Plan Review Stops For Permit 01111092 |
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-12-12 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-12-12 |
Time |
10:03 |
Rev Time |
2.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-12-12 00:00:00 | PLUMBING PLAN REVIEWRESUB | | 1 DEPT OF AGRACULTURE | | 2 WEAVER FOR GREASE TRAP. | | 3 SAMPLE POINT. | | 4 R/R UNDER 20 0/0 RULE VALUE 1,700.00 | | 5 EX B/F. | | PES. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-12-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-12-07 |
Time |
10:34 |
Rev Time |
1.25 |
Received By |
kstevens |
Date |
2001-12-07 |
Time |
10:34 |
Sent To |
|
|
Notes |
2001-12-07 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) PLANS SHALL BE ROUTED TO DEPT. OF | | BUSINESS REGULATION, HOTEL AND RESTURANT | | DIVISION FOR REVIEW BEFORE PLUMBING PLAN | | REVIEW. | | 2) GREASE TRAP NOT ALLOWED INSIDE FOOD | | PREP AREA. PLEASE CONTACT RODNEY COMPO | | FOR SIZE AND LOCATION. WASTE ORD. #2938- | | 96 - PHONE #837-4074. | | 3) SEPARATE GREASE DRAIN LINE TO OUTSIDE | | BLDG REQUIRED. | | 4) EXISTING BATHROOM DOES NOT MEET FACB | | CODE. TOILET ROOM SHALL COMPLY WITH | | FACBC SEC 4.22. PLEASE SHOW DETAILS ON | | PLANS. | | 5) SEPARATE BACKFLOW REQUIRED. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
|