Plan Review Details - Permit 01120616
Plan Review Stops For Permit 01120616
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-01-25 Cont ID  
Sent By jwitmer Date 2002-01-25 Time 07:34 Rev Time 0.75
Received By jwitmer Date 2002-01-25 Time 07:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-31 Cont ID  
Sent By jwitmer Date 2001-12-31 Time 15:18 Rev Time 3.00
Received By jwitmer Date 2001-12-31 Time 15:18 Sent To  
Notes
2001-12-31 00:00:00BUILDING PLAN REVIEW
 2400 CENTREPARK WEST DRIVE/ #175
 PERMIT # 01120616
 CONT. HEDRICK BROTHERS
 TEL. 689-8880
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 1)- THE ORIGINAL SHELL PERMIT FOR THE
 WAREHOUSE SHOWS THE DUMPSTER LOCATION
 AT A DIFFERENT LOCATION THAN THE TENANT
 BUILD OUT LOCATION. WILL NEED ZONING AND
 ENGINEERING APPROVAL.
  
 2)- THE NEW GAS PUMP LOCATION WILL ALSO
 REQUIRE APPROVAL FROM ZONING AND ENGIN-
 EERING. ADDITIONAL INFORMATION WILL BE
 REQUIRED.INDICATE CODE COMPLIANCE WITH
 SECTIONS 404.2.3-404.2.7.PUMPS AND OTHER
 DISPENSING DEVISES.
  
 3)- SHEET A-1 DOOR #116 AS INDICATED
 NEED TO SWING IN THE DIRECTION OF EGRESS
 WHEN SERVING AN OCCUPANT LOAD OF 50 OR
 MORE. OCCUPANT LOAD FOR OFFICE AREA
 ALONE OVER 50.
  
 4)- SBC104.2.2* ADDITIONAL INFORMATION
 REQUIRED. TYPE OF BUSINESS, TYPE OF
 USEAGE FOR ROOM # 115? WAREHOUSE, TYPE
 OF MATERIALS?3'-0" DEEP RACKS, TYPE OF
 MATERIAL TO BE STORED? HEIGTH OF RACKS?
 INDICATE THE STORAGE AREAS, IT IS CRITIC
 AL THAT THE REQUIRED MEANS OF EGRESS BE
 DESIGNATED & MAINTAINED TO ENSURE THAT
 OBSTRUCTIONS BE ELIMINATED. SPECIAL
 MARKINGS OR SOME TYPE OF RAILING OR
 SCREENING MAY BE USED TO SEPERATE THE
 DESIGNATED MEANS OF EGRESS FROM THE
 STORAGE.
  
 5)- SBC 104.2.2 ADDITIONAL INFORMATION
 ON LIFT, NOTE # 9.
  
 6)- SHEET A-3 THE WRONG ROOM #'S ASSIGN-
 ED TO ELE. OF RESTROOMS.
  
 7)- SBC 1204.2 SURROUNDING MATERIALS,
 THE FLOORS & WALLS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4 FT ABOVE THE
 FLOOR.
  
 8)- FL ACCESS CODE 4.5 FLOOR SURFACES AL
 ONG ACCESSIBLE ROUTES AND IN ACCESSIBLE
 ROOMS & SPACES INCLUDING FLOORS, WALKS,
 RAMPS & STAIRS SHALL BE FIRM, SLIP-
 RESISTANT.ADDAGG 4.5 A STATIC COEFFIC-
 IENT OF FRICTION OF 0.6 IS RECOMMENDED
 FOR ACCESSIBLE ROUTES & 0.8 FOR RAMPS.
  
