Plan Review Details - Permit 01111133
Plan Review Stops For Permit 01111133
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-11-29 Cont ID  
Sent By mamini Date 2001-11-29 Time 10:16 Rev Time 0.00
Received By mamini Date 2001-11-29 Time 10:24 Sent To  
Notes
2001-11-29 00:00:00PASSED WITH PROVISOS :
 1. ALL WORKS MUST BE DONE PER CITY OF
 WEST PALM BEACH PUBLIC UTILITIES
 ENGINEERING SERVICES DEPARTMENT'S
 STANDARD AND REQUIREMENTS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FS  
Rev No 1 Status P Date 2001-11-29 Cont ID  
Sent By mcarsill Date 2001-11-29 Time 10:01 Rev Time 0.00
Received By mcarsill Date 2001-11-29 Time 10:01 Sent To  
Notes
2001-11-29 00:00:001) THE FIRE DEPARTMENT CONNECTION SHOWN
 ON THE PLANS IS NOT NEEDED AT THIS
 TIME BECAUSE IT APPEARS THAT IT WILL
 SERVE NO PURPOSE UNTIL THE FUTURE.
 2) FIRE LINE TO BE INSTALLED IN
 ACCORDANCE WITH NFPA 24.
 3) FIRE LINE TO BE PRESSURE TESTED
 AT 200 LBS. FOR TWO HOURS.
 4) PLANS NEED TO BE SIGNED AND SEALED
 SINCE A TITLE BLOCK APPEARS ON THE
 PLANS. (ENGINEERING)
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-12-04 Cont ID  
Sent By mamini Date 2001-12-04 Time 14:35 Rev Time 0.00
Received By mamini Date   Time   Sent To  
Notes
***NONE***