Plan Review Details - Permit 01111251
Plan Review Stops For Permit 01111251
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-01-08 Cont ID  
Sent By mcarsill Date 2002-01-08 Time 15:28 Rev Time 0.00
Received By mcarsill Date 2002-01-08 Time 15:28 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2002-01-08 Cont ID  
Sent By mcarsill Date 2002-01-08 Time 15:29 Rev Time 0.00
Received By mcarsill Date 2002-01-08 Time 15:29 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status F Date 2001-12-06 Cont ID  
Sent By mcarsill Date 2001-12-06 Time 18:11 Rev Time 0.00
Received By mcarsill Date 2001-12-06 Time 18:11 Sent To  
Notes
2001-12-06 00:00:001) WHAT PREVENTS THE HOSE FROM KINKING
 AFTER IT IS CONNECTED TO THE FIRE
 DEPARTMENT CONNECTION SINCE THE RISERS
 WILL BE LOCATED ON THE SIDES OF THE
 BUILDING.
 2) IT WAS NOTED ON THE SPEC BOOKS AND
 ON THE PLANS THAT CENTRAL BRAND FIRE
 SPRINKLER HEADS TYPE LF WILL BE USED.
 LF SPRINKLER HEADS WERE NOTED ON THE
 VOLUNTARY RECALL LIST FROM CENTRAL,
 PLEASE SEE WWW.SPRINKLERREPLACEMENT.COM
 3) PLEASE EXPLAIN WHY THE SPARE
 SPRINKLER HEADS WILL BE STORED IN
 THE CLUBHOUSE AS OPPOSED TO THE
 INDIVIDUAL BUILDINGS.
 4) A 2 1/2 FDC WILL BE REQUIRED.
 5) WHAT PREVENTS THE VALVE FROM
 BEING CLOSED ON THE UNDERGROUND FIRE
 LINE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-01-08 Cont ID  
Sent By mcarsill Date 2002-01-08 Time 15:29 Rev Time 0.00
Received By mcarsill Date 2002-01-08 Time 15:29 Sent To  
Notes
***NONE***