Plan Review Details - Permit 02010168
Plan Review Stops For Permit 02010168
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-03-28 Cont ID  
Sent By jwitmer Date 2002-03-28 Time 11:23 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-28 00:00:00TRUSS ENG + STRUC REVOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-03-19 Cont ID  
Sent By jwitmer Date 2002-03-19 Time 12:44 Rev Time 0.00
Received By jwitmer Date 2002-03-19 Time 16:05 Sent To  
Notes
2002-03-19 00:00:00***TRUSS ENGINEERING***
 C-B-A-B-C
  
 REVIEWED UNDER :
 1997 STANDARD BUILDING CODE
  
 1)- FG-5 A5 INDICATES A 3 POINT BEARING
 GIRDER TRUSS, TRUSS ENG. INDICATES A
 5 POINT BEARING, MISSING BEARING POINTS
 13 & 14.
  
 2)- SG-1 TRUSS ENG. POINT #5 INDICATES
 2060 LBS. UPLIFT WHERE AS SH A5 NOTE
 A-3 INDICATES 1370 OR 1890, SHORT
 RESTRAINT OR UPLIFT VALUE.
  
 3)- TRUSS ENG H-4 TRUSS ENG POINT #1 IN-
 DICATES 3203 LBS UPLIFT, POINT 11 INDICA
 TES 3174, ARCH A-6 DETAIL 4/10 IS A WALL
 SECTION TO A FLOOR GIRDER TRUSS CONNEC-
 TION MISSING INFO FOR THE ROOF GIRDER TO
 2ND STORY WALL CONNECTION?
  
 4)- TRUSS ENG H-5,- H-8,& T-1 INDICATE A
 3" BEARING END (BUCKET) ARCH SHEET A6
 INDICATES A (WA-5) NOT IN SCHEDULE?
  
 5)- WHERE MULTIPLE STRAPS ARE TO BE USED
 IN CMU OR CONCRETE A DERATING SHALL BE
 REQUIRED WHEN THEY ARE CLOSER THAN 8".
 USP SHALL CALCULATE THE AMOUNT OF DERAT-
 ING REQUIRED.
  
 6)- SHEET A-6 DETAIL 2 INDICATES A STRAP
 TO BE WELDED TO A MANUFACTURED BUCKET.
 SHALL REQUIRE MANUFACTURES APPROVAL &
 FIELD WELDING REQUIRES CERTIFICATION
 OF THE WELDER.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-02-19 Cont ID  
Sent By jwitmer Date 2002-02-19 Time 11:33 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-05 Cont ID  
Sent By btrobaug Date 2002-02-05 Time 17:40 Rev Time 0.00
Received By btrobaug Date 2002-02-05 Time 16:09 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-01-31 Cont ID  
Sent By mcarsill Date 2002-01-31 Time 11:04 Rev Time 0.00
Received By mcarsill Date 2002-01-31 Time 11:04 Sent To  
Notes
2002-01-31 00:00:00SEE NOTES WITH PERMIT # 02010168.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-19 Cont ID  
Sent By btrobaug Date 2002-02-05 Time 17:40 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-02-19 00:00:00PROVISO: LOTS 91-95
 1)- SUBMIT MANUAL J BEFORE FIRST INSPEC-
 TION.
 2)- REFER TO SECTION 503.3 BATHROOM
 EXHAUST 1997 STANDARD MECHANICAL CODE
 3)- REFER TO SEC 509.3 RESIDENTIAL
 DRYER 25 FT.
  
 JIM WITMER
 MECHANICAL PLAN REVIEW

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-02-02 Cont ID  
Sent By jleech Date 2002-02-02 Time 09:29 Rev Time 0.25
Received By jleech Date 2002-02-02 Time 09:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-30 Cont ID  
Sent By aneil Date 2002-01-30 Time 12:38 Rev Time 1.00
Received By aneil Date   Time   Sent To  
Notes
2002-01-30 00:00:00PASSED PER SHRILEY 1-30-2002 AN