Plan Review Stops For Permit 01120180 |
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2001-12-24 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-12-24 |
Time |
08:15 |
Rev Time |
2.00 |
Received By |
mamini |
Date |
2001-12-24 |
Time |
08:15 |
Sent To |
|
|
Notes |
2001-12-24 00:00:00 | PASSED : | | 1. RESPONSES TO THE PREVIOUS REVIEW | | COMMENTS DATED 12-11-01 SATISFACTORY. | | PLANS REVISED. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2001-12-11 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-12-11 |
Time |
10:39 |
Rev Time |
3.00 |
Received By |
mamini |
Date |
2001-12-11 |
Time |
10:39 |
Sent To |
|
|
Notes |
2001-12-11 00:00:00 | FAILED : | | 1. PLEASE PROVIDE WATER SERVICE FOR RPZ | | AT LIFT STATION. | | 2. PLEASE PROVIDE EASMENT FOR THE | | PROPOSED LIFT STATIONS. | | 3. JACK & BORE, SHEET 2 OF 13 | | A) PLAN SHOWS 8" PVC @ 0.42% | | B) DETAILS SHOWS 18" CASING @ 0.75% | | C) SHEET 4 OF 13(SANITARY SEWER PROFILE) | | SHOWS 8" DIP @ 0.75% (FROM MH4 TO MH5) | | D) PLEASE CLARIFY | | 4. PLEASE REFER TO CITY STANDARD P-12 ON | | SHEET 10 OF 13 FOR CARRIER PIPE SIZE & | | CASING SIZE AND THICKNESS REQUIREMENT. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI. |
|
|
|