Plan Review Details - Permit 02010255
Plan Review Stops For Permit 02010255
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-10 Cont ID  
Sent By btrobaug Date 2002-01-10 Time 16:42 Rev Time 0.50
Received By btrobaug Date 2002-01-10 Time 16:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-08 Cont ID  
Sent By btrobaug Date 2002-01-08 Time 11:00 Rev Time 0.50
Received By btrobaug Date 2002-01-08 Time 10:50 Sent To  
Notes
2002-01-08 00:00:00****************UNSAT!******************
  
  
 PLEASE PROVIDE THE FOLLOWING AND RESUBM
 IT FOR REVIEW:
  
 1)COMPLETE THE AIC RATING TO THELIN SIDE
 OF THE MAIN DISCONNECTING MEANS.
 2)PROVIDE LOAD CALCULATION FOR THE SERVI
 CE.
 3)INCLUDE THE CONDUIT SIZE AND TYPE BETW
 EEN THE DISCONNECTS.
 4)INDICATE THE WIRE SIZE FEEDING THE DIS
 CONNECT.
 5)INDICATE YYPE AND LOCATION OF PANELS.
 6)PLEASE SHOW SIZE OF GROUNDING ELECTROD
 E CONDUCTOR.
  
 BILL TROBAUGH
 ELECTRICAL PLAN EXAMINER
 (561)0659-8096 EXT.8392