Plan Review Details - Permit 01120902
Plan Review Stops For Permit 01120902
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-27 Cont ID  
Sent By rbrown Date 2002-03-27 Time 15:19 Rev Time 0.00
Received By rbrown Date 2002-03-27 Time 15:19 Sent To  
Notes
2002-03-27 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 --PROVISO--
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 --PROVISO--
 A SOIL LETTER SHALL BE SUBMITTED TO THIS
 OFFICE, SIGNED AND SEALED, CERTIFYING
 SOIL PREPARATION WAS COMPLETED AND A
 BEARING VALUE OF OF 2500 PSF HAS BEEN
 ACHIEVED BEFORE CONSTRUCTION
  
 --PROVISO--
 A SEPARATE SHUTTER PERMIT APPLICATION IS
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-13 Cont ID  
Sent By rbrown Date 2002-02-13 Time 20:22 Rev Time 0.00
Received By rbrown Date 2002-02-13 Time 20:22 Sent To  
Notes
2002-02-13 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC 1804.1.3SHEET S-1, SECTION 1.
 THE BASE OF THE EXTERIOR WALL FOUNDATION
 SHALL BE AT LEAST 12" BELOW FINISH GRADE
  
 3) SBC* 1804.2A SOIL REPORT SHALL BE
 SUBMITTED TO CONFIRM THE DESIGN
 ASSUMPTIONS.
  
 4) SBC 2309.2 AND SBC* 104.2SUBMIT
 SIGNED AND SEALED TRUSS SHOP DRAWINGS
 ANDDESIGN CALCULATIONS.
  
 5) SHEET S-1, SECTION 5 AND 'NOTE 2'.
 THE STATED 'USP' RTPGA820 AND RTPGA824
 ARE NOT VALID USP CONNECTOR REFERENCES.
 AMEND THE NOTES TO CLARIFY THE PROPOSALS
  
 6) SBC* 1707.4 AND SBC* 104.1.1 EXTERIOR
 DOOR ASSEMBLIES.THE SUBMITTED PRODUCT
 APPROVAL STATES THAT HURRICANE SHUTTERS
 ARE REQUIRED.A SEPARATE SHUTTER PERMIT
 APPLICATIO IS REQUIRED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-28 Cont ID  
Sent By dpalmer Date 2002-03-28 Time 06:43 Rev Time 0.00
Received By dpalmer Date 2002-03-28 Time 06:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-05 Cont ID  
Sent By dpalmer Date 2002-02-05 Time 19:23 Rev Time 0.00
Received By dpalmer Date 2002-02-05 Time 19:23 Sent To  
Notes
2002-02-05 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS A MAIN BUT MAIN IS NOT SHOWN ON
 PLANS? PLEASE SHOW.
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING BETWEEN MAIN AND PANEL.
 250-122
  
 3)NOTE: PLEASE NOTE 384-7 AND 110-26,
 PLEASE SHOW LAYOUT FOR REQ`D CLEARENCES
 FOR PANEL IN STORAGE ROOM OR LABEL
 ROOM FOR ELECTRICAL/MECH EQUIPMENT ROOM
 ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-02-01 Cont ID  
Sent By mcarsill Date 2002-02-01 Time 13:45 Rev Time 0.00
Received By mcarsill Date 2002-02-01 Time 13:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-23 Cont ID  
Sent By pkrauss Date 2002-04-23 Time 16:44 Rev Time 0.35
Received By pkrauss Date 2002-04-23 Time 16:43 Sent To  
Notes
2002-04-23 00:00:00PROVISO:MECHANICAL PERMIT 01120942
  
 PLEASE PROVIDE VENTILATION CALCULATIONS
 SHOWING COMPLIANCE WITH ASHRAE 62-89 FOR
 PUBLIC RESTROOMS.
  
 PLEASE PROVIDE PRIOR TO INSPECTIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT.8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-23 Cont ID  
Sent By kstevens Date 2002-04-20 Time 17:43 Rev Time 0.00
Received By kstevens Date 2002-04-20 Time 17:43 Sent To  
Notes
2002-04-20 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) COMMENTS #1 AND #2 FROM PREVIOUS RE-
 VIEW NOT ADDRESSED. PLEASE ADDRESS
 PREVIOUS COMMENTS AND RESUBMIT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-11 Cont ID  
Sent By kstevens Date 2002-02-11 Time 19:29 Rev Time 0.75
Received By kstevens Date 2002-02-11 Time 19:28 Sent To  
Notes
2002-02-11 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLEASE ROUTE PLANS TO PALM BEACH
 COUNTY HEALTH UNIT, 901 EVERNIA ST WPB
 (561) 355-3018 FOR APPROVAL BEFORE SUB-
 MITTING FOR PLAN REVIEW.
 2) BACKFLOW REQUIRED ON WATER SERVICE.
 3) HI/LOW DRINKING FOUNTAIN REQUIRED TO
 MAKE PROVISIONS FOR THOSE WHO HAVE DIFF-
 ICULTY BENDING OR STOOPING. FACBC SEC
 4.1.3(10)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-30 Cont ID  
Sent By sgraham Date 2002-01-30 Time 15:43 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***