Plan Review Details - Permit 01121242
Plan Review Stops For Permit 01121242
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-02-15 Cont ID  
Sent By jwitmer Date 2002-02-15 Time 09:11 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2002-02-15 00:00:00PROVISO: NOTE #6 G. C. TO PROVIDE
 PRODUCT TESTING REPORT FOR NEW EXTERIOR
 DOORWAY 124 C.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-05 Cont ID  
Sent By jwitmer Date 2002-01-05 Time 12:42 Rev Time 2.50
Received By jwitmer Date 2002-01-05 Time 10:59 Sent To  
Notes
2002-01-05 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01121242
 1400 NORTHPOINT PARKWAY # 40
 CONT BUTTERS CONSTRUCTION
 TEL: (954)570-8111
  
 SBC= 1997 STANDARD BUILDING CODE
 FL ACC= 1997 FLORIDA ACCESSIBILITY CODE
  
 1)- WAREHOUSE- BSC 104.2.2. ADDITIONAL
 INFORMATION REQUIRED, THE TYPES OF MATER
 IALS TO BE STORED, QUANITIES, TYPE OF
 STORAGE UNITS, RACKS, THE HEIGTH OF THE
 RACKS, WILL FIRE SPRINKLERS BE INCORP-
 ARATED INTO THE RACK SYSTEMS? THIS ADDI-
 TIONAL INFORMATION SHALL BE NECESSARY
 BEFORE WE WILL BE ABLE TO CLASSIFY THE
 OCCUPANCY OF THE WAREHOUSE.
  
 2)- ROOM # 144 SHOWROOM, WITHOUT A LAY-
 OUT OF FURNATURE OR BETTER DISCRIPTION
 OF THE USE OF THIS ROOM, IT MAY APPEAR
 TO BE A, A-2 SMALL ASSEMBLY USAGE,
 1840 SQ FT @ 15 FT/PERSON= 122 OCCUPANTS
 IN THIS CASE (2) PROBLEMS OCCUR: (1)
 SBC TABLE 704.1 SHALL REQUIRE 2 HR SEPER
 ATION/ W 1 1/2 HR OPENING PROTECTION.
 704.1.2.2 THIS SPACE DOES NOT FALL UNDER
 EXEMPTIONS FOR ACCESSORY UES.(2) DOOR
 144B WOULD HAVE TO REVERSE THE SWING OF
 THE DOORS PER SBC 1004.1.2.(ROOMS WITH
 AN OCC LOAD > 50.
  
 3)- SHEET A-8 DETAIL "A" DEPICTS A 2 HR
 WALL ASSEMBLY, A UL LISTING OR U.S.
 GYPSUM NUMBER REQUIRED. SBC 705.1.2.
 WHAT TYPE OF FIRESTOP SYSTEM WILL BE
 USED AT THE METAL ROOF DECK ?
  
 4)- WAREHOUSE EGRESS:SBC 1001.1.3:
 IT IS CRITICAL THAT THE REQUIRED MEANS
 OF EGRESS BE DESIGNATED AND MAINTAINED
 TO INSURE THAT THESE OBSTRUCTIONS ARE
 ELIMINATED, SPECIAL MARKINGS OR SOME
 TYPE OF RAILING OR SCREENING MAY BE USED
 TO SEPERATE THEDESIGNATED MEANS OF
 EGRESS FROM THE STORAGE USE.
  
 5)- SHEET A-6/2 STAIR DETAIL, MORE
 INFORMATION SHALL BE REQUIRED. THERE IS
 NO INFORMATION ON THE SIDE WALLS OF THE
 ELEVATED LANDING. THE DETAIL ALSO INDICA
 TES AN EXISTING SLAB THAT CONTINUES
 UNDER THE BUILDING?!!
 GIVE THE CORRECT RISE & RUN SBC 1007.3.1
 NOT 7T@6 25/32. FOR THE GAURDRAIL INFOR-
 MATION LOOK AT THE 4" SPHERE DETAILED
 VS. SBC 1015.3, BOTTOM RAIL OF GUARDRAIL
 CLEARENCE FROM LANDING 2" NOT 4".
  
 6)- SHEET A-4 DETAIL A6/1 NEW EXTERIOR
 DOORWAY, SBC 1606.2.6.2 COMPONENTS AND
 CLADDING, PROVIDE 2 COPIES OF PRODUCT
 TESTING REPORT FOR LARGE MISSLE IMPACT
 RESISTANCE TESTING.EITHER SBCCI OR DADE
 COUNTY REPORTS ARE ACCEPTED.
  
 7)- PUBLIC RESTROOMS: SBC 1204.2
 SCHEDULE MISSING INFORMATION FOR CT-2?
  
 FLORIDA ACCESSIBILITY CODE:
 8)- DOOR 104-A 4.22.2/4.23.2 DOORS
 ACCESSIBILE TO BATHROOM SHALL COMPLY
 WITH 4.13 DOORS SHALL NOT SWING INTO THE
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 9)- DOOR114-A SAME AS ABOVE.
  
 10)- MENS RESTROOM WATERCLOSET STALLS:
 4.17.3(2) SIZE & ARRANGEMENT ACCESSIBLE
 WATER CLOSET SHALL BE LOCATED IN THE
 CORNER DIAGONAL TO THE DOOR.
  
 SHEET# 5 DETAIL #1 UPPER CABINETS & THE
 MICROVAWE ARE OUT OF REACH, 4.2 SPACE
 & REACH RANGE, SEE ALSO A-5-10 &
 A-5 SEC 11.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-02-28 Cont ID  
Sent By dpalmer Date 2002-02-28 Time 12:17 Rev Time 0.00
Received By dpalmer Date 2002-02-28 Time 12:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-12 Cont ID  
Sent By dpalmer Date 2002-02-12 Time 07:16 Rev Time 0.00
Received By dpalmer Date 2002-02-12 Time 07:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-12-27 Cont ID  
Sent By dpalmer Date 2001-12-27 Time 17:15 Rev Time 0.00
Received By dpalmer Date 2001-12-27 Time 17:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-02-28 Cont ID  
Sent By mcarsill Date 2002-02-28 Time 08:27 Rev Time 0.00
Received By mcarsill Date 2002-02-28 Time 08:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-02-15 Cont ID  
Sent By mcarsill Date 2002-02-15 Time 11:02 Rev Time 0.00
Received By mcarsill Date 2002-02-15 Time 11:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-28 Cont ID  
Sent By mcarsill Date 2001-12-28 Time 11:10 Rev Time 0.00
Received By mcarsill Date 2001-12-28 Time 11:10 Sent To  
Notes
2001-12-28 00:00:001) NO FIRE SPRINKLER PLANS PROVIDED WITH
 DRAWINGS.
 2) PLEASE INDICATE THE RATING OF THE
 DEMISING WALL BETWEEN THE WAREHOUSE AND
 THE ADJACENT TENANT.
 3) LOCKS PROVIDED ON EXIT DOORS SHALL
 NOT REQUIRE THE USE OF A KEY, TOOL,
 SPECIAL KNOWLEDGE OR EFFORT.
 RE: NFPA 101, THE LIFE SAFETY CODE,
 SECTION 5-2.1.5.1.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-04-30 Cont ID  
Sent By ndenmark Date 2002-04-30 Time 12:37 Rev Time 0.25
Received By ndenmark Date 2002-04-30 Time 12:37 Sent To  
Notes
2002-04-30 00:00:00REVISION ON 3 PC 90'S INSTEAD OF TURNING
 VANES LETTER

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-02-28 Cont ID  
Sent By pkrauss Date 2002-02-28 Time 10:48 Rev Time 0.40
Received By pkrauss Date 2002-02-28 Time 10:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-02-13 Cont ID  
Sent By pkrauss Date 2002-02-13 Time 10:56 Rev Time 0.40
Received By pkrauss Date 2002-02-13 Time 10:37 Sent To  
Notes
2002-02-13 00:00:00******************PROVISO***************
  
  
 PROVIDE MANUFACTURER SUBMITTAL DATA &
 INSTALLATION INSTRUCTIONS FOR THE
 CONDENSER UNIT STAND.
  
