Plan Review Details - Permit 02010382
Plan Review Stops For Permit 02010382 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-01-25 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-01-25 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-01-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-01-15 |
Time |
17:13 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2002-01-15 |
Time |
17:07 |
Sent To |
|
|
Notes |
2002-01-15 00:00:00 | PROVISO: | | 1)- DOOR# 209 MEETS THE 12" SIDE CLEAR- | | ENCE ON THE LATCH SIDE (PUSH).4.13.6. | | 2)- LOUNGE 101 TO MEET THE SIDE APPROACH | | REACH RANGE REQUIREMENTS FOR UPPER CABIN | | ETS & MICROWAVE.4.2.6. | | FLORIDA ACCESSIBILITY CODE, 1997 ED. | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096X8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-01-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-14 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-01-14 |
Time |
13:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-01-10 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-01-10 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-01-10 |
Time |
14:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-01-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-12 |
Time |
06:49 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-01-12 |
Time |
06:43 |
Sent To |
|
|
Notes |
2002-01-12 00:00:00 | MECHANICAL PERMIT 02010437 | | | | PROVISO: | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | WITH NOTIFICATION TO ALARM/STROBE AS | | PER 1997 SMC 406.1, 609.1.1 (PLENUMS) & | | NFPA 90A 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-01-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-01-29 |
Time |
16:01 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-01-29 |
Time |
16:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-01-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-01-14 |
Time |
09:00 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-01-14 |
Time |
09:00 |
Sent To |
|
|
Notes |
2002-01-14 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) PLEASE SHOW DETAILS ON COMPLIANCE FOR | | FACBC SEC'S 4.24.3, 4.24.5 & 4.24.6 | | | | REVEIW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
|