Plan Review Details - Permit 01121259
Plan Review Stops For Permit 01121259
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status C Date 2002-03-04 Cont ID  
Sent By hpiskura Date 2002-03-04 Time 13:58 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-04 00:00:00THE CONVERSION FROM RESIDENTIAL TO "LIVE
 WORK" IS SUBJECT TO IMPACT FEES
 COLLECTED BY THE COUNTY FOR THE CITY.
 THE PERMIT PLANS MUST BE STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 233-5025 FOR MORE
 INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-01-04 Cont ID  
Sent By jwitmer Date 2002-01-04 Time 16:21 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-07-03 Cont ID  
Sent By btrobaug Date 2002-07-03 Time 13:02 Rev Time 0.00
Received By btrobaug Date 2002-07-03 Time 12:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-05-16 Cont ID  
Sent By dpalmer Date 2002-05-16 Time 09:46 Rev Time 0.00
Received By dpalmer Date 2002-05-16 Time 09:46 Sent To  
Notes
2002-05-16 00:00:00*************** UNSAT ***************
  
 1 )NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
 PLEASE SHOW TRACK LIGHTING PER 220-12B
 PLEASE ALSO NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
  
 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS AND CORRELATE WITH PANEL
 SCHEDULES SUBMITTED. USE HAS CHANGED .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-806 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-25 Cont ID  
Sent By dpalmer Date 2002-02-25 Time 07:09 Rev Time 0.00
Received By dpalmer Date 2002-02-25 Time 07:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-12-26 Cont ID  
Sent By dpalmer Date 2001-12-26 Time 20:27 Rev Time 0.00
Received By dpalmer Date 2001-12-26 Time 20:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-02-22 Cont ID  
Sent By mcarsill Date 2002-02-22 Time 12:52 Rev Time 0.00
Received By mcarsill Date 2002-02-22 Time 12:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-12-27 Cont ID  
Sent By mcarsill Date 2001-12-27 Time 12:58 Rev Time 0.00
Received By mcarsill Date 2001-12-27 Time 12:58 Sent To  
Notes
2001-12-27 00:00:001) THE EXISTING ELECTRIC POWERED SMOKE
 DETECTORS ARE TO REMAIN WITHIN THE
 UNITS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-12-31 Cont ID  
Sent By pkrauss Date 2001-12-31 Time 15:14 Rev Time 0.40
Received By pkrauss Date 2001-12-31 Time 15:14 Sent To  
Notes
2001-12-31 00:00:00 
  
 MECHANICAL PLANS NOT INCLUDED WITH THIS
 PERMIT APPLICATION.PLEASE PROVIDE
 PLANS WITH MECHANICAL PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-05-22 Cont ID  
Sent By kstevens Date 2002-05-22 Time 14:30 Rev Time 0.00
Received By kstevens Date 2002-05-22 Time 14:30 Sent To  
Notes
2002-05-22 00:00:00PASSED/PROVISO
  
 SANT RISER DIAGRAM OK - PRODUCT APPROVAL
 DETAIL FOR FLOOR MEMBRANE IN AREA OF
 FLOOR DRAIN REQUIRED.

Review Stop P PLUMBING
Rev No 3 Status N Date 2002-03-05 Cont ID  
Sent By lmartine Date 2002-03-05 Time 16:01 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2002-02-10 Cont ID  
Sent By pschmitz Date 2002-02-10 Time 07:59 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-02-10 00:00:00PLUMBING PLAN REVIEW,PROVISO, PROVIDE
 A DETAIL FOR THE INSTALLATION OF FLOOR
 DRAINS TO COMPLY WITH SPC-94,SEC 409.8.2
 REQUIRED FLOOR DRAINS SHALL MEET THE
 DESIGN CRITERIA FOR SHOWER DRAINS,409.8
 PRIOR TO PLUMBING PERMIT, ISSUED.
 END OF COMMENTS, PAUL SCHMITZ
 561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-12 Cont ID  
Sent By kstevens Date 2002-01-12 Time 14:27 Rev Time 1.00
Received By kstevens Date 2002-01-12 Time 14:26 Sent To  
Notes
2002-01-12 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) EXISTING FLOOR PLAN REQUIRED TO SEE
 WHAT IS CHANGED.
 2) NEW LAUNDRY FLOOR DRAIN. PLEASE GIVE
 DETAILS FOR AREA. SHOW HOW THE FLOOR
 WILL BE SEALED IN AREA OF DRAIN. FLOOR
 DRAIN SHALL HAVE A TRAP PRIMER.
 3) PLEASE INDICATE WHAT THE COMMERCIAL
 SINKS WILL BE USED FOR.
 4) SANITARY RISER DIAGRAM REQUIRED FOR
 FLOOR DRAIN TO SHOW HOW IT IS TIED INTO
 EXISTING SYSTEM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-12 Cont ID  
Sent By sgraham Date 2002-02-12 Time 16:16 Rev Time 0.25
Received By sgraham Date 2002-02-11 Time 14:09 Sent To  
Notes
2002-02-11 00:00:00DENIED SEE APPLICATION AND FRONT PAGE
 NOTE SCREEN.