Plan Review Details - Permit 01120918
Plan Review Stops For Permit 01120918
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-15 Cont ID  
Sent By dpalmer Date 2002-03-27 Time 07:33 Rev Time 3.50
Received By jwitmer Date 2002-03-15 Time 11:35 Sent To  
Notes
2002-03-15 00:00:00BUILDING PLAN REVIEW
 01120918
 727 SUNSET
  
 ********PROVISO*********
 1) SHEET A-7 TWO- STORY WALL SECTION,
 INDICATES THAT 2X4 WOOD TRUSSES MAKE UP
 THE SECOND STORY CEILING / ROOF FRAMING
 ASSEMBLY. ENGINEER TO CERTIFY THAT THE
 TRUSSES WILL ACCEPT THE ADDTIONAL LOAD-
 ING. IF DIAGONAL WEBBING REMOVED ENGIN-
 EER IS TO DESIGN THE TRANSFER OF LOADING
  
 2) THE NEW STAIRWAY LEADING TO THE 3RD
 FLOOR INDICATES A TRUE 3RD FLOOR.TABLE
 500 REQUIRES A 1 HR RATING, THIS IS ACCO
 MPLISHED THROUGH TABLE 709.6.2A & B
 TIME ASSIGNED TO WOOD FRAMING, INSULA-
 TION & WALLBOARD MEMBRANE.
  
 3) THE 3RD STORY IF CONVERTED FROM
 STORAGE TO A HABITAL OCCUPANCY SHALL
 NEED TO MEET THE FOLLOWING CODE SECTIONS
 1997 STANDARD BUILDING CODE
 1203.1 7'-6" CEILING HEIGTH.
 1203.2.2. SLOPED CEILING, 1/2 AREA THERE
 OF.
 1004.1.2 EVERY ROOM OR TENANT SPACE
 SHALL BE PROVIDED WITH A MINIMUM OF ONE
 MEANS OF EGRESS.1004.1 FOR EVERY SLEEP-
 ING ROOM ON THE 1ST, 2ND OR 3RD STORY
 AAT LEAST ONE EXTERIOR EMERGENCY ESCAPE
 AND RESCUE OPENING IS REQUIRED. FOR THE
 3RD FLOOR A MINIMUM OF 5.7 SQ. FT OF
 CLEAR OPEN AREA PER SLEEPING ROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-07 Cont ID  
Sent By pkrauss Date 2002-03-13 Time 14:54 Rev Time 4.00
Received By jwitmer Date 2002-01-07 Time 13:17 Sent To  
Notes
2002-01-07 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01120918
 727 SUNSET RD.
 CONT.: ROGER G. THOMAS
 TEL: (561)575-1389
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- NOTICE OF COMMENCEMENT MUST BE RE-
 CORDED AT THE COUNTY COURTHOUSE BEFORE
 THE PERMIT MAY BE ISSUED.
  
 2)- SBC 1804.2.7.2 SOILS TEST TO VERIFY
 THE MINIMUM SAFE BEARING VALUE.
  
 3)- ADDITIONAL INFORMATION REQUIRED:
 AVERAGE EAVE HEIGTH=
 BASIC PRESSURE=
 SHEET A-2 MISSING THIS INFORMATION. THE
 PRESSURE ZONES FOR ALL EXTERIOR OPENINGS
 (WINDOWS & DOORS) SHOW ON ELEVATIONS.
  
 4)-MISSING ENERGY CALCS,
  
 5)- SHEET A-4 DEPICTS A THIRD STORY,
 ATTIC LOFT AND FUTURE BATH, THIS WOULD
 REQUIRE THIS STRUCTURE TO BE A TYPE VI
 1-HOUR PROTECTED BUILDING.
 A) TABLE 600 TYPE V1 PROTECTED INDICATE
 THE 1 HR PROTECTION FOR ALL STRUCTUR
 AL MEMBERS AS REQUIRED BY TABLE 600.
 B) GIVE A CUT SECTION THROUGH THE 3
 FLOORS INDICATING THE HEIGTH OF EACH
 STORY, SBC 1203.2.1 OCCUPLIABLE ROOMS
 AND HABITABLE SPACES SHALL NOT HAVE A
 CEIL LESS THAN 7'-6", STORAGE, BATHROOMS
 MAY BE 7'-0". IF ANY ROOM IN A BUILDING
 HAS A SLOPING CEILING, THE PRESCRIBED
 CEILING HEIGTH FOR THE ROOM IS REQUIRED
 IN ONLY 1/2 THE AREA THEREOF.(1203.2.2)
 6) SHEET A-6
 DISCREPANCY BETWEEN FLOOR PLAN NEW
 WINDOWS AND SHEETS 5/SHEET6. IN REVIEW-
 ING PLANS WITH HISTORICS THEY INDICATE
 THAT NEITHER DRAWING IS CORRECT BUT
 CASEMENT WINDOWS SHALL BE INSTALLED?
  
