Plan Review Stops For Permit 02010047 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-02-22 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-02-22 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-02-14 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-02-14 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-02-14 00:00:00 | SAME AS PREVIOUS LIST WITH THE EXCEPTION | | OF THE SITE PLAN. OTHER FIVE ITEMS HAVE | | NOT BEEN ADDRESSED.. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-01-16 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-01-16 |
Time |
08:28 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-01-16 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY | | AND A SITE PLAN WITH DIMENSIONS LOCATING | | THE PROPOSED BUILDING ON THE PROPERTY. | | INCLUDE TOPOGRAPHIC INFORMATION SO | | THATCOMPLIANCE WITH HANDICAP SITE | | ACCESSIBILTY MAY BE DETERMINED. | | | | PROVIDE PRODUCT TEST REPORTS AND OR | | NOTICE OF ACCEPTANCE DATA FOR THE | | DOORS, WINDOWS AND ROOF COVERING TO BE | | USED. | | | | SHOW THE METHOD OF HURRICANE MISSILE | | IMPACT RESISTANT FOR THE EXTERIOR | | GLAZED PORTIONS OF THE BUILDING. | | | | SHOW THE SPECIFIC CODE AND DESIGNS | | STANDARDS USED FOR THIS BUILDING. | | | | THE ROOF NOTES ON SHEET S3 DO NOT | | DEFINETHE SIZE OR LOCATION OF THE 3 | | ZONES FOR WIND PRESSURE.INCLUDE THE | | PRESSURE ZONES FOR COMPONENTS AND | | CLADDING ON THE WALLS ALSO. | | | | PLEASE PROVIDE STRUCTURAL CALCULATIONS | | FOR THE 2X4 PURLINS ON THE ROOF | | DEMONSTRATING THEIR ABILITY TO RESIST | | UPLIFT THE DECLARED UPLIFT PRESSURES. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
N |
Date |
2002-02-01 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2002-02-01 |
Time |
11:19 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2002-01-07 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-01-07 |
Time |
08:30 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2002-01-07 |
Time |
08:29 |
Sent To |
|
|
Notes |
2002-01-07 00:00:00 | PASSED: | | 1. SEE PERMIT # 02010222 FOR CIVIL/SITE | | ENGINEERING REVIEW. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-01-24 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-01-24 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-01-24 |
Time |
16:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-01-03 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-01-03 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-01-03 |
Time |
15:03 |
Sent To |
|
|
Notes |
2002-01-03 00:00:00 | | | | | | | | | 1) SINCE NO FIRE SPRINKLERS ARE PLANNED | | THE ELECTRICAL ROOM, MECHANICAL, AND | | UTILITY ROOMS ARE TO BE AT LEAST ONE | | HOUR FIRE SEPARATED WITH C LABELED FIRE | | DOORS WITH CLOSERS. | | 2) PLEASE PROVIDE INTERIOR FINISH | | INFORMATION FOR THE WALLS AND CEILINGS. | | 3) BUILDING ADDRESS IS REQUIRED PER | | CITY CODE 3343-00. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-01-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-24 |
Time |
17:10 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2002-01-24 |
Time |
17:09 |
Sent To |
|
|
Notes |
2002-01-24 00:00:00 | | | APPROVED PER MTG WITH MECH ENG AND | | ARCHITECT. | | | | TRANSFER AIR TO BE REMOVED FROM | | BATHROOMS. | | | | DUCT SMOKE DETECTOR TO HAVE NOTIFICATION | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | AREAS.TO BE SUBMITTED WITH FIRE ALARM | | PLANS & PERMIT. | | | | TO SUBMIT PLAN INDICATING DRYWELL FOR | | CONDENSATE. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-01-11 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-11 |
Time |
08:12 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2002-01-11 |
Time |
07:45 |
Sent To |
|
|
Notes |
2002-01-11 00:00:00 | ********************DENIED************** | | | | 1.PLAN SHEET M1.1 INDICATE AIR FROM | | THE MALE AND FEMALE BATHROOMS IS | | TO BE TRANSFERED INTO THE COMMON | | AREAS, AS PER 1997 SMC 503.3.1 - | | AIR EXHAUSTED FROM BATH TOILET, | | URINAL, LAVATORY, LOCKER, COAT ROOM | | OR SIMILAR ROOMS SHALL NOT BE | | RECIRCULATED. | | | | 2.PLEASE NOTE FIRE DEPARTMENT COMMENT | | #1,SHOULD THESE ROOMS HAVE A FIRE | | SEPARATION, FIRE DAMPERS WILL BE | | REQUIRED.INDICATE LOCATION OF | | FIRE DAMPERS AND INSTALLATION DETAIL | | ON PLAN. | | | | 3.WHAT IS THE UTILITY ROOM USED FOR? | | | | 4.AS PER 1997 SMC 406.1, FAN SHUTDOWN | | BY DUCT SMOKE DETECTOR IN THE RETURN | | AIRSTREAM PROIR TO ANY EXHAUSTING | | FROM THE BUILDING OR MIXING WITH | | FRESH AIR MAKEUP. | | | | 5.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | WITH NOTIFICATION TO ALARM/STROBE IN | | NORMALLY OCCUPIED AREAS. NFPA 90A | | 4-4.4.3. | | | | 6.PLEASE INDICATE SIZE AND TERMINATION | | OF THE CONDENSATE.UNITS LARGER | | THAN 3 TON SHALL TERMINATE INTO: | | | | 1.AN APPROVED DRY WELL | | 2.TO STORM DRAIN | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-01-24 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-01-24 |
Time |
17:47 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-01-24 |
Time |
17:46 |
Sent To |
|
|
Notes |
2002-01-24 00:00:00 | PER NEIL MELICK - WATER COOLER UNDER | | ALTERNATE METHOD. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-01-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-01-18 |
Time |
18:43 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-01-18 |
Time |
18:42 |
Sent To |
|
|
Notes |
2002-01-18 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) SHT A2.0, 1 DRINKING FOUNTAIN REQUIR- | | ED PER SPC TABLE 407. HI-LOW TO COMPLY | | WITH FACBC 4.1.3(10) TO PROVIDE FOR | | THOSE WITH DIFFICULTY BENDING OR STOOP- | | ING. ALSO COMPLY WITH FACBC 4.15, 4.15.2 | | & 4.15.5 | | | | 2) SHT A2.O/A4.0 WATER CLOSETS, SHOW | | COMPLIANCE WITH 4.16, 4.14.2, 4.16.5 - | | (MENS ROOM #103), SHOW W/C'S 1'6" OFF | | WALL. | | | | 3) SHT A2.0/A4.0 URNAL, SHOW COMPLIANCE | | WITH 4.18, 4.18.3. | | | | 4) SHT A2.0/A4.0 LAVS, SHOW COMPLIANCE | | WITH 4.19, 4.19.3, 4.19.4 & 4.19.5 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-01-03 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-01-03 |
Time |
10:17 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|