 NOTE: 18" MINIMUM BETWEEN THE ROOF
 SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL. COUNTY WIDE
 AMENDMENTS 1997 SMC 304.2.5.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-01-23 Cont ID  
Sent By pkrauss Date 2002-01-23 Time 10:04 Rev Time 1.30
Received By pkrauss Date 2002-01-17 Time 12:59 Sent To  
Notes
2002-01-23 00:00:00******************DENIED****************
  
  
 1.2 HR SEPERATION BETWEEN WAREHOUSE
 AND OFFICES, PLAN SHEET M2.1 SHOW
 THE 1 1/2 HOUR RATED DOORS BEING
 UNDERCUT.PLEASE CLARIFY.
  
 2.IN REFERENCE TO BUILDING PLAN REVIEW
 COMMENTS #2, SHOULD THE "SHOWROOM"
 HAVE A 2 HR RATING, FIRE DAMPERS ARE
 REQUIRED FOR ANY DUCT PENETRATIONS.
 PLEASE REVISE PLANS ACCORDINGLY.
  
 3.PLEASE CLARIFY THE USE OF THE "PHOTO
 MODEL SHOP" AND THE "PRODUCTION
 DEVELOPMENT" AREAS.INDICATE WHAT
 TYPE OF WORK IS TO BE DONE IN THESE
 ROOMS.
  
 4.INDICATE ON THE PLANS THE USE OF
 THE WAREHOUSE.REFERENCE BUILDING
 PLAN REVIEW COMMENTS #1.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-02-11 Cont ID  
Sent By kstevens Date 2002-02-11 Time 15:55 Rev Time 1.00
Received By kstevens Date 2002-02-11 Time 15:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-12 Cont ID  
Sent By kstevens Date 2002-01-12 Time 17:33 Rev Time 2.50
Received By kstevens Date 2002-01-12 Time 17:33 Sent To  
Notes
2002-01-12 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) MINIMUM FACILITIES FOR OFFICE SPACE
 OK, BUT WAREHOUSE USE IS UNCLEAR. WHAT
 TYPE OF WAREHOUSING IS GOING TO BE IN
 THIS SPACE. ACCORDING TO SHT A1, 43
 PEOPLE WILL BE WORKING IN THE WAREHOUSE.
 FACILITIES SHALL BE REQUIRED FOR THOSE
 PEOPLE ALSO AT A RATE OF 2 MALE W/C'S &
 2 LAVS AND 2 FEMALE W/C'S & 2 LAVS. 1
 DRINKING FOUNTAIN IS REQUIRED FOR WARE-
 HOUSE ALSO.
 2) SHTS A4 & A5 RESTROOMS 104 & 114. PER
 FACBC SEC 4.22.2 & 4.22.3 DOORS TO AN
 ADAPTABLE TOILET SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE OF ANY FIXTURE.
 3) SHTS A4 & A5. MINIMUM FACILITIES SHOW
 2 DRINKING FOUNTAINS REQUIRED. A HI-LOW
 IS CONSIDERED 1 FIXTURE. 1 MORE DRINKING
 FOUNTAIN IS REQUIRED. SPC TABLE 407
 4) SHTS A4 & A5, MENS RESTROOM HDCP
 STALL, W/C SHALL BE LOCATED IN THE COR-
 NER DIAGONAL FROM STALL DOOR. FACBC SEC
 4.17.3(2).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377