Plan Review Details - Permit 02010352
Plan Review Stops For Permit 02010352 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2002-02-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-01 |
Time |
15:22 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-02-01 |
Time |
15:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2002-01-23 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-23 |
Time |
10:28 |
Rev Time |
0.20 |
Received By |
pkrauss |
Date |
2002-01-23 |
Time |
10:28 |
Sent To |
|
|
Notes |
2002-01-23 00:00:00 | | | AS PER FLORIDA ENERGY CODE 407.1.ABCD.3. | | 3, THE CONDENSING COIL SHALL NOT BE | | INSTALLED IN THE COOL AIR STREAM OF | | ANOTHER AIR CONDITIONING UNIT. | | | | APPLIANCES LISTED FOR OUTDOOR | | INSTALLATIONS SHALL NOT BE INSTALLED | | INSIDE A BULDING AS PER 1997 SMC | | 304.2.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
|
Date |
2002-01-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-14 |
Time |
13:13 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2002-01-14 |
Time |
12:35 |
Sent To |
|
|
Notes |
2002-01-14 00:00:00 | ******************DENIED**************** | | | | 1.PLEASE SHOW COMPLIANCE WITH 1997 SMC | | 304.2.1 & 304.7, ACCESSIBILITY FOR | | SERVICE AS WELL AS REQUIRED CLEAR | | SPACE FOR SERVICE & INSPECTION, | | REFRIGERANT TYPE AND VENTILATION | | REQUIRMENTS AS PER 1997 SMC 304.7.4. | | | | 2.PROVIDE ENERGY CALCULATIONS. | | | | 3.PLEASE PROVIDE MANUFACTURER | | INSTALLATION AND SUBMITTAL DATA FOR | | THE EQUIPMENT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2002-01-10 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-10 |
Time |
12:17 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-01-10 |
Time |
12:16 |
Sent To |
|
|
Notes |
2002-01-10 00:00:00 | NO MECHANICAL PLANS SUBMITTED - MASTER | | PERMIT THAT IS TIED TO THIS PERMIT IS | | FOR A "SHELL" PERMIT ONLY.SPOKE WITH | | CONTRACTOR, TO BRING PLANS IN FOR | | REVIEW. |
|
|
|