 9)- MISSING FIRE SPRINKLER DRAWINGS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-22 Cont ID  
Sent By dpalmer Date 2002-01-22 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2002-01-22 Time 12:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-12-12 Cont ID  
Sent By dpalmer Date 2001-12-12 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2001-12-12 Time 19:34 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-01-25 Cont ID  
Sent By mamini Date 2002-01-25 Time 14:07 Rev Time 0.00
Received By mamini Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-17 Cont ID  
Sent By mcarsill Date 2002-01-16 Time 15:25 Rev Time 0.00
Received By mcarsill Date 2002-01-16 Time 15:25 Sent To  
Notes
2002-01-16 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) WITH REGARDS TO FUEL TANK, THE
 FOLLOWING DETAILS ARE TO BE PROVIDED:
 A) SIZE OF TANK
 B) AGE OF TANK
 C) ANY CERTIFICATIONS ON THE TANK
 D) TYPE OF PRODUCT STORED IN THE TANK.
 E) DISTANCES FROM THE BUILDING AND
 ANY PROPERTY LINES.
 F) BOLLARD PROTECTION FROM MECHANICAL
 INJURY.
 G) VENTING OF TANK.
 H) LABELING ON THE TANK.
 THIS INSTALLATION WILL REQUIRE A
 SEPARATE PERMIT SINCE IT IS A FUEL
 INSTALLATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-11 Cont ID  
Sent By mcarsill Date 2001-12-11 Time 15:46 Rev Time 0.00
Received By mcarsill Date 2001-12-11 Time 15:46 Sent To  
Notes
2001-12-11 00:00:001) FIRE ALARM NOTES INDICATES CLASS B,
 STYLE C CIRCUITS. ONLY CLASS A, STYLE
 D CIRCUITS WILL BE ALLOWED.
 2) EXITING IS NOTED THRU THE HUMAN
 RESOURCE RECEPTION AND THE BOARDROOM.
 THESE DOORS CAN NEVER BE LOCKED AS THEY
 COULD PREVENT EXIT ACCESS TO THE EXITS.
 3) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 4) PLEASE INDICATE OCCUPANT LOAD FOR
 OPERATIONS AREA 115. IT WAS NOTED THAT
 ONE OF THE EXIT DOORS OPEN INWARDS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-29 Cont ID  
Sent By kstevens Date 2002-01-29 Time 16:57 Rev Time 0.00
Received By kstevens Date 2002-01-25 Time 15:34 Sent To  
Notes
2002-01-25 00:00:00PROVISO ON PLAN MECH PERMIT 02011225

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-18 Cont ID  
Sent By pkrauss Date 2001-12-18 Time 12:53 Rev Time 0.50
Received By pkrauss Date 2001-12-18 Time 12:48 Sent To  
Notes
2001-12-18 00:00:00*******************DENIED***************
  
  
 PLEASE INDICATE WHAT THE "OPERATIONS"
 AREA IS USED FOR (STORAGE, REPAIR
 SHOP?).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-01-31 Cont ID  
Sent By kstevens Date 2002-01-31 Time 10:27 Rev Time 1.25
Received By kstevens Date 2002-01-31 Time 10:27 Sent To  
Notes
2002-01-31 00:00:00PASSED/PROVISO
  
 FLOOR DRAINS REQUIRED IN BATHROOMS -
 WITH TRAP PRIMERS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-01-31 Cont ID  
Sent By kstevens Date 2002-01-31 Time 10:29 Rev Time 1.25
Received By kstevens Date 2002-01-29 Time 17:23 Sent To  
Notes
2002-01-31 00:00:00PASSED/PROVISO
  
 FLOOR DRAINS REQUIRED IN BATHROOMS -
 WITH TRAP PRIMERS

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-04 Cont ID  
Sent By kstevens Date 2002-01-04 Time 13:42 Rev Time 0.00
Received By kstevens Date 2002-01-04 Time 13:42 Sent To  
Notes
2002-01-04 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A-1, BUILDING DATA, MINIMUM FAC-
 ILITIES SHALL BE DETERMINED BY SPC-94
 TABLE 407. PLEASE SUBMIT CALCULATIONS
 FOR FACILITIES USING PROPER CODE AND
 TABLE.
  
 2) MORE INFORMATION IS REQUIRED FOR
 STORAGE FACILITIES. PLEASE INDICATE WHAT
 IS BEING STORED, SIZE OF ITEMS BEING
 STORED, AND IF THERE IS ANY HAZARDOUS
 MATERAILS BEING STORED.
  
 3) SHT A-3, ROOMS #120 & 130, FINISH
 SCHEDULE. PER SBC SEC 1204.2 WALLS OF
 ALL PUBLIC RESTROOM SHALL BE NON-ABSOR-
 BANT WATER PROOF MATERIALS.
  
 4) SHT A-3, PLEASE PROVIDE DETAILS FOR
 DRINKING FOUNTAINS SHOWING HEIGHT AND
 CLEAR FLOOR SPACE PER FACBC SEC 4.15
 AND FOR THE URNAL PER FACBC SEC 4.18.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2002-01-31 Cont ID  
Sent By kstevens Date 2002-01-31 Time 10:36 Rev Time 0.25
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-01-03 Cont ID  
Sent By sgraham Date 2002-01-03 Time 11:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-01-03 00:00:00NEED REVISED SITE PLAN & LANDSCAPING
 PLAN SHOWING SCREENING AROUND GAS PUMP