Plan Review Stops For Permit 01111005 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-03-25 |
|
|
Cont ID |
|
Sent By |
sjohnson |
Date |
2002-03-25 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
sjohnson |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-25 00:00:00 | APPROVED PER ROBERT BROWN 3/22/02 | | APPROVED PER ROBERT BROWN 3/22/02 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2002-03-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-22 |
Time |
06:33 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-22 |
Time |
06:33 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2002-03-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-13 |
Time |
17:55 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-13 |
Time |
17:55 |
Sent To |
M |
|
Notes |
2002-03-13 00:00:00 | ************** UNSAT ***************** | | MODEL "C". | | 1) NOTE: PLEASE NOTE THAT OUTLET SPACING | | NEEDS TO MEET 210-52. 2` AND 6` RULE. | | | | 2)NOTE: PLEASE NOTE LOAD CALCULATIONS | | NEED TO BE GONE OVER. PLEASE NOTE THAT | | AFTER THE FIRST 10KW WASA TAKEN, 40% | | OF REMAINING, SEEMS TO HAVE COME OUT | | TOO LOW. | | PLEASE ADJUST. | | | | 3)NOTE: PLEASE NOTE POOL PANEL IS STILL | | NOT LISTED ON MAIN PANEL SCHEDULE?? | | PLEASE NOTE THAT RISER SHOWS A POOL | | PANEL DISC AND POOL PANEL? | | PLEASE ALSO NOTE THAT POOL PANEL IS IN | | GARAGE AND POOL PANEL DISC IS SHOWN AT | | THE REAR OF HOUSE?? PLEASE CORRELATE. | | | | 4)NOTE: PLEASE NOTE FEED TO POOL PANEL | | SHOWING TWO "HOTS"? NO NEUTRAL, NO | | EQUIPMENT GROUNDING CONDUCTOR?? | | PLEASE CORRECT. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS. | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-13 |
Time |
19:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-13 |
Time |
19:02 |
Sent To |
|
|
Notes |
2002-02-13 00:00:00 | ****************** UNSAT *************** | | | | REVIEW FOR MODEL "C" | | | | PLEASE NOTE THAT NOT ALL NOTES FROM | | FIRST REVIEW WERE ADDRESSED. | | PLEASE NOTE THAT OTHER CHANGES WERE | | MADE THAT NOW NEED TO BE ADDRESSED. | | | | 1) NOTE: SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | PER NFPA-72 2-2.1.1.1. | | MISSING FIRST FLOOR. | | | | 2) NOTE: PLEASE SHOW ALL OUTLET SPACING | | TO MEET 2`,6`,12` RULE PER 210-52. | | MISSING IN SOME LOCATIONS. | | | | 3)NOTE: PLEASE NOTE MISSING REQ`D EGRESS | | LIGHTING AT MANY LOCATIONS. PER 210-70 | | | | 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | GOING TO BUILDING STEEL AND COLD WATER | | PER 250-50. | | FOOTER STEEL. | | | | 5) PLEASE NOTE MISSING OUTLET FOR A/C | | EQUIPMENT PER 210-63 OF NEC AND 309.2 | | MECHANICAL CODE. | | | | 6)NOTE: PLEASE NOTE THAT OUTLET SPACING | | ALONG KITCHEN COUNTERSPACES SEEM TO | | HAVE CHANGED WHEN "GFI" WAS ADDED? | | PLEASE CLARFIY "TWO" OUTLETS SHOWN | | TOGETHER. SHOWN ON OTHER MODELS LIKE | | THIS. 210-52-C1 | | | | 7)NOTE: PLEASE NOTE THAT NOTES ON RIGHT | | STILL REFERENCE ART FOR BATHS WHEN NOTED | | FOR KITCHEN? PLEASE CORRELATE. 210-11-C- | | 1. NOTED AS 210-52D"BATHS". | | | | 8)NOTE: PLEASE NOTE THAT DERATING FOR | | AHU WAS TAKEN TWICE AT 65%?? PLEASE | | CORRECT. 220 | | | | 9)NOTE: PLEASE NOTE LOAD CALCULATIONS | | NEED TO MEET 220. PLEASE NOTE THAT LOAD | | IS SHOWN AS BEING DIVIDED BY 120V ON | | A 230/240V SERVICE? PLEASE CLARIFY. | | | | 10)NOTE: PLEASE NOTE RISER DIAGRAM WAS | | REVISED AND NOW SHOWS AN EQUIPMENT | | GROUNDING CONDUCTOR BETWEEN METER AND | | MAIN DISCONNECT? PLEASE NOTE THAT THIS | | IS PARALLELING THE NEUTRAL? | | | | 11)NOTE: PLEASE NOTE MISSING HALL OUTLET | | UPSTAIRS PER 210-52H | | | | 12)NOTE: PLEASE NOTE THAT RISER SHOWS | | 3/0`S GOING TO A 30A POOL PANEL? PLEASE | | SHOW PANEL ON PLANS AND SHOW OCP AND | | CONDUCTOR SIZE FOR POOL PANEL ON MAIN | | PANEL SCHEDULE. | | | | 13)NOTE: PLEASE NOTE MISSING REQ`D BATH | | GFI FOR POWDER ROOM FIRST FLLOR.210-52D | | | | 14)NOTE: PLEASE NOTE THAT NO OUTLET IS | | SHOWING FOR RANGE. ALSO NOT SHOWN ON | | OTHER PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-12-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-20 |
