Plan Review Details - Permit 02010056
Plan Review Stops For Permit 02010056
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-09-04 Cont ID  
Sent By hpiskura Date 2002-09-04 Time 15:15 Rev Time 0.00
Received By hpiskura Date 2002-08-28 Time 11:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-02-27 Cont ID  
Sent By hpiskura Date 2002-02-27 Time 14:09 Rev Time 0.00
Received By hpiskura Date   Time 11:11 Sent To  
Notes
2002-02-27 00:00:00PROVISO:SEPARATE PERMIT AND TEST
 REPORT FOR RE-ROOF OF COVERED SHELTERS.
  
 PROVIDE HC ACCESSIBLE TABLES IN THE
 ACCESSIBLE PICNIC SHELTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-11 Cont ID  
Sent By jwitmer Date 2002-02-11 Time 13:27 Rev Time 4.50
Received By jwitmer Date 2002-02-11 Time 13:27 Sent To  
Notes
2002-02-11 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02010056
 1501 N. AUSWTRALIAN AV
 CONT: WHITING- TURNER
 TEL: (561) 832-4995
 CEL: (561) 418-2367
  
 PLAN DESIGN?
  
 1) PLANS ARE TO DESIGNATE TO WHICH CODE
 THEY ARE DESIGNED TOO?UNTIL MARCH 1,2002
 PLANS MAY BE DESIGNED TO EITHER 2001
 FLORIDA CODE OR 1997 SBC., SEE C-19.
  
 2) LIST THE DESIGN CRITERIA, SEE C-19.
  
 3) LR-3, LR-4 & LR-7 INDICATE EXISTING
 COVERED SHELTERS, SHELTERS ARE NOT SHOWN
 TO BE HANDICAPPED ACCESSIBLE TO THE
 EXISTING PATH. FLORIDA ACCESSIBILITY
 CODE 4.1.6.1(B).
  
 4) THESE SAME SHELTERS, PLANS INDICATE
 THAT THEY ARE TO RECEIVE NEW METAL
 ROOFING. PROVIDE (2 COPIES) OF PRODUCT
 APPROVAL REPORTS FOR WIND ZONE. WILL THE
 FINISHED ROOFING MATERIAL BE CONSIDERED
 ARCHITECTURAL METAL PANELS COVERED BY
 SECTION 1509 OR STRUCTURAL METAL PANELS
 COVERED BY SECTION 1510?
 5) A ROOFING CONTRACTOR SHALL HAVE TO
 PULL THIS PERMIT, NOT COVERED UNDER GC
 LICENSE.
  
 6) HANDICAPPED PARKING NOT SHOWN AT BALL
 FIELDS?
  
 7)- REHABILITATION GAINES PARK:
 L-1- L-9 NEW PIC NIC TABLES ARE NOT
 SHOWN ON ACCESSIBILE ROUTE.
  
 8)- LD-3 PICNIC TABLE DETAIL DOES NOT
 ALLOW FOR HANDICAPPED USE.
  
 9)- SHEET LD-1 SOUTH BOARDWALK (FOOT-
 BRIDGE) NO DETAILS, WHICH CODE DESIGNED
 TOO? DESIGN CRITERIA?
  
 BUILDING PLAN REIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2003-05-06 Cont ID  
Sent By btrobaug Date 2003-05-06 Time 12:09 Rev Time 1.00
Received By btrobaug Date 2003-05-06 Time 12:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2003-04-21 Cont ID  
Sent By btrobaug Date 2003-04-21 Time 11:00 Rev Time 1.00
Received By btrobaug Date 2003-04-21 Time 11:00 Sent To  
Notes
2003-04-21 00:00:00PLEASE SEND TO HEALTH DEPARTMENT FOR
 REVIEW OF POOL PHOTOMETRICS,AND RETURN
 TO THIS DEPARTMENT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-08-27 Cont ID  
Sent By shernand Date 2003-04-11 Time 13:59 Rev Time 0.50
Received By btrobaug Date 2002-08-27 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-07-30 Cont ID  
Sent By btrobaug Date 2002-07-30 Time 18:01 Rev Time 0.00
Received By btrobaug Date 2002-07-30 Time 17:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-22 Cont ID  
Sent By btrobaug Date 2002-02-22 Time 16:44 Rev Time 0.00
Received By btrobaug Date 2002-02-22 Time 16:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-04 Cont ID  
Sent By dpalmer Date 2002-02-04 Time 09:40 Rev Time 0.00
Received By dpalmer Date 2002-02-04 Time 09:39 Sent To  
Notes
2002-02-04 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE ELEC RISER FOR EAST END
 OF PARK ON E-10.PLEASE CLARIFY GROUND
 FOR TRANSFORMER?250
  
