2002-02-11 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) PROVIDE SOIL TEST PER SEC. 1804.2.2 |
| OF CITY AMENDMENTS TO 1997 SBC. |
| |
| 4) REVIEW LOCATIONS OF REINFORCED FILLED |
| CELLS ON SHEETS A-1 AND A-2, SOME DOOR & |
| WINDOW OPENINGS ARE INDICATED WITHOUT |
| REINFORCING ON EACH SIDE OF OPENING. THE |
| 6FT. MAXIMUM O.C. SPACING INDICATED ON |
| SHEET A-1 APPEARS TO BE EXCEEDED IN |
| SEVERAL AREAS. |
| |
| 5) PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILDING |
| CONSTRUCTION. |
| |
| 6) THE DESIGN DATA ON SHEET A-1 SITES |
| THE 1994 STANDARD BUILDING CODE. THE |
| CORRECT EDITION IS THE 1997 STANDARD |
| BUILDING CODE. PLEASE CORRECT. |
| NOTE: APPLICATIONS FOR PERMITS SUBMITTED |
| ON OR AFTER MARCH 1, 2002, ARE REQUIRED |
| TO BE DESIGNED TO COMPLY WITH THE 2001 |
| SOUTH FLORIDA BUILDING CODE. |
| |
| 7) THE TRUSS ANCHORS GIVEN ON SHEET A-1 |
| DO NOT CLEARLY INDICATED WHICH TRUSSES |
| THEY WILL BE USED ON. PLEASE CLARIFY. |
| THE ETA TRUSS ANCHORS INDICATED ON THE |
| PLANS ARE NO LONGER LISTED IN THE |
| CURRENT (2002) SIMPSON CATALOG. PLEASE |
| REVISE PLANS TO SHOW MODEL #S FOR |
| CURRENTLY LISTED TRUSS ANCHORS. |
| |
| 8)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - STRUCTURAL WINDOW MULLIONS |
| - EXTERIOR DOORS |
| |
| 9) SITE SPECIFIC ENGINEERING (PRODUCT |
| APPROVAL) REQUIRES THE WET SIGNATURE, |
| DATE AND EMBOSSED SEAL OF THE ENGINEER |
| CERTIFYING THE PRODUCT AND OF THE DESIGN |
| PROFESSIONAL OF RECORD ON THE PROPER |
| FORM. SEE ATTACHED. |
| |
| 10) BEDROOM WINDOWS MUST COMPLY WITH |
| 97 SBC 1005.4 FOR EMERGENCY ESCAPE AND |
| RESCUE OPENINGS. THE MINIMUM NET CLEAR |
| OPENING HEIGHT IS 24 INCHES AND SH 24 |
| WINDOWS DO NOT PROVIDE THIS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |