Plan Review Details - Permit 01121760
Plan Review Stops For Permit 01121760
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-06-21 Cont ID  
Sent By rbrown Date 2002-06-21 Time 19:37 Rev Time 0.00
Received By rbrown Date 2002-06-21 Time 19:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-05-20 Cont ID  
Sent By rbrown Date 2002-05-20 Time 11:08 Rev Time 0.00
Received By rbrown Date 2002-05-20 Time 11:08 Sent To  
Notes
2002-05-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/31/02:
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) SBC* 1504.1.2SUBMIT A PRODUCT
 APPROVAL FOR THE ROOFING.
  
 5) ROOF TRUSS UPLIFT ANCHORS.GENERAL
 NOTE 15 ON SHEET SD1 REFERS TO THE TRUSS
 FABRICATOR FOR UPLIFT ANCHORS, BUT THE
 TRUSS DRAWING DOES NOT SPECIFY ANCHORS.
 NOTE THAT, FROM THE ARRANGEMENT SHOWN ON
 THE TRUSS DRAWING, THE SIMPSON LGT2
 ANCHOR SPECIFIED ON THE TYPICAL WALL
 SECTION IS NOT SUITABLE FOR THE HIP TO
 WALL JUNCTION.SPECIFY THE ANCHORS TO
 BE USED FOR EACH TRUSS.
  
 7) SBC TABLE 600THE AMENDMENT TO THE
 PERCENTAGE OF WINDOW AREA SHOULD HAVE
 BEEN MADE TO THE EAST ELEVATION NOT THE
 WEST ELEVATION.THE WEST ELEVATION
 (KITCHEN) WINDOW MAY BE REINSTATED BUT
 THE TOTAL EAST ELEVATION WINDOW AREA
 SHOULD BE REDUCED TO LESS THAN 10% OF
 THE WALL AREA.IN DOING THIS THE WINDOW
 AREA FOR THE TWO ROOMS MUST BE AT LEAST
 8% OF THE ROOM FLOOR AREA, FOR MINIMUM
 LIGHT REQUIREMENTS (REF SBC 1203.1.4).
 ALTERNATIVELY, INCREASE THE EAST
 ELEVATION SETBACK TO AT LEAST 10'.
  
 NOTE:
 WHEN RESUBMITTING THE PLANS, PLEASE
 COLLATE THE REVISED SHEETS WITH THE
 VALID SHEETS/DOCUMENTS FROM THE ORIGINAL
 SET.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-31 Cont ID  
Sent By rbrown Date 2002-01-31 Time 15:16 Rev Time 0.00
Received By rbrown Date 2002-01-31 Time 15:16 Sent To  
Notes
2002-01-31 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FL ENERGY CODE 103.1.2BEFORE A
 BUILDING PERMIT CAN BE ISSUED, THE
 SUBMITTED ENERGY CODE COMPLIANCE FORMS
 SHALL BE SIGNED BY THE BUILDING OWNER,
 THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY
 THE OWNER.
  
 4) SBC* 104.1.1A SEPARATE ROOFING
 PERMIT APPLICATION IS REQUIRED.
  
 5) ROOF TRUSS DRAWINGS SHALL BE
 SUBMITTED.
  
 6) SBC* 104.2.2PREFABRICATED ROYALL
 WALL PANELS.ENGINEERING DETAILS,
 INCLUDING ANCHORAGE TO THE FOUNDATIONS,
 SIGNED AND SEALED BY THE ENGINEER, SHALL
 BE SUBMITTED.ASSOCIATED WINDOW/DOOR
 HEADER AND FASTENING DETAILS ARE ALSO
 REQUIRED.
  
 7) SBC TABLE 600THE "LEFT ELEVATION"
 (EAST ELEVATION) SETBACK IS 8'6".FOR
 TYPE V CONSTRUCTION AND A SETBACK
 BETWEEN 3' AND 10', TABLE 600 ALLOWS FOR
 10% OF THE WALL AREA TO BE UNPROTECTED
 OPENINGS.THE PROPOSED AREA OF WINDOWS
 IN THIS WALL EXCEEDS THE ALLOWABLE
 PERCENTAGE.ADJUST THE SETBACK TO AT
 LEAST 10' OR AMEND THE WINDOW AREA TO
 COMPLY.
  
 8) SBC 1804.1.3THE PLANS SHALL BE
 AMENDED TO SHOW THE BASE LEVEL FOR THE
 EXTERIOR WALL FOUNDATIONS AT LEAST 12"
 BELOW FINISH GRADE.
  
 9) SBC* 1606.4THE PLANS SHALL MAKE
 REFERENCE TO THE REQUIREMENT FOR STORM
 SHUTTERS ON ALL WINDOWS AND DOORS EXCEPT
 THE FRONT ENTRANCE DOOR.
  
 10) SBC 2405.2.1THE GLAZING IN THE
 PATIO DOORS AND THE DOOR TO THE PATIO IS
 IN A "HAZARDOUS LOCATION".PROVIDE
 DETAILS TO SHOW COMPLIANCE WITH THE
 REQUIREMENT FOR 'SAFETY GLASS'.
  
 11) SBC 2309.6THE PLANS SHALL BE
 AMENDED TO SHOW AN INTERIOR ATTIC ACCESS
 OPENING NOT LESS THAN 22"X36".
  
 12) SBC 2309.7ATTIC SPACE VENTILATION
 SHALL BE PROVIDED IN COMPLIANCE WITH THE
 AREA AND LOCATION REQUIREMENTS.
  
 13) TYPICAL HIP TRUSS CONNECTION TO WALL
 THE TYPICAL WALL SECTION SHOWS SIMPSON
 LGT2 CONNECTORS WITH 14-10D NAILS INTO
 THE HIP TRUSS.THIS WOULD RESULT IN
 REDUCED LOAD CAPACITY COMPARED TO THE
 SIMPSON RECOMMENDATION FOR 14-16D
 FASTENERS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-10-23 Cont ID  
Sent By btrobaug Date 2002-10-23 Time 18:42 Rev Time 0.25
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-10-21 Cont ID  
Sent By btrobaug Date 2002-10-21 Time 10:19 Rev Time 0.50
Received By btrobaug Date 2002-10-21 Time 10:13 Sent To  
Notes
2002-10-21 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE NOTE THAT PLANS ARE TO
 BE SIGNED, DATED AND SEALED BY AN P.E.
 PER FS/FAC 553-79-6A.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-06-18 Cont ID  
Sent By btrobaug Date 2002-06-18 Time 09:54 Rev Time 0.00
Received By btrobaug Date 2002-06-18 Time 09:24 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-04-23 Cont ID  
Sent By pkrauss Date 2002-06-17 Time 14:25 Rev Time 0.00
Received By btrobaug Date 2002-04-23 Time 09:59 Sent To P
Notes
2002-04-23 00:00:00*****************UNSAT!*****************
  
 PLEASE INCLUDE THE SHEET WITH THE LOAD
 CALCULATIONS,PANEL SCHEDULE AND RISER
 DIAGRAM WITH THE RESUBMITTED PLANS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-18 Cont ID  
Sent By btrobaug Date 2002-01-18 Time 09:25 Rev Time 1.00
Received By btrobaug Date 2002-01-18 Time 07:58 Sent To R
Notes
2002-01-18 00:00:00****************UNSAT!******************
  
 PLEASE REVISE AND RESUBMIT WITH THE
 FOLLOWING:
  
 1) PROVIDE AN A.I.C. RATING TO THE LOAD
 SIDE OF THE FIRST MEANS OF DISCONNECT.
  
 2) INDICATE GROUNDING METHOD BEING
 USED,INCLUDE 250-50(A) & (C).
  
 3) 250-52 (D) INSTALL GFI IN BATH.
  
 4) COMPLY WITH 250-52(A)(2)(A),IN
 BEDROOMS AND MASTER SUITE,(SEE PLANS).
  
 5) WATER HEATER TO COMPLY WITH 422-16(A)
 ALSO NOTE 422-33.
  
 6) ENGINEER PLEASE NOTE AND COMPLYWITH
 F.S. 61G15-23.002, ALL SHEETS.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT.8392

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-17 Cont ID  
Sent By pkrauss Date 2002-06-17 Time 14:24 Rev Time 0.40
Received By pkrauss Date 2002-06-17 Time 14:24 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-01-10 Cont ID  
Sent By hmoser Date 2002-01-10 Time 19:37 Rev Time 0.00
Received By hmoser Date 2002-01-10 Time 19:38 Sent To  
Notes
2002-01-10 00:00:00NO MECHANICAL PLANS.A/C CONTRACTOR MUST
 SUBMIT PLANS WITH PERMIT APPLICATION
 01/10/02H.M.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-10-05 Cont ID  
Sent By jleech Date 2002-10-05 Time 09:07 Rev Time 0.33
Received By jleech Date 2002-10-05 Time 09:07 Sent To  
Notes
2002-10-05 00:00:00REVISED FLOOR PLAN AND PLUMBING DIAGRAM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-13 Cont ID  
Sent By jleech Date 2002-06-13 Time 17:50 Rev Time 0.33
Received By jleech Date 2002-06-13 Time 17:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-06 Cont ID  
Sent By jleech Date 2002-05-06 Time 16:52 Rev Time 0.33
Received By jleech Date 2002-05-06 Time 16:52 Sent To  
Notes
2002-05-06 00:00:00DENIED;
 1.RISER DIAGRAM REQUIRED.
 2.WASHING MACHINE CONNECTION REQUIRED
 SEE TABLE 407.
 SECOND PLUMBING REVIEW.
 REVIEW BY JOHN LEECH
 659-8096 EXT 8369

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-05 Cont ID  
Sent By btrobaug Date 2002-04-23 Time 12:19 Rev Time 0.50
Received By jleech Date 2002-01-05 Time 10:11 Sent To  
Notes
2002-01-05 00:00:00DENIED;
 1.RISER DIAGRAM NOT TO CODE. @ W/C
 FLUSHING PAST AN UNVENTED TUB.
 2.W/M STACK NOT SHOWN.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2002-06-25 Cont ID  
Sent By btrobaug Date 2002-06-18 Time 09:54 Rev Time 0.00
Received By rbrown Date 2002-05-20 Time 11:03 Sent To  
Notes
2002-05-20 00:00:00SEE BUILDING PLAN REVIEW COMMENTS
 ENTERED UNDER REVIEW STOP 'B'.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-03 Cont ID  
Sent By sgraham Date 2002-01-03 Time 09:24 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***