Plan Review Details - Permit 02010346
Plan Review Stops For Permit 02010346
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-14 Cont ID  
Sent By btrobaug Date 2002-01-14 Time 16:13 Rev Time 0.25
Received By btrobaug Date 2002-01-14 Time 16:13 Sent To  
Notes
2002-01-14 00:00:00PASSED FOR T-POLE ONLY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-14 Cont ID  
Sent By btrobaug Date 2002-01-14 Time 11:16 Rev Time 0.50
Received By btrobaug Date 2002-01-14 Time 11:15 Sent To  
Notes
2002-01-14 00:00:00*************FAILED*********************
  
 1) NEED TO INSTALL A TEMPORARY
 ELECTRICAL POLE AND SERVICE DURING
 CONSTRUCTION
 AS PER BOB GERWE.
  
 2)WHEN RESUBMITTING,PLEASE PROVIDE AIC
 RATING PER 200-12,NEC.,ALSO PROVIDE
 ELECTRICAL LOAD CALCULATIONS PER 215-5.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561)659-8096 EXT.8392