Plan Review Stops For Permit 02010252 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-01-10 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-01-10 |
Time |
16:29 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2002-01-10 |
Time |
16:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-01-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-01-08 |
Time |
13:55 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2002-01-08 |
Time |
12:55 |
Sent To |
|
|
Notes |
2002-01-08 00:00:00 | *****************UNSAT!***************** | | | | 1)SEE NOTES ON RISER DIAGRAM. | | 2)PROVIDE AIC RATING TO THE LINE SIDE OF | | DISCONNECTING MEANS. | | 3)PROVIDE DRAWINGS FOR ALL UNITS.PLEASE | | MAKE PLANS MORE LEGIBLE. | | 4)SHOW SMOKE DETECTORS IN ALL UNITS. | | 5)LIGHTING AS PER 210-70 | | 6)PROVIDE PANEL SCHEDULES FOR ALL UNITS. | | 7)GFI OUTLETS PER 210-52E. | | 8)BEDROOM OUTLETS PER 210-12(ARC FAULT). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | (561) 659-8096 EXT.8392 |
|
|
|