Plan Review Stops For Permit 01111007 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-05-22 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-05-22 |
Time |
16:05 |
Sent To |
|
|
Notes |
2002-05-22 00:00:00 | SEE REVIEW STOP 'R' FOR COMMENTS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-03-25 |
|
|
Cont ID |
|
Sent By |
sjohnson |
Date |
2002-03-25 |
Time |
12:31 |
Rev Time |
0.00 |
Received By |
sjohnson |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-25 00:00:00 | APPROVED PER ROBERT BROWN 3/22/02 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-05-22 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-05-22 |
Time |
16:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2002-03-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-22 |
Time |
06:34 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-22 |
Time |
06:34 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2002-03-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-13 |
Time |
17:17 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-13 |
Time |
17:17 |
Sent To |
M |
|
Notes |
2002-03-13 00:00:00 | ******************* UNSAT ************ | | MODEL "E". | | 1)NOTE: PLEASE NOTE OUTLET SPACING FOR | | KITCHEN COUNTERSPACE. 210-52-C-1 | | | | 2)NOTE: PLEASE NOTE MISSING OUTLET | | SPACING PER 210-52 | | | | 3)NOTE: PLEAS ENOTE THAT POOL PANEL IS | | STILL NOT SHOWN ON PANEL SCHEDULE? | | PLEASWE NOTE THAT RISER SHOWS POOL PANEL | | DISC AND POOL PANEL? PLEASE NOTE THAT | | POOL PANEL DISC IS SHOWN AT THE REAR OF | | HOUSE? AND POOL PANEL IN GARAGE? | | PLEASE CORRELATE LOCATIONS. | | | | 4)NOTE: PLEASE NOTE THAT RISER SHOWS | | POOL PANEL BEING FED WITH TWO "HOTS" | | AND NO NEUTRAL AND NO EQUIPMENT GROUND- | | -ING CONDUCTOR?? SIZE PER 250-122 | | | | 5)NOTE: PLEASE GO OVER LOAD CALCULATIONS | | PLEASE REDO TO MEET ART220. THE 40% | | OF LOAD AFTER FIRST 10KW IS LOWER THAN | | IT SHOULD BE? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-13 |
Time |
18:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-13 |
Time |
18:44 |
Sent To |
|
|
Notes |
2002-02-13 00:00:00 | ***************** UNSAT ************** | | REVIEW FOR MODEL "E" | | PLEASE NOTE THAT NOT ALL ITEMS WERE | | ADDRESSED FROM FIRST REVIEW. | | PLEASE ALSO NOTE THAT OTHER CHANGES | | WERE MADE THAT NEED TO BE ADDRESSED ALSO | | | | | | 1) PLEASE NOTE EITHER MISSING EGRESS | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | PER 210-70 OF THE NEC. | | PLEASE NOTE THAT SOME WERE DONE ON SOME | | OF THE MODELS BUT NOT ALL. | | | | 2) NOTE: PLEASE SHOW ALL OUTLET SPACING | | TO MEET 2`,6`,12` RULE PER 210-52. | | PLEASE NOTE SOME WERE DONE AND OTHERS?? | | MISSING IN MANY LOCATIONS | | 3)NOTE: PLEASE NOTE RECEPT IN GARAGE | | NEEDS TO BE SHOWN AS GFI PER 210-8 | | | | 4)NOTE: PLEASE CLARFIY OUTLET SHOWN | | UNDER WATER CLOSET? | | | | 5)NOTE: PLEASE NOTE THAT OUTLET SPACING | | IN KITCHEN CHANGED?? SOME OUTLETS SHOWN | | AS DOUBLE INSTEAD? DID ADDRESS COMMENT | | FOR BEING GFI. | | | | 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | GOING TO BUILDING STEEL AND COLD WATER | | PER 250-50. | | FOOTER STEEL. | | | | 7)NOTE: PLEASE NOTE, DERATING FOR AHU | | LOAD IS DOEN TWICE? | | PLEASE NOTE THAT LOAD CALCUALTIONS DO | | NOT MEET NEC 220. | | | | 8) NOTE: SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | PER NFPA-72 2-2.1.1.1. | | NOTE SD`S NOT TO BE WITHIN 3' OF BATHS | | AND KITCHENS. NFPA-72 2-5.2.1.6 | | | | 9)NOTE: PLEASE NOTE THAT RISER NOW SHOWS | | AN EQUIPMENT GROUNDING CONDUCTOR BETWEEN | | METER AND MAIN DISC. THIS IS PARALLELING | | THE NEUTRAL? | | | | 10)NOTE: PLEASE NOTE THAT 30A POOL PANEL | | IS SHOWING 3/0`S FEEDING? PLEASE CLARIFY | | AND SHOW OCP ON PANEL SCHEDULE WITH | | CONDUCTOR SIZE.SHOW POOL PANEL LOCATION. | | | | 11)NOTE: PLEASE NOTE THAT NOTES ON | | RIGHT STILL REFERENCE WRONG NEC FOR | | WHATS LISTED. KITCHEN NOT HAS BATH ART? | | PLEASE CORRELATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | | | ***NOTE** | | ONLY ONE SET OF "E" PLANS WERE SUBMITTED | | PLEASE SUBMIT TWO FOR PERMITTING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-12-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-20 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-12-20 |
Time |
12:32 |
Sent To |
|
|
Notes |
2001-12-20 00:00:00 | ****************** UNSAT *************** | | | | | | PLEASE SEE NOTES ATTACHED TO PERMIT `#S | | 01111002 AND 01111006. | | PLEASE NOTE THE SAME NOTES FOR ALL. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-03-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-03-14 |
Time |
12:37 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2002-03-14 |
Time |
12:37 |
Sent To |
|
|
Notes |