Time |
12:30 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-12-20 |
Time |
12:30 |
Sent To |
|
|
Notes |
2001-12-20 00:00:00 | ****************** UNSAT ********** | | | | PLEASE SEE NOTE ATTACHED TO PERMIT #`S | | 01111002 AND 01111006. | | PLEASE NOTE THAT SAME NOTES FOR | | ALL E-SHEETS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONSD, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW. | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-03-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-03-14 |
Time |
11:02 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2002-03-14 |
Time |
10:57 |
Sent To |
|
|
Notes |
2002-03-14 00:00:00 | | | MECHANICAL PERMIT 01111065 | | | | APPROVED PER HAROLD MOSER 12-11-01 | | NO CHANGES WITH THIS SUBMITTAL. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-12-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-13 |
Time |
18:06 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2001-12-11 |
Time |
18:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2002-03-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-03-22 |
Time |
11:22 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-03-22 |
Time |
11:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2002-03-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-22 |
Time |
06:33 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-03-12 |
Time |
18:25 |
Sent To |
|
|
Notes |
2002-03-12 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) FROM PREVIOUS REVIEW - FLOOR PLAN AND | | RISER DIAGRAM DO NOT MATCH. WASH MACHINE | | HAS NO VENT ON FLOOR PLAN.. | | 2) FROM PREVIOUS REVIEW - RUNNING TRAP | | AT MASTER BATH TUB IS NOT APPROVED AS | | SHOWN ON RISER DIAGRAM. | | 3) FROM PREVIOUS REVIEW - LAVS AT BATH | | #2 AND MASTER BATH ARE "S" TRAPPED ON | | RISER DIAGRAM. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-02-13 |
Time |
18:21 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-02-13 |
Time |
18:21 |
Sent To |
|
|
Notes |
2002-02-13 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) SHT A-02 RISER DIAGRAM DOES NOT RE- | | FLECT FLOOR PLAN. W/M ON FLOOR PLAN IS | | AFTER RISER FOR 2ND FLOOR AND NO VENT IS | | SHOWN ON FLOOR PLAN. RISER DIAGRAM SHOWS | | W/M BEFORE RISER FOR 2ND FLOOR AND RE- | | VENT BELOW FLOOR LEVEL NOT ALLOWED. SEC | | 906.3 SEE COMMENTS 3'S ONE AND TWO FROM | | PREVIOUS REVIEW. | | 2) SHT A-02 FLOOR PLAN DOES NOT SHOW | | SEPARATE STACK FOR M/BATH AS SHOWN ON | | RISER. SEE COMMENT #7 FROM PREVIOUS RE- | | VIEW. | | 3) SHT A-02 FLOOR PLAN SHOWS 2" VTR FOR | | POWDER ROOM & 3" VTR ON RISER DIAGRAM. | | PLEASE CLAIRFY. | | 4) SHT A-02 RUNNING TRAP AT M/BATH TUB | | NOT APPROVED AS SHOWN ON RISER DIAGRAM. | | SEE COMMENT #8 FROM PREVIOUS REVIEW. | | 5) SHT A-02 LAVS IN M/BATH AND BATH #2 | | ARE "S" TRAPPED ON RISER DIAGRAM. THESE | | TRAPS ARE NOT APPROVED. SEC 1001.5.2 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-12-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-12-07 |
Time |
18:38 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-12-07 |
Time |
18:38 |
Sent To |
|
|
Notes |
