2002-01-05 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 01121242 |
| 1400 NORTHPOINT PARKWAY # 40 |
| CONT BUTTERS CONSTRUCTION |
| TEL: (954)570-8111 |
| |
| SBC= 1997 STANDARD BUILDING CODE |
| FL ACC= 1997 FLORIDA ACCESSIBILITY CODE |
| |
| 1)- WAREHOUSE- BSC 104.2.2. ADDITIONAL |
| INFORMATION REQUIRED, THE TYPES OF MATER |
| IALS TO BE STORED, QUANITIES, TYPE OF |
| STORAGE UNITS, RACKS, THE HEIGTH OF THE |
| RACKS, WILL FIRE SPRINKLERS BE INCORP- |
| ARATED INTO THE RACK SYSTEMS? THIS ADDI- |
| TIONAL INFORMATION SHALL BE NECESSARY |
| BEFORE WE WILL BE ABLE TO CLASSIFY THE |
| OCCUPANCY OF THE WAREHOUSE. |
| |
| 2)- ROOM # 144 SHOWROOM, WITHOUT A LAY- |
| OUT OF FURNATURE OR BETTER DISCRIPTION |
| OF THE USE OF THIS ROOM, IT MAY APPEAR |
| TO BE A, A-2 SMALL ASSEMBLY USAGE, |
| 1840 SQ FT @ 15 FT/PERSON= 122 OCCUPANTS |
| IN THIS CASE (2) PROBLEMS OCCUR: (1) |
| SBC TABLE 704.1 SHALL REQUIRE 2 HR SEPER |
| ATION/ W 1 1/2 HR OPENING PROTECTION. |
| 704.1.2.2 THIS SPACE DOES NOT FALL UNDER |
| EXEMPTIONS FOR ACCESSORY UES.(2) DOOR |
| 144B WOULD HAVE TO REVERSE THE SWING OF |
| THE DOORS PER SBC 1004.1.2.(ROOMS WITH |
| AN OCC LOAD > 50. |
| |
| 3)- SHEET A-8 DETAIL "A" DEPICTS A 2 HR |
| WALL ASSEMBLY, A UL LISTING OR U.S. |
| GYPSUM NUMBER REQUIRED. SBC 705.1.2. |
| WHAT TYPE OF FIRESTOP SYSTEM WILL BE |
| USED AT THE METAL ROOF DECK ? |
| |
| 4)- WAREHOUSE EGRESS:SBC 1001.1.3: |
| IT IS CRITICAL THAT THE REQUIRED MEANS |
| OF EGRESS BE DESIGNATED AND MAINTAINED |
| TO INSURE THAT THESE OBSTRUCTIONS ARE |
| ELIMINATED, SPECIAL MARKINGS OR SOME |
| TYPE OF RAILING OR SCREENING MAY BE USED |
| TO SEPERATE THEDESIGNATED MEANS OF |
| EGRESS FROM THE STORAGE USE. |
| |
| 5)- SHEET A-6/2 STAIR DETAIL, MORE |
| INFORMATION SHALL BE REQUIRED. THERE IS |
| NO INFORMATION ON THE SIDE WALLS OF THE |
| ELEVATED LANDING. THE DETAIL ALSO INDICA |
| TES AN EXISTING SLAB THAT CONTINUES |
| UNDER THE BUILDING?!! |
| GIVE THE CORRECT RISE & RUN SBC 1007.3.1 |
| NOT 7T@6 25/32. FOR THE GAURDRAIL INFOR- |
| MATION LOOK AT THE 4" SPHERE DETAILED |
| VS. SBC 1015.3, BOTTOM RAIL OF GUARDRAIL |
| CLEARENCE FROM LANDING 2" NOT 4". |
| |
| 6)- SHEET A-4 DETAIL A6/1 NEW EXTERIOR |
| DOORWAY, SBC 1606.2.6.2 COMPONENTS AND |
| CLADDING, PROVIDE 2 COPIES OF PRODUCT |
| TESTING REPORT FOR LARGE MISSLE IMPACT |
| RESISTANCE TESTING.EITHER SBCCI OR DADE |
| COUNTY REPORTS ARE ACCEPTED. |
| |
| 7)- PUBLIC RESTROOMS: SBC 1204.2 |
| SCHEDULE MISSING INFORMATION FOR CT-2? |
| |
| FLORIDA ACCESSIBILITY CODE: |
| 8)- DOOR 104-A 4.22.2/4.23.2 DOORS |
| ACCESSIBILE TO BATHROOM SHALL COMPLY |
| WITH 4.13 DOORS SHALL NOT SWING INTO THE |
| FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| |
| 9)- DOOR114-A SAME AS ABOVE. |
| |
| 10)- MENS RESTROOM WATERCLOSET STALLS: |
| 4.17.3(2) SIZE & ARRANGEMENT ACCESSIBLE |
| WATER CLOSET SHALL BE LOCATED IN THE |
| CORNER DIAGONAL TO THE DOOR. |
| |
| SHEET# 5 DETAIL #1 UPPER CABINETS & THE |
| MICROVAWE ARE OUT OF REACH, 4.2 SPACE |
| & REACH RANGE, SEE ALSO A-5-10 & |
| A-5 SEC 11. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561)659-8096 X8412. |