Plan Review Details - Permit 01120706
Plan Review Stops For Permit 01120706
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-02-11 Cont ID  
Sent By jwitmer Date 2002-02-11 Time 14:53 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-04 Cont ID  
Sent By jwitmer Date 2002-01-04 Time 08:13 Rev Time 1.75
Received By jwitmer Date 2002-01-04 Time 07:23 Sent To  
Notes
2002-01-04 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01120706
 6710 S DIXIE HWY
 CONT: RAPP
 TEL:802-9997
  
 SBC= 1997 STANDARD BUILDING CODE
 FL ACC CODE= FLORIDA ACCESSIBLITY CODE
 1997 ED
  
 1)- FL ACC CODE 4.1.6 ACCESSIBLE BUILD-
 INGS: ALTERATIONS, SHOW THE ACCESSIBLE
 ROUTE FROM THE POINT OF PUBLIC TRANSPOR-
 TATION & FROM THE HANDICAPPED PARKING!
 4.1.6.2.2ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20%.
  
 2)- WORK ROOM #115 INDICATES THAT A OVER
 HEAD DOOR WILL BE CLOSED UP W/ BLOCK &
 GLASS BLOCK. THERE IS NO DETAILS AS TO
 COLUMNS,LINTEL,BEAMS, HORIZONTAL REIN-
 FORCEMENT KEYING INTO EXESTING COLUMNS
 ETC.
 THERE IS ALSO NO REFRENCE, SPECING OF
 THE GLASS BLOCK, THICK, THIN WALL OR
 SOLID. PROVIDE DETAIL FOR INSTALATION.
 PROVIDE (2 COPIES) OF PRODUCT APPROVAL,
 SBCCI OR DADE COUNTY.
  
 3)- PROVIDE INFORMATION ON ELECTRIC LOCK
 FOR OPENINGS # 9/12 SHOW COMPLIANCE WITH
 SBC 1012.7.
  
 4)- SHEET A-3/E-3 INDICATE EGRESS
 THROUGH STORAGE ROOM # 115. SBC1001.1.3.
 EGRESS THROUGH STORAGE AREAS, THOUGH NOT
 PROHIBITED ASA COMPONENT OF A MEANS OF
 EGRESS, REQUIRES SPECIAL CONSIDERATION.
 IT IS CRITICAL THAT THE MEANS OF OF
 EGRESS BE DESIGNATED AND MAINTAINED TO
 INSURE THAT THESE OBSTRUCTIONS ARE ELIMI
 NATED. SPECIAL MARKINGS OR SOME TYPE OF
 RAILING OR SCREENING MAY BE REQUIRED TO
 SEPERATE THE DESIGNATED MEANS OF EGRESS
 FROM THE STORAGE AREA.
  
 5)- SSSHEET A-6 INDICATES A SOFFIT HUNG
 FROM THE PLASTER CEILING NO INFORMATION
 IS SUPPLIED FOR ATTACHMENT?
  
 6)- SHEET A-9, MISSING INFORMATION FOR
 THE MINIMUM INTERIOR FINISH SCHEDULE AS
 PER SBC TABLE 803.3.
  
 7)- SHEET A-9 PUBLIC RESTROOMS, SBC
 1204.2 THE FLOORS & WALLS OF ALL PUBLIC
 RESTROOMS SHALL BE LINED WITH NONABSORB-
 ANT MATERIALS TO A HEIGTH OF 4' ABOVE
 THE FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-04 Cont ID  
Sent By dpalmer Date 2002-02-04 Time 10:43 Rev Time 0.00
Received By dpalmer Date 2002-02-04 Time 10:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-26 Cont ID  
Sent By dpalmer Date 2001-12-26 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2001-12-26 Time 19:33 Sent To  
Notes
2001-12-26 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO BE SHOWM PER 220-11/-13 ETC.
  
 2)NOTE: PLEASE NOTE, ALL CONTINOUS LOADS
 NEED TO BE SHOWN AT 125%.215-2-3 AND
 230-42.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-30 Cont ID  
Sent By mcarsill Date 2002-01-30 Time 13:42 Rev Time 0.00
Received By mcarsill Date 2002-01-30 Time 13:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-12 Cont ID  
Sent By mcarsill Date 2001-12-12 Time 10:40 Rev Time 0.00
Received By mcarsill Date 2001-12-12 Time 10:40 Sent To  
Notes
2001-12-12 00:00:001) IT APPEARS THAT EXITING OCCURS
 THRU CLOSET 123. THE PLANS ALSO CALLS
 THIS ROOM STORAGE 115. PLEASE BE
 ADVISED THAT EXITING IS NOT PERMITTED
 THRU CLOSETS OR STORAGE ROOMS.
 2) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE ALARM REMODEL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-12-19 Cont ID  
Sent By ndenmark Date 2001-12-19 Time 11:23 Rev Time 0.33
Received By ndenmark Date 2001-12-19 Time 11:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2002-02-11 Cont ID  
Sent By jwitmer Date 2002-02-11 Time 15:28 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***