2002-02-05 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) PROVIDE SOIL REPORT PER SEC. 1804.2.2 |
| OF CITY AMENDMENTS TO 1997 SBC. |
| |
| 3) GENERAL NOTE #9 ON SHEET C-1 SITES |
| THE WRONG EDITION OF THE FLORIDA ENERGY |
| CODE. CORRECT EDITION IS THE 1997. |
| |
| 4) ON SHEET C-1 THE NOTE UNDER LOAD |
| SCHEDULE INCORRECTLY REFERENCES THE 1999 |
| STANDARD BUILDING CODE. THE 1997 SBC IS |
| THE CORRECT EDITION. |
| |
| 5) SAFETY GLASS IS REQUIRED IN THE |
| WINDOW OF BATH #3 PER 97 SBC 2405.2. |
| |
| 6)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - SINGLE HUNG WINDOWS |
| - ARCHED FIXED GLASS WINDOWS |
| - RECTANGULAR F.G. WINDOWS |
| - STRUCTURAL MULLIONS |
| |
| 7) THE 1-1/2" FASTNERS SPECIFIED FOR |
| ATTACHING THE 2X4 P.T. BUCKS ON THE DOOR |
| JAMB DETAIL(SHEET A-4)IS NOT SUFFICIENT. |
| PLEASE CORRECT. |
| |
| 8) THE TRUSS CONNECTOR SCHEDULE ON SHEET |
| A-6 SPECIFIES SEMCO CONNECTORS. SEMCO |
| HAS BEEN PURCHASED BY USP AND THE |
| TAPR 220 IS LISTED IN THEIR CATALOG WITH |
| WITH A MAXIMUM UPLIFT OF 1485#. PLEASE |
| REVISE THE SCHEDULE. |
| |
| 9) BRACING NOTE #7 ON SHEET A-6 STATES |
| THAT IT MEETS THE REQUIREMENTS OF |
| CHAPTER 23 AND SECTION 2906.17 OF THE |
| S.F.B.C. ARE YOU REFERING TO CHAPTER 23 |
| OF THE S.B.C.? DELETE THE REFERENCE TO |
| THE SOUTH FLORIDA BUILDING CODE. |
| |
| 10) THE SITE SPECIFIC PRODUCT APPROVAL |
| FORMS ARE REQUIRED TO BE SIGNED AND |
| SEALED BY THE DESIGNER OF RECORD, IN |
| ADDITION TO THE ENGINEER. |
| |
| 11) THE L-2 LINTEL OVER THE SLIDING |
| GLASS DOOR AT THE LIVING ROOM IS |
| REQUIRED TO HAVE A MINIMUM END BEARING |
| OF 4" PER 2101.3.1. HOW IS THIS BEING |
| ACCOMPLISHED AT MASONRY COLUMN C-7? |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |