Plan Review Details - Permit 01120926
Plan Review Stops For Permit 01120926 |
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2002-01-28 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-01-28 |
Time |
13:10 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2002-01-28 |
Time |
10:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-01-15 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-01-15 |
Time |
14:23 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2002-01-15 |
Time |
14:23 |
Sent To |
|
|
Notes |
2002-01-15 00:00:00 | **************PROVISO******************* | | 1)RESUBMIT WITH CORRECT LIGHT FIXTURE. | | 2)RESUBMIT CORRECT RISER DIAGRAM WITH | | CONDUIT TYPE AND EQUIPMENT GROUND. | | 3) INDICATE ORIGIN OF TRANSFORMER FEED. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | (561) 659-8096 EXT.8392 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-12-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-24 |
Time |
15:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-12-24 |
Time |
15:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-12-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-18 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-12-18 |
Time |
09:45 |
Sent To |
|
|
Notes |
2001-12-18 00:00:00 | *************** UNSAT *************** | | | | 1)NOTE: PLEASE NOTE NO MAIN DISCONNECT | | SHOWN AT DETACHED STRUCTURE.ART 225-31 | | | | 2)NOTE: PLEASE NOTE EASEMENT ISSUE STILL | | NEEDS TO BE RESOLVED. | | | | 3)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | IS SHOWN COMING FROM PANEL THAT FEEDS | | COMMON STREET LIGHTING, PLEASE ALSO | | NOTE THAT SERVICE IS SUPPOSED TO BE | | COMING FROM A NEW SEPARATE METER FROM | | FPL, FROM ELEC ROOM IN "A" BLOCK/?? | | PLEASE CLARIFY | | | | 4)NOTE: PLEASE CLARIFY 4-2/0`S IS | | ONE OF THESE A GROUNDING CONDUCTOR? | | PLEASE CLARIFY TRANSFORMER GROUND? | | 250-30 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | | | BILL STAPLES | | ASST BUILDING OFFICIAL | | 659-8096 EXT 8315 | | FOR ANY EASEMENT QUESTIONS. |
|
|
|