2001-12-07 00:00:00 | DENIED | | REFERENCE: SPC-94-SBC-97 | | | | 1) SANITARY RISER DIAGRAM DOES NOT MATCH | | FLOOR PLAN. STACK FOR BATH #2 UPSTAIRS | | SHOULD BE TAKEN OFF BEFORE W/MACHINE. | | 2) W/MACHINE NOT VENTED ON RISER DIAG. | | 3) LAV IN POWDER ROOM NOT VENTED ON DIAG | | 4) 3" STACK NOT ALLOWED IN BLOCK WALL & | | CAN NOT PASS THRU TIE BEAM. SBC-97 SEC | | 1907.3.5 | | 5) TUB NOT VENTED IN BATH #2, SPC SEC | | 913.2 | | 6) DISH WASHER DRAIN SHALL GO TO GARBAGE | | DISPOSAL OR TAILPIECE ON KITCHEN SINK. | | 7) DISCHARGE FROM MASTER BATH SHALL NOT | | DRAIN INTO VENT STACK FOR KITCHEN SINK. | | SPC SEC 913.2 & 910.2. SEPARATE VENT RE- | | QUIRED FOR KITCHEN SINK. | | 8) RUNNING TRAPS IN MASTER BATH TUB NOT | | ALLOWED. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
4 |
Status |
P |
Date |
2002-03-22 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-03-22 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-03-22 |
Time |
15:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
F |
Date |
2002-03-13 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-03-13 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-03-13 |
Time |
15:12 |
Sent To |
|
|
Notes |
2002-03-13 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | 1) SEE REVIEW, DATED 3/13/02, OF MODEL B | | (PERMIT NO. 01111002) FOR GENERAL | | COMMENTS. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2002-02-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-02-15 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-02-15 |
Time |
10:12 |
Sent To |
|
|
Notes |
2002-02-15 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | ARE NUMBERED AS PER THE BUILDING PLAN | | REVIEW OF 1/15/02: | | | | 1) SEE REVIEW, DATED 2/14/02, OF MODEL B | | (PERMIT NO. 01111002) FOR GENERAL | | COMMENTS.COMMENTS SPECIFIC TO MODEL C | | ARE LISTED BELOW. | | | | 4) THIS COMMENT HAS NOT BEEN ADDRESSED. | | PART OF THE SECOND FLOOR BED 3 EXTERIOR | | WALL FACES THE COMMON PROPERTY LINE AT A | | DISTANCE OF 6'-8".FROM TABLE 600, THAT | | PART OF THE WALL IS REQUIRED TO HAVE A | | FIRE RESISTANCE RATING OF ONE HOUR. | | SUBMIT DETAILS TO SHOW THE RATING OF | | THIS WALL. | | | | 5) THIS COMMENT HAS NOT BEEN PROPERLY | | ADDRESSED.THE MODEL D DOOR SCHEDULE IS | | STILL MISSING ALL REFERENCE MARKS ABOVE | | NO. 14 | | | | 6) THIS COMMENT HAS NOT BEEN PROPERLY | | ADDRESSED.SHEET A-07 REFERS TO BEAM | | REF. 8F801B BUT THIS REF. DOES NOT MATCH | | THAT SHOWN ON BEAM SCHEDULE (SHEET A-06) | | AMEND THE BEAM REFERENCE TO SUIT THAT | | GIVEN ON THE SCHEDULE. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2002-01-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-01-15 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-01-15 |
Time |
08:51 |
Sent To |
|
|
Notes |
2002-01-15 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | SBC = STANDARD BUILDING CODE | | SBC*= STANDARD BUILD'G CODE (AMENDMENTS) | | | | 1) SEE REVIEW, DATED 1/15/02, OF MODEL B | | (PERMIT NO. 01111002) FOR GENERAL | | COMMENTS.COMMENTS SPECIFIC TO MODEL C | | ARE LISTED BELOW. | | | | 2) THE PAD FOOTINGS UNDER GARAGE WALL | | COLUMNS AND THE PATIO COLUMN SHALL NOT | | ENCROACH ON THE COMMON PROPERTY (ZERO | | LOT) LINE. | | | | 3) SHEET A-02, FOUNDATION PLAN.THE | | FOOTING SCHEDULE IS BLANK. ADD DETAILS. | | | | 4) SBC 705.1.3OPENING PROTECTIVES. | | TABLE 600 REQUIRES THE SECOND FLOOR | | BED 3 EXTERIOR WALL FACING TH COMMON | | PROPERTY LINE TO HAVE A MINIMUM FIRE | | RESISTANCE RATING OF ONE HOUR.SUBMIT | | DETAILS TO SHOW THE RATING OF THIS WALL. | | | | 5) MODELS C, D AND E.THE DOOR SCHEDULE | | IS MISSING ALL REFERENCE MARKS ABOVE | | NO. 14.AMEND SCHEDULES. | | | | 6) SHEET A-06, BEAM SCEDULE,DOES NOT | | GIVE DETAILS FOR THE BEAMS, REF 8F01B ON | | SHEET A-07, TO THE STAIRCASE WINDOW AND | | MASTER BEDROOM WALK-IN CLOSET WINDOW. | | REVISE SCHEDULE TO SHOW BEAM TYPE & SIZE | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-01-03 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-01-03 |
Time |
08:45 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|