 7) SHEET A-5 INDICATES WINDOWS WITH MULL
 ION, WINDOW REPORT INDICATES THAT THIS
 REPORT IS FOR SINGLE UNIT APPLICATION.
 REPORT REQUIRED FOR MULLION.
  
 8) FRENCH DOOR REPORT SHALL REQUIRE
 LARGE MISSLE IMPACT RESISTANCE PROTEC-
 TION.
  
 9) SHEET A-11 THE FIRST FLOOR FRAMING
 PLAN INDICATES A DOUBLE 2X12 BEAM AROUND
 THE PERIMETER OF THE PORCH, WHAT TYPE
 OF SUPPORT IS USED WHERE WOOD BEAM ENDS
 AT WALL LINE? SECTION OF KITCHEN WHERE
 WALL WAS REMOVED, WHAT TYPE OF CONNEC-
 TION IS TO BE USED FOR 6X6 POST AND FOR
 GIRDER, DOES THE EXISTING 2ND FLOOR
 JOIST BEAR ON THIS WALL?
  
 10)- SHEET A-7 SECTION 2 STORY INDICATES
 STUCCO ALL THE WAY TO THE GROUND, A 6"
 AIR GAP REQUIRED TERMITE PROTECTION,
 SBC2304.2.5 AMENDMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-04-24 Cont ID  
Sent By btrobaug Date 2002-04-24 Time 13:14 Rev Time 0.00
Received By btrobaug Date 2002-04-12 Time 07:58 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-27 Cont ID  
Sent By dpalmer Date 2002-03-27 Time 05:42 Rev Time 0.00
Received By dpalmer Date 2002-03-27 Time 05:42 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-08 Cont ID  
Sent By dpalmer Date 2002-03-08 Time 16:04 Rev Time 0.00
Received By dpalmer Date 2002-03-08 Time 16:04 Sent To P
Notes
2002-03-08 00:00:00*************** UNSAT *****************
  
 PLEASE NOTE THAT NOTES 1,2,3 FROM FIRST
 REVIEW WERE NOT DONE.
  
 1)NOTE: PLEASE NOTE THAT NOTE#1 HAS
 2/0`S FOR 250AMP SERVICE? PLEASE NOTE
 THAT WHEN PLANS CAME BACK, THE CONDUCTOR
 SIZE WENT EVEN SMALLER, DOWN TO 1/0`S?
 PLEASE NOTE THAT CONDUCTORS ARE TO BE
 SIZED PER NEC 310-15/16.
 310-15, 250A SERVICE IS A MIN OF 4/0`S.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT THIS IS REQ`D AT TIME
 OF REVIEW OF PLANS. 110-9/215-5.
  
 3)NOTE: PLEASE NOTE THAT RISER STILL
 DOES NOT SHOWN AN EQUIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN DISCONNECT AND
 PANEL. 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, PLEASE CALL IF THERE
 ARE ANY QUESTIONS,OR GOING OVER THE PLAN
 -S WOULD BE BETTER SUITED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-24 Cont ID  
Sent By dpalmer Date 2001-12-24 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2001-12-24 Time 10:39 Sent To P
Notes
2001-12-24 00:00:00************* **** UNSAT ***************
  
 1)NOTE: PLEASE NOTE SERVICE MAIN IS
 SHOWN AT 225A WITH 250A MAIN??? AND
 WIRE FOR 200AMPS 310-15/310-16
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDCUTOR 250-122
 BETWEEN MAIN AND PANEL.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 6) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 7)NOTE: PLEASE CLARIFY GFI PROTECTION
 FOR SCREENED PORCH RECEPTS.
  
 PLEASE SUBMIT ALL OF THE ABOVE INFORMAT-
 -ION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-03-13 Cont ID  
Sent By kstevens Date 2002-03-13 Time 14:56 Rev Time 0.50
Received By pkrauss Date 2002-03-13 Time 13:58 Sent To B
Notes
2002-03-13 00:00:00 
 MECHANICAL PERMIT REQUIRED.
  
 PROVISO:DUCTS SHALL NOT BE INSTALLED
 IN OR WITHIN 4" OF THE GROUND.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-12-31 Cont ID  
Sent By pkrauss Date 2001-12-31 Time 13:28 Rev Time 0.40
Received By pkrauss Date 2001-12-31 Time 13:15 Sent To B
Notes
2001-12-31 00:00:00 
  
 MECHANICAL PLANS NOT INCLUDED WITH THIS
 SUBMITTAL.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 INDICATE ON PLAN CALCULATION FOR GAS
 APPLIANCES IN LAUNDRY ROOM.REFERENCE
 1997 SMC CHAPTER 2, "CONFINED SPACE".
 SHOW COMPLIANCE WITH 1997 SMC 704.3.
 PLEASE SUBMIT MANUFACTURE SUBMITTAL
 DATA FOR GAS APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-05-01 Cont ID  
Sent By kstevens Date 2002-05-01 Time 12:03 Rev Time 0.00
Received By kstevens Date 2002-05-01 Time 12:03 Sent To  
Notes
2002-05-01 00:00:00SEPARATE PLANS AND PERMIT FOR GAS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-04-24 Cont ID  
Sent By kstevens Date 2002-04-24 Time 14:13 Rev Time 0.00
Received By kstevens Date 2002-04-24 Time 14:13 Sent To  
Notes
2002-04-24 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97
  
 1) SHT A-4 KITCHEN / LAUNDRY ROOM SANT.
 RISER DIAGRAM DOES NOT REFLECT FLOOR
 PLAN. SHOWS KITCHEN SINK BEING TAKEN OFF
 BEFORE SALAD SINK.
 2) SHT A-4 SHOWS CLOUD AT RISER DIAGRAM
 FOR SANT., 2ND FLOOR W/C - BIDET BUT
 NOT ON FLOOR PLAN. PLEASE CLARIFY.
 3) SEPARATE PERMIT REQUIRED FOR GAS.
 PLEASE PROVIDE GAS PERMIT APPLICATION
 REQUIREMENT INFORMATION AS FOLLOWS.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE STANDARD GAS CODE SECS. 305.2 THRU
 305.4 AND TABLES 305.4(A) THRU 305.4(E).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE STANDARD GAS CODE SEC. 305.4(I).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER THE STANDARD GAS
 CODE SECS. 402.4 THRU 402.4.4.7.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 602 THRU 612.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-03-13 Cont ID  
Sent By btrobaug Date 2002-04-24 Time 13:15 Rev Time 1.00
Received By kstevens Date 2002-03-13 Time 14:55 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-12-29 Cont ID  
Sent By pkrauss Date 2002-03-13 Time 14:54 Rev Time 1.00
Received By jleech Date 2001-12-29 Time 10:47 Sent To  
Notes
2001-12-29 00:00:00DENIED;
 1.SHOW EXISTING BUILDING DRAIN (SIZE)
 AND LOCATION. ALSO WHERE NEW PLUMBING
 WILL TIE INTO.
 2.RISER DIAGRAM ARE NOT TO CODE;
 2ND FL. WATER CLOSET FLUSHES PAST
 THE BIDET.
 ATTIC BATH 3" MIN. PIPE REQUIRED
 FOR A WATER CLOSET.
 3.LAUNDRY AND MECH ROOMS MAYBE TOO SMALL
 FOR GAS APPLIANCES. SEE "CONFINED
 SPACE" IN THE 97 SMC CHAPTER 2. USE
 FOURMULA OF 50 CU. FT. PER 1000 BTU"S
 TO FIND AREA REQUIRED. VENTS MY BE
 REQUIRED.
 4.A SEPORATE GAS PERMIT IS REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2001-12-19 Cont ID  
Sent By sgraham Date 2001-12-19 Time 10:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***