Plan Review Details - Permit 01111002
Plan Review Stops For Permit 01111002
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-25 Cont ID  
Sent By sjohnson Date 2002-03-25 Time 12:23 Rev Time 0.00
Received By sjohnson Date   Time   Sent To  
Notes
2002-03-25 00:00:00APPROVED PER ROBERT BROWN 3/22/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-14 Cont ID  
Sent By rbrown Date 2002-02-14 Time 19:31 Rev Time 0.00
Received By rbrown Date 2002-02-14 Time 19:30 Sent To  
Notes
2002-02-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 **NOTE**
 THE PERMIT APPLICATIONS FOR MODELS B, C,
 D AND E WERE MADE PRIOR TO JANUARY 1,
 2002 AND MUST, THEREFOR, BE REVIEWED FOR
 COMPLIANCE WITH STANDARD BUILDING CODE
 1997.ANY PERMIT, OR PLAN REVIEW,
 APPLICATION MADE AFTER MARCH 1, 2002
 MUST BE REVIEWED FOR COMPLIANCE WITH
 FLORIDA BUILDING CODE 2001. APPLICATIONS
 MADE BETWEEN THESE TWO DATES MAY BE
 REVIEWED FOR COMPLIANCE WITH EITHER ONE
 OF THE TWO CODES.
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/15/02:
  
 1) THE ORIGINAL PERMIT APPLICATIONS HAVE
 ADDRESSES AND LOT NUMBERS.THEY CANNOT
 BE TREATED AS "MASTERS" AS PROPOSED.A
 RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THESE ARE NOT MASTERS, SEE (1) ABOVE.
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, PLANS STAMPED BY THEM AND A COPY
 OF THE RECEIPT SUBMITTED TO CITY OF WEST
 PALM BEACH BUILDING DEPARTMENT, BEFORE
 A BUILDING PERMIT CAN BE ISSUED.
  
 4) THESE ARE NOT MASTERS, SEE (1) ABOVE.
 SUBMIT A SOIL TEST REPORT.
  
 5) THIS COMMENT HAS NOT BEEN ADDRESSED.
  
 9) THIS COMMENT HAS BEEN ADDRESSED ONLY
 IN RESPECT OF MODEL B.AS STATED
 PREVIOUSLY THE COMMENT ALSO APPLIES TO
 MODEL D.
  
 11) THIS COMMENT BEEN PROPERLY ADDRESSED
 ONLY IN RESPECT OF MODEL D.CORRECT THE
 MODEL B REFERENCES CONCERNED, INCLUDING,
 BUT NOT LIMITED TO, BEDROOM 3 WINDOW,
 MASTER BATH WINDOW, MASTER BED SIDE
 WINDOW AND FAMILY ROOM WINDOW AND PATIO
 DOORS.
  
 12) PRODUCT APPROVALS.THE SUBMITTED
 WINDOW AND DOOR PRODUCT APPROVALS VARY
 AS TO WHETHER HURRICANE SHUTTERS ARE
 REQUIRED.PRODUCT APPROVAL 00-0512.04
 SERIES 4230 ALUMINUM FIXED WINDOW'
 REQUIRES THE USE OF SHUTTERS.ANNOTATE
 THE PLANS TO DENOTE WHICH EXTERIOR
 OPENINGS ARE TO BE PROVIDED WITH
 HURRICANE SHUTTERS.
  
 17) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE MODEL B ARCHITECTURAL
 ROOF FRAMING PLAN STILL DOES NOT REFLECT
 THE ROOF PROFILE ON THE ELEVATION AND ON
 THE ROOF TRUSS SHOP DRAWING.
  
 18) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE HANGER REFERENCE USP NFM
 STATED ON THE TRUSS ANCHOR SCHEDULES IS
 INCOMPLETE.SPECIFY THE FULL REFERENCE.
  
 20) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE COMMENT REFERS TO VENTILATION OF
 ATTIC SPACE NOT HABITABLE ROOMS.
  
