2.1.6
  
 3) LOCATION OF A/C CONDENSOR AND GFI ?
  
 PLEASE REVISE FOR ABOVE AND RESUBMIT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561) 659-8096 EXT.8392

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-01-30 Cont ID  
Sent By hmoser Date 2002-01-30 Time 17:58 Rev Time 0.33
Received By hmoser Date 2002-01-30 Time 17:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-01-26 Cont ID  
Sent By jleech Date 2002-01-26 Time 11:02 Rev Time 0.25
Received By jleech Date 2002-01-26 Time 11:02 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-03-27 Cont ID  
Sent By rmcdouga Date 2002-03-27 Time 07:46 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-03-27 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR DOORS
 - STRUCTURAL WINDOW MULLIONS

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-03-05 Cont ID  
Sent By rmcdouga Date 2002-03-05 Time 15:13 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-03-05 00:00:00*************BUILDING DENIED************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FORM 600A-97 HAS THE WRONG ADDRESS
 AND IS REQUIRED TO BE SIGNED AND DATED
 BY THE OWNER/AGENT. PLEASE CORRECT.
  
 3) PLEASE CORRECT THE DESIGN DATA ON
 SHEET A-1 TO REFER TO THE 1997 STANDARD
 BUILDING CODE.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL WINDOW MULLIONS
 - EXTERIOR DOORS
  
 5) THE SITE SPECIFIC PRODUCT APPROVAL
 SUBMITTAL FORM FOR THE NORANDEX SINGLE-
 HUNG WINDOWS IS REQUIRED TO BE SEALED
 AND DATED BY THE ENGINEER CERTIFYING THE
 PRODUCT. THE ARCHITECT IS REQUIRED TO
 INDICATE DATE IN ADDITION TO SIGNING AND
 SEALING THE FORM.
  
 6) THE BEDROOM WINDOWS MUST PROVIDE A
 MINIMUM NET CLEAR OPENING HEIGHT OF 24"
 TO COMPLY WITH 1997 SBC 1005.4. THE
 SH 24 WINDOWS TYPICALLY DO NOT PROVIDE
 THIS. PLEASE PROVIDE CUT SHEETS FROM THE
 WINDOW MANUFACTURER WHICH INDICATE THAT
 THE OPENING REQUIREMENTS WILL BE MET.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-02-11 Cont ID  
Sent By btrobaug Date 2002-03-01 Time 10:50 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-02-11 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE SOIL TEST PER SEC. 1804.2.2
 OF CITY AMENDMENTS TO 1997 SBC.
  
 4) REVIEW LOCATIONS OF REINFORCED FILLED
 CELLS ON SHEETS A-1 AND A-2, SOME DOOR &
 WINDOW OPENINGS ARE INDICATED WITHOUT
 REINFORCING ON EACH SIDE OF OPENING. THE
 6FT. MAXIMUM O.C. SPACING INDICATED ON
 SHEET A-1 APPEARS TO BE EXCEEDED IN
 SEVERAL AREAS.
  
 5) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 6) THE DESIGN DATA ON SHEET A-1 SITES
 THE 1994 STANDARD BUILDING CODE. THE
 CORRECT EDITION IS THE 1997 STANDARD
 BUILDING CODE. PLEASE CORRECT.
 NOTE: APPLICATIONS FOR PERMITS SUBMITTED
 ON OR AFTER MARCH 1, 2002, ARE REQUIRED
 TO BE DESIGNED TO COMPLY WITH THE 2001
 SOUTH FLORIDA BUILDING CODE.
  
 7) THE TRUSS ANCHORS GIVEN ON SHEET A-1
 DO NOT CLEARLY INDICATED WHICH TRUSSES
 THEY WILL BE USED ON. PLEASE CLARIFY.
 THE ETA TRUSS ANCHORS INDICATED ON THE
 PLANS ARE NO LONGER LISTED IN THE
 CURRENT (2002) SIMPSON CATALOG. PLEASE
 REVISE PLANS TO SHOW MODEL #S FOR
 CURRENTLY LISTED TRUSS ANCHORS.
  
 8)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL WINDOW MULLIONS
 - EXTERIOR DOORS
  
 9) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE DESIGN
 PROFESSIONAL OF RECORD ON THE PROPER
 FORM. SEE ATTACHED.
  
 10) BEDROOM WINDOWS MUST COMPLY WITH
 97 SBC 1005.4 FOR EMERGENCY ESCAPE AND
 RESCUE OPENINGS. THE MINIMUM NET CLEAR
 OPENING HEIGHT IS 24 INCHES AND SH 24
 WINDOWS DO NOT PROVIDE THIS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-23 Cont ID  
Sent By sgraham Date 2002-01-23 Time 08:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***