 2)NOTE: PLEASE SEE E-11, PLEASE NOTE THE
 NEW 300KVA TRANSFORMER NEEDS TO BE
 SHOWN ON LINE DIAGRAM. PLEASE CLARIFY
 EQUIPMENT GRPUNDS TO AND FROM??
 ALSO GROUNDING OF TRANSFORMER.250
  
 3)NOTE: PLEASE SEE ELEC POWER DIST AT
 WEST END OF PARK. PLEASE CLARIFY
 GROUND FOR THE TRANSFOMER.
 PLEASE CLARIFY WHICH PART OF THIS DIST
 SYSTEM IS FPL/ OR OTHER.215-5
  
 4)NOTE: PLEASE LABEL ALL PANEL SCHEDUE
 TO CORRELATE WITH RISER DIAGRAM.215-5
  
 5)NOTE: PLEASE SHOW ALL CONTINUOUD LOADS
 AT 125%.215-2/3,230-42
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-01-23 Cont ID  
Sent By mamini Date 2002-01-23 Time 09:51 Rev Time 3.00
Received By mamini Date 2002-01-23 Time 09:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-02-26 Cont ID  
Sent By mcarsill Date 2002-02-26 Time 14:12 Rev Time 0.00
Received By mcarsill Date 2002-02-26 Time 14:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-29 Cont ID  
Sent By mcarsill Date 2002-01-29 Time 09:55 Rev Time 0.00
Received By mcarsill Date 2002-01-29 Time 09:55 Sent To  
Notes
2002-01-29 00:00:001) CULVERT AREA IS TO BE DESIGNED TO
 SUPPORT LIVE LOADS OF FIRE APPARATUS.
 2) PLEASE PROVIDE DETAILS ON REMOVABLE
 BOLLARDS PLANNED FOR THE FIRE LANE
 AREA. ALSO PLEASE PROVIDE DETAILS ON
 APPROPRIATE SIGNAGE FOR THIS AREA.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 13:59 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 13:59 Sent To E
Notes
2003-04-11 00:00:00BT DESK

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-03-04 Cont ID  
Sent By kstevens Date 2002-03-04 Time 13:22 Rev Time 0.50
Received By kstevens Date 2002-03-04 Time 13:22 Sent To  
Notes
2002-03-04 00:00:00PASSED/PROVISO: BACKFLOW FOR D.F. - HI/
 LOW DRINKING FOUNTAIN REQUIRED.
 KSTEVENS
 IRRIGATION PLANS SUBMITTED SEPARATELY.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-02 Cont ID  
Sent By kstevens Date 2002-02-02 Time 08:04 Rev Time 0.75
Received By kstevens Date 2002-02-02 Time 07:52 Sent To  
Notes
2002-02-02 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHTS LR-2 & LR-7 REFER TO EXISTING
 IRRIGATION VALVES AND IRRIGATION PLANS.
 NO IRRIGATION PLANS FOUND.
  
 2) SHT L-6 OF L-9 STATES TO TIE INTO
 EXISTING WATER LINE WITH BACKFLOW PRE-
 VENTER AS REQUIRED. IF TYING INTO CITY
 WATER, A PLUMBING CONTRACTOR WILL BE
 REQUIRED FOR THE JOB AND WILL HAVE TO
 CONTACT BACKFLOW DEPT (659-8005) AND THE
 SITE PLAN MUST BE APPROVED PRIOR TO IN-
 STALLATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-17 Cont ID  
Sent By sgraham Date 2002-01-17 Time 13:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***