Plan Review Details - Permit 01120180
Plan Review Stops For Permit 01120180
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-12-24 Cont ID  
Sent By mamini Date 2001-12-24 Time 08:15 Rev Time 2.00
Received By mamini Date 2001-12-24 Time 08:15 Sent To  
Notes
2001-12-24 00:00:00PASSED :
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS DATED 12-11-01 SATISFACTORY.
 PLANS REVISED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-12-11 Cont ID  
Sent By mamini Date 2001-12-11 Time 10:39 Rev Time 3.00
Received By mamini Date 2001-12-11 Time 10:39 Sent To  
Notes
2001-12-11 00:00:00FAILED :
 1. PLEASE PROVIDE WATER SERVICE FOR RPZ
 AT LIFT STATION.
 2. PLEASE PROVIDE EASMENT FOR THE
 PROPOSED LIFT STATIONS.
 3. JACK & BORE, SHEET 2 OF 13
 A) PLAN SHOWS 8" PVC @ 0.42%
 B) DETAILS SHOWS 18" CASING @ 0.75%
 C) SHEET 4 OF 13(SANITARY SEWER PROFILE)
 SHOWS 8" DIP @ 0.75% (FROM MH4 TO MH5)
 D) PLEASE CLARIFY
 4. PLEASE REFER TO CITY STANDARD P-12 ON
 SHEET 10 OF 13 FOR CARRIER PIPE SIZE &
 CASING SIZE AND THICKNESS REQUIREMENT.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI.