Plan Review Details - Permit 02010047
Plan Review Stops For Permit 02010047
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-02-22 Cont ID  
Sent By hpiskura Date 2002-02-22 Time 10:07 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-02-14 Cont ID  
Sent By hpiskura Date 2002-02-14 Time 15:49 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-02-14 00:00:00SAME AS PREVIOUS LIST WITH THE EXCEPTION
 OF THE SITE PLAN. OTHER FIVE ITEMS HAVE
 NOT BEEN ADDRESSED..

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-16 Cont ID  
Sent By hpiskura Date 2002-01-16 Time 08:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-01-16 00:00:00PLEASE PROVIDE A RECENT PROPERTY SURVEY
 AND A SITE PLAN WITH DIMENSIONS LOCATING
 THE PROPOSED BUILDING ON THE PROPERTY.
 INCLUDE TOPOGRAPHIC INFORMATION SO
 THATCOMPLIANCE WITH HANDICAP SITE
 ACCESSIBILTY MAY BE DETERMINED.
  
 PROVIDE PRODUCT TEST REPORTS AND OR
 NOTICE OF ACCEPTANCE DATA FOR THE
 DOORS, WINDOWS AND ROOF COVERING TO BE
 USED.
  
 SHOW THE METHOD OF HURRICANE MISSILE
 IMPACT RESISTANT FOR THE EXTERIOR
 GLAZED PORTIONS OF THE BUILDING.
  
 SHOW THE SPECIFIC CODE AND DESIGNS
 STANDARDS USED FOR THIS BUILDING.
  
 THE ROOF NOTES ON SHEET S3 DO NOT
 DEFINETHE SIZE OR LOCATION OF THE 3
 ZONES FOR WIND PRESSURE.INCLUDE THE
 PRESSURE ZONES FOR COMPONENTS AND
 CLADDING ON THE WALLS ALSO.
  
 PLEASE PROVIDE STRUCTURAL CALCULATIONS
 FOR THE 2X4 PURLINS ON THE ROOF
 DEMONSTRATING THEIR ABILITY TO RESIST
 UPLIFT THE DECLARED UPLIFT PRESSURES.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-02-01 Cont ID  
Sent By lmartine Date 2002-02-01 Time 11:19 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-01-07 Cont ID  
Sent By mamini Date 2002-01-07 Time 08:30 Rev Time 1.00
Received By mamini Date 2002-01-07 Time 08:29 Sent To  
Notes
2002-01-07 00:00:00PASSED:
 1. SEE PERMIT # 02010222 FOR CIVIL/SITE
 ENGINEERING REVIEW.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-24 Cont ID  
Sent By mcarsill Date 2002-01-24 Time 16:21 Rev Time 0.00
Received By mcarsill Date 2002-01-24 Time 16:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-03 Cont ID  
Sent By mcarsill Date 2002-01-03 Time 15:03 Rev Time 0.00
Received By mcarsill Date 2002-01-03 Time 15:03 Sent To  
Notes
2002-01-03 00:00:00 
  
  
  
 1) SINCE NO FIRE SPRINKLERS ARE PLANNED
 THE ELECTRICAL ROOM, MECHANICAL, AND
 UTILITY ROOMS ARE TO BE AT LEAST ONE
 HOUR FIRE SEPARATED WITH C LABELED FIRE
 DOORS WITH CLOSERS.
 2) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR THE WALLS AND CEILINGS.
 3) BUILDING ADDRESS IS REQUIRED PER
 CITY CODE 3343-00.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-24 Cont ID  
Sent By pkrauss Date 2002-01-24 Time 17:10 Rev Time 0.45
Received By pkrauss Date 2002-01-24 Time 17:09 Sent To  
Notes
2002-01-24 00:00:00 
 APPROVED PER MTG WITH MECH ENG AND
 ARCHITECT.
  
 TRANSFER AIR TO BE REMOVED FROM
 BATHROOMS.
  
 DUCT SMOKE DETECTOR TO HAVE NOTIFICATION
 TO ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS.TO BE SUBMITTED WITH FIRE ALARM
 PLANS & PERMIT.
  
 TO SUBMIT PLAN INDICATING DRYWELL FOR
 CONDENSATE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-01-11 Cont ID  
Sent By pkrauss Date 2002-01-11 Time 08:12 Rev Time 0.50
Received By pkrauss Date 2002-01-11 Time 07:45 Sent To  
Notes
2002-01-11 00:00:00********************DENIED**************
  
 1.PLAN SHEET M1.1 INDICATE AIR FROM
 THE MALE AND FEMALE BATHROOMS IS
 TO BE TRANSFERED INTO THE COMMON
 AREAS, AS PER 1997 SMC 503.3.1 -
 AIR EXHAUSTED FROM BATH TOILET,
 URINAL, LAVATORY, LOCKER, COAT ROOM
 OR SIMILAR ROOMS SHALL NOT BE
 RECIRCULATED.
  
 2.PLEASE NOTE FIRE DEPARTMENT COMMENT
 #1,SHOULD THESE ROOMS HAVE A FIRE
 SEPARATION, FIRE DAMPERS WILL BE
 REQUIRED.INDICATE LOCATION OF
 FIRE DAMPERS AND INSTALLATION DETAIL
 ON PLAN.
  
 3.WHAT IS THE UTILITY ROOM USED FOR?
  
 4.AS PER 1997 SMC 406.1, FAN SHUTDOWN
 BY DUCT SMOKE DETECTOR IN THE RETURN
 AIRSTREAM PROIR TO ANY EXHAUSTING
 FROM THE BUILDING OR MIXING WITH
 FRESH AIR MAKEUP.
  
 5.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. NFPA 90A
 4-4.4.3.
  
 6.PLEASE INDICATE SIZE AND TERMINATION
 OF THE CONDENSATE.UNITS LARGER
 THAN 3 TON SHALL TERMINATE INTO:
  
 1.AN APPROVED DRY WELL
 2.TO STORM DRAIN
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-01-24 Cont ID  
Sent By kstevens Date 2002-01-24 Time 17:47 Rev Time 1.00
Received By kstevens Date 2002-01-24 Time 17:46 Sent To  
Notes
2002-01-24 00:00:00PER NEIL MELICK - WATER COOLER UNDER
 ALTERNATE METHOD.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-18 Cont ID  
Sent By kstevens Date 2002-01-18 Time 18:43 Rev Time 1.00
Received By kstevens Date 2002-01-18 Time 18:42 Sent To  
Notes
2002-01-18 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A2.0, 1 DRINKING FOUNTAIN REQUIR-
 ED PER SPC TABLE 407. HI-LOW TO COMPLY
 WITH FACBC 4.1.3(10) TO PROVIDE FOR
 THOSE WITH DIFFICULTY BENDING OR STOOP-
 ING. ALSO COMPLY WITH FACBC 4.15, 4.15.2
 & 4.15.5
  
 2) SHT A2.O/A4.0 WATER CLOSETS, SHOW
 COMPLIANCE WITH 4.16, 4.14.2, 4.16.5 -
 (MENS ROOM #103), SHOW W/C'S 1'6" OFF
 WALL.
  
 3) SHT A2.0/A4.0 URNAL, SHOW COMPLIANCE
 WITH 4.18, 4.18.3.
  
 4) SHT A2.0/A4.0 LAVS, SHOW COMPLIANCE
 WITH 4.19, 4.19.3, 4.19.4 & 4.19.5
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-03 Cont ID  
Sent By sgraham Date 2002-01-03 Time 10:17 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***