Plan Review Details - Permit 02010579
Plan Review Stops For Permit 02010579
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-03-18 Cont ID  
Sent By rmcdouga Date 2002-03-18 Time 15:29 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-02-25 Cont ID  
Sent By pkrauss Date 2002-03-18 Time 07:56 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-02-25 00:00:00*************BUILDING UNSAT*************
  
 1) THE DESIGNER OF RECORD (ENGINEER) IS
 REQUIRED TO INITIAL AND DATE THE HAND
 WRITTEN CHANGES TO THE PLANS.
  
 2)PROVIDE A KEY PLAN AND AN INSTALLATION
 SCHEDULE FOR THE HURRICANE PANELS.
 INDICATE THE METHOD OF INSTALLATION AND
 TYPE OF FASTENER THAT WILL BE USED BY
 CIRCLING THEM ON THE APPROVAL DRAWINGS.
 INDICATE ON THE PLANS THAT ADEQUATE
 SUBSTRATE WILL BE PROVIDED FOR THE
 ATTACHMENT OF THE STORM PANELS.
  
 3) THE STRAPPING DIAGRAMS FOR OPENINGS
 THAT ARE STAPLED TO THE PLANS ARE
 REQUIRED TO BE SIGNED SEALED AND DATE BY
 THE DESIGNER OF RECORD (ENGINEER).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-24 Cont ID  
Sent By pkrauss Date 2002-02-22 Time 09:50 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-01-24 00:00:00*************BUILDING DENIED************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) FL ENERGY CODE COMPLIANCE FORM MUST
 BE SIGNED AND DATED BY THE OWNER OR
 AGENT.
  
 4) CORRECT ENERGY FORM TO INDICATE THE
 RAISED WOOD FLOOR AND R-11 INSULATION
 THAT IS REQUIRED.
  
 5) INDICATE R-11 INSULATION AT RAISED
 WOOD FLOOR SYSTEM ON THE PLANS.
  
 6) PROVIDE CRAWL SPACE VENTILATION PER
 97 SBC 1804.6.2.1.
  
 7) INDICATE STEM WALL BOND BEAM WITH
 HORIZONTAL REINFORCEMENT. INDICATE THE
 SIZE AND SPACING OF THE VERTICLE
 REINFORCEMENT BETWEEN THE BOND BEAM AND
 THE FOOTING.
  
 8) PROVIDE ATTIC ACCESS. 97 SBC 2309.6
  
 9)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - HARDY BOARD SIDING
 - FRENCH DOORS
 - ROOFING MATERIAL (OR SUBMIT UNDER A
 SEPARATE PERMIT)
  
 10) PROVIDE AN UPDATED PRODUCT APPROVAL
 (SBCCI REPORT NO. 9756A) FOR STORM
 PANELS. PROVIDE AN INSTALLATION SCHEDULE
 AND KEY PLAN. INDICATE THE TYPE ANCHORS
 THAT WILL BE USED ON SHEET 4 OF THE
 STORM PANEL DRAWINGS.
  
 11) PROVIDE A DOOR WITH A 29" CLEAR
 OPENING TO TOILET AS REQUIRED BY 97 FL
 ACCESSIBILITY CODE.
  
 12) PROVIDE A TYPICAL DETAIL OF EXTERIOR
 BEARING WALL WINDOW/DOOR OPENINGS,
 INDICATING HEADER SIZE, # OF JACKS,
 STRAPPING, ETC.
  
 13) INDICATE THE INTERIOR BEARING WALL
 AND THE SIZE HEADER AT THE OPENING TO
 THE MASTER BEDROOM. PROVIDE TYPICAL
 INTERIOR BEARING WALL DETAIL, INDICATING
 CONTINOUS LOAD PATH FROM FOOTER TO ROOF.
 OR INDICATE IF GIRDER TRUSS WILL BE USED
 IN PLACE OF INTERIOR BEARING WALL.
 INDICATE ADEQUATE LOAD PATH TO RESIST
 UPLIFT FOR GIRDER TRUSS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-14 Cont ID  
Sent By btrobaug Date 2002-03-14 Time 17:22 Rev Time 0.00
Received By btrobaug Date 2002-03-14 Time 17:20 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-02-20 Cont ID  
Sent By dpalmer Date 2002-02-20 Time 12:35 Rev Time 0.00
Received By dpalmer Date 2002-02-20 Time 09:58 Sent To  
Notes
2002-02-20 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT LOAD CALCS ARE
 SHOWN BUT DO NOT SHOW WHAT SIZE SERVICE
 IS EXISTING?
  
 2)NOTE: PLEASE NOTE THAT PER FS/FAC ALL
 PLANS THAT ARE SIGNED AND SEALED BY
 AN ENGINEER MUST CONTAIN A TITLE BLOCK
 WITH ALL THE INFORMATION SET FORTH IN
 61G15-23.002/471.025
 PLEASE NOTE THAT ALL HANDWRITTEN CHANGES
 ON PLANS NEED TO BE SIGNED BY ENG OF
 RECORD OR REPRINTED AND SIGNED AND SEAL-
 ED.
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-14 Cont ID  
Sent By btrobaug Date 2002-01-14 Time 16:27 Rev Time 1.00
Received By btrobaug Date 2002-01-14 Time 15:50 Sent To B
Notes
2002-01-14 00:00:00*****************UNSAT!*****************
 1)PLEASE PROVIDE A LOAD CALCULATION PER
 220-3(C)(1)
 2)PLEASE NOTE ALL BEDROOMS MUST CONFORM
 TO 212-12,AS OF 1/1/02.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561) 659-8096 EXT.8392

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-07-11 Cont ID  
Sent By ndenmark Date 2002-07-11 Time 14:12 Rev Time 0.25
Received By ndenmark Date 2002-07-11 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2002-07-02 Cont ID  
Sent By ndenmark Date 2002-07-02 Time 14:22 Rev Time 0.33
Received By ndenmark Date 2002-07-02 Time 14:22 Sent To  
Notes
2002-07-02 00:00:00REVISION NOT SIGNED AND SEALED BY ARCH
 OF RECORD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-06-24 Cont ID  
Sent By pkrauss Date 2002-06-24 Time 15:00 Rev Time 0.25
Received By pkrauss Date 2002-06-24 Time 14:59 Sent To  
Notes
2002-06-24 00:00:00REVISION CHANGED SIZE OF A/C EQUIP
 SUBMITTED NEW MANUAL J CALCS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-03-18 Cont ID  
Sent By pkrauss Date 2002-03-18 Time 07:52 Rev Time 0.30
Received By pkrauss Date 2002-03-18 Time 07:44 Sent To B
Notes
2002-03-18 00:00:00MECHANICAL PERMIT 01020580

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-02-22 Cont ID  
Sent By btrobaug Date 2002-03-14 Time 17:22 Rev Time 0.35
Received By pkrauss Date 2002-02-22 Time 09:48 Sent To B
Notes
2002-02-22 00:00:00*******************DENIED***************
  
  
 SEE REVIEW COMMENTS DATED 1/25/02.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-01-25 Cont ID  
Sent By pkrauss Date 2002-01-25 Time 16:38 Rev Time 0.30
Received By pkrauss Date 2002-01-25 Time 16:34 Sent To  
Notes
2002-01-25 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.INFORMATION ON THE EXISTING
 EQUIPMENT (MODEL, BTU, SEER).
  
 2.SQUARE FOOTAGE OF EXISTING HOUSE.
  
 3.SQUARE FOOTAGE OF ADDITION.
  
 4.CFM DISTRIBUTION OF ADDITION.
  
 5.INDICATE SIZE AND TERMINATION OF
 DRYER VENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-01-12 Cont ID  
Sent By jleech Date 2002-01-12 Time 11:24 Rev Time 0.33
Received By jleech Date 2002-01-12 Time 11:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-25 Cont ID  
Sent By sgraham Date 2002-01-25 Time 15:58 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***