Plan Review Details - Permit 02010252
Plan Review Stops For Permit 02010252
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-10 Cont ID  
Sent By btrobaug Date 2002-01-10 Time 16:29 Rev Time 0.50
Received By btrobaug Date 2002-01-10 Time 16:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-08 Cont ID  
Sent By btrobaug Date 2002-01-08 Time 13:55 Rev Time 1.00
Received By btrobaug Date 2002-01-08 Time 12:55 Sent To  
Notes
2002-01-08 00:00:00*****************UNSAT!*****************
  
 1)SEE NOTES ON RISER DIAGRAM.
 2)PROVIDE AIC RATING TO THE LINE SIDE OF
 DISCONNECTING MEANS.
 3)PROVIDE DRAWINGS FOR ALL UNITS.PLEASE
 MAKE PLANS MORE LEGIBLE.
 4)SHOW SMOKE DETECTORS IN ALL UNITS.
 5)LIGHTING AS PER 210-70
 6)PROVIDE PANEL SCHEDULES FOR ALL UNITS.
 7)GFI OUTLETS PER 210-52E.
 8)BEDROOM OUTLETS PER 210-12(ARC FAULT).
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561) 659-8096 EXT.8392