2002-03-14 00:00:00 | | | MECHANICAL PERMIT 01111078 | | | | APPROVED 12-11-01 BY H. MOSER |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-12-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-13 |
Time |
17:30 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2001-12-11 |
Time |
18:32 |
Sent To |
|
|
Notes |
2001-12-11 00:00:00 | IF GAS DRYERS ARE USED REFER TO SECTION | | 704 COMBUSTION AIR | | STANDARD MECHANICAL CODE 1997 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2002-03-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-03-22 |
Time |
11:25 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-03-22 |
Time |
11:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2002-03-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-22 |
Time |
06:34 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-03-12 |
Time |
18:37 |
Sent To |
|
|
Notes |
2002-03-12 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) FROM PREVIOUS REVIEW - BATH #3 LAV | | NOT VENTED. | | 2) BATH #3 HORIZONTAL DRY VENT NOT APP- | | ROVED. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-02-13 |
Time |
19:27 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2002-02-13 |
Time |
19:27 |
Sent To |
|
|
Notes |
2002-02-13 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) MODEL "E" - 2 SETS OF PLANS REQUIRED | | FOR PLAN REVIEW. ONLY ONE SUBMITTED. | | 2) SHT A-02 BATH #2 NOT VENTED AND HORIZ | | ONTAL DRY VENT NOT ALLOWED, SEC 906.2.1 | | SEE COMMENT #1 PREVIOUS REVIEW. | | 3) SHT A-02 BATH #2 VENT PIPE SHALL RISE | | VERTICALLY OR AT AN ANGLE NOT EXCEEDING | | 45 DEG. FROM VERTICAL TO A POINT AT | | LEAST 6" ABOVE THE FLOOD RIM LEVEL. SEC | | 906.2.1 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-12-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-12-07 |
Time |
19:30 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-12-07 |
Time |
19:30 |
Sent To |
|
|
Notes |
2001-12-07 00:00:00 | DENIED | | REFERENCE: SPC-94-SBC-97 | | | | 1) BATH #3 DRY HORIZONTAL VENT NOT | | ALLOWED PER SPC SEC 906.2.1 | | 2) 3" VENT NOT ALLOWED TO PASS THRU | | BLOCK WALL AND TIE BEAM PER SBC SEC | | 1907.3.5 | | 3) MASTER BATH VENT SEE COMMENT #2. | | 4) DISHWASHER TO DRAIN INTO GARBAGE DISP | | OR KITCHEN SINK TAILPIECE. | | 5) BATH #2 TUB NOT VENTED PROPERLY PER | | SPC SEC 913.2 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
5 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-05-22 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-05-22 |
Time |
16:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
4 |
Status |
P |
Date |
2002-03-22 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-03-22 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-03-22 |
Time |
15:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
F |
Date |
2002-03-13 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-03-13 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-03-13 |
Time |
15:18 |
Sent To |
|
|
Notes |
2002-03-13 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | 1) SEE REVIEW, DATED 3/13/02, OF MODEL B | | (PERMIT NO. 01111002) FOR GENERAL | | COMMENTS. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2002-02-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-02-15 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-02-15 |
Time |
11:03 |
Sent To |
|
|
Notes |
2002-02-15 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | ARE NUMBERED AS PER THE BUILDING PLAN | | REVIEW OF 1/15/02: | | | | 1) SEE REVIEWS, DATED 2/14/02 & 2/15/02, | | OF MODELS B AND C (PERMIT NOS 01111002 | | AND 01111005) FOR GENERAL COMMENTS. | | COMMENTS SPECIFIC TO MODEL E ARE LISTED | | BELOW. | | | | 2) THIS COMMENT HAS NOT BEEN PROPERLY | | ADDRESSED.THE DOOR TYPE ELEVATION 'E' | | (SHEET A-03) DOES NOT CORRESPOND TO THE | | DOOR SHOWN ON THE REAR ELEVATION | | (SHEET A-07). | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2002-01-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-01-15 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-01-15 |
Time |
10:01 |
Sent To |
|
|
Notes |
2002-01-15 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | 1) SEE REVIEWS, DATED 1/15/02, OF | | MODELS B AND C (PERMIT NOS 01111002 AND | | 01111005) FOR GENERAL COMMENTS. COMMENTS | | SPECIFIC TO MODEL E ARE LISTED BELOW. | | | | 2) SHEET A-03, FLOOR PLAN.THE | | BATH/BED 2 EXTERIOR DOOR TO THE PATIO IS | | GIVEN A DOOR TYPE REFERENCE D, FOR WHICH | | THE DOOR TYPE ELEVATION DOES NOT | | CORRELATE TO THAT SHOWN ON THE REAR | | ELEVATION (SHEET A-07). | | | | 3) SHEET A-05, ROOF PLAN.THE BEAM OVER | | THE SLIDING GLASS DOOR LEADING TO THE | | PATIO FROM THE MASTER BEDROOM HAS NO | | BEAM REFERENCE MARK SHOWN. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-01-03 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-01-03 |
Time |
09:12 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|