Plan Review Details - Permit 02010568
Plan Review Stops For Permit 02010568
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-01-31 Cont ID  
Sent By btrobaug Date 2002-01-31 Time 17:44 Rev Time 0.00
Received By btrobaug Date 2002-01-31 Time 17:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-01-29 Cont ID  
Sent By dpalmer Date 2002-01-29 Time 07:14 Rev Time 0.00
Received By dpalmer Date 2002-01-29 Time 07:14 Sent To  
Notes
2002-01-29 00:00:00********************* UNSAT ************
  
 PLEASE NOTE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS WERE
 SUBMITTED FOR APT PANELS BUT NOTHING FOR
 SERVICE MAIN DISCONNECTS OR APT MAIN
 DISCONNECTS? MAIN DISCONNECTS WOULD BE
 THE FIRST POINT OF ENTRANCE. PLEASE
 SEE 110-9.
  
 2)NOTE: PLEASE NOTE, MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN 100A MAINS
 AND PANELS, CLARIFY METHOD OF GROUNDING
 OR SIZE PER 250-122.
  
 3)NOTE: PLEASE NOTE MISSING TWO OUTLETS
 FOR 2' OF WALL IN APTS #2,#1, CAN BE
 REDLINED ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-14 Cont ID  
Sent By dpalmer Date 2002-01-14 Time 21:21 Rev Time 0.00
Received By dpalmer Date 2002-01-14 Time 21:21 Sent To  
Notes
2002-01-14 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT A TYPICAL
 ELECTRICAL RISER DIAGRAM IS SHOWN ON A3
 AND A DIFFERENT RISER IS SHOWN ON A5
 PLEASE NOTE THAT A COMPLETE RISER
 DIAGRAM IS NEEDED FOR REVIEW. PLEASE
 NOTE GROUPING OF MAIN DISCONNECTS PER
 230-72.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3)NOTE: PLEASE NOTE THAT NO PANEL
 SCHEDULES WERE SUBMITTED FOR UNITS,
 CAN BE
 TYPICAL.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6)NOTE: PLEASE NOTE THAT NO HANDWRITTEN
 CHANGES MAY BE ON PLANS UNLESS DONE BY
 THE ARCH/ENGINEER OF RECORD AND THEN
 EACH INDIVIDUAL CHANGE MUST BE SIGNED
 AND DATED.471.025/481.221
  
 7)NOTE: PLEASE NOTE/CLARIFY IF THERE
 IS A 2HR SEPARATION OF UNITS IN ORDER
 TO HAVE THE SEPARATE SERVICES THAT ARE
 SHOWN? 230-2
  
 8)NOTE: PLEASE CLARIFY "DOOR" SHOWN IN-
 -FRONT OF STAIRS?
  
 9)NOTE: PLEASE NOTE LOAD CALCULATIONS
 SHOW UNITS 1,2,4,5 AND THEN UNITS 4&6,
 PLEASE CLARIFY 2-#4 UNITS? IS THE UPPER
 #4 SUPPOSE TO BE #3
  
 10)NOTE: PLEASE ELECTRICAL PLANS DUE TO
 NOTES ON SIDE OF PLANS.
  
  
 PLEASE MAKE THE ABOVE CORRECTIONS, AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372