 22) THIS COMMENT HAS NOT BEEN ADDRESSED.
  
 23) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE MODEL C INTERNAL DOOR TO
 THE GARAGE IS STILL SHOWN, ON THE DDOR
 SCHEDULE, AS TYPE F WHICH IS A DOUBLE
 DOOR AND DOES NOT CORRELATE TO THE PLAN.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-03-22 Cont ID  
Sent By dpalmer Date 2002-03-22 Time 06:32 Rev Time 0.00
Received By dpalmer Date 2002-03-22 Time 06:18 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-03-13 Cont ID  
Sent By pkrauss Date 2002-03-21 Time 15:08 Rev Time 0.00
Received By dpalmer Date 2002-03-13 Time 18:17 Sent To M
Notes
2002-03-13 00:00:00************** UNSAT *****************
  
 MODEL "B"
  
 1) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 STILL MISSING FROM ATRIUM TO OUTSIDE.??
  
 2)NOTE: PLEASE NOTE THAT A POOL DISC
 AND POOL PANEL ARE BOTH SHOWN ON THE
 RISER DIAGRAM? PLEASE NOTE THAT POOL
 PANEL IS STILL NOT SHOWN ON POOL PANEL.,
 POOL PANEL IS BEING SHOWN IN GARAGE AND
 THE POOL PANEL DISC IS SHOWN AT THE
 REAR OF HOUSE?? PLEASE CORRELATE
 LOCATIONS.
  
 3)NOTE: PLEASE NOTE THAT POOL PANEL IS
 BEING FED WITHTWO "HOTS"? PLEASE
 CLARIFY WHERE NEUTRAL AND EQUIPMENT
 GROUNDING CONDUCTOR,
  
 4)NOTE: PLEASE NOTE THAT LOAD CALCULATIO
 NS NEED TO BE GONE OVER AND DONE PER
 NEC(220),
 PLEASE NOTE, 40% DERATING SEEMS TO BE
 TOO LOW. PLEASE RECONFIGURE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-02-13 Cont ID  
Sent By dpalmer Date 2002-02-13 Time 19:33 Rev Time 0.00
Received By dpalmer Date 2002-02-13 Time 19:33 Sent To  
Notes
2002-02-13 00:00:00*************** UNSAT ****************
  
 REVIEW FOR MODEL "B"
  
 PLEASE NOTE THAT SOME NOTES WERE ADDRESS
 -ED AND OTHER NOT. PLEASE NOTE OTHER
 CHANGES WERE MADE AND NOW HAVE COMMENTS
 TO BE ADDRESSED.
  
 1)NOTE: PLEASE NOTE THAT SOME REQ`D
 EGRESS LIGHTING WAS STILL NOT ADDRESSED.
 210-70 SOME SHOWN AS OPT?? MISSING OTHER
 -S
 2) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING IN SOME LOCATIONS.
  
 3)NOTE: PLEASE NOTE GARAGE OUTLET NEEDS
 TO BE SHOWN AS GFI. PER 210-8
  
 4)NOTE: PLEASE NOTE MISSINGLT FOR
 ATTIC ACCESSIN BEDROOM CLOSET. 210-70
  
 5)NOTE: PLEASE NOTE, LOAD CALCUALTIONS
 NEED TO BE SHOWN PER 220. PLEASE NOTE
 DERATING OF AHU TWICE? AT 65%
 PLEASE NOTE TOTAL KW DIVIDED BY 120V
 ON A 230/240V SERVICE?
  
 6)NOTE: PLEASE NOTE THAT RISER SHOWS
 3/0`S TO 30A POOL PANEL? PLEASE SHOW
 OCP AND CONDUCTOR SIZES ON PANEL SCHED-
 -ULE. PLEASE ALSO SHOW POOL PANEL ON
 PLANS.
  
 7)NOTE: PLEASE NOTE RISER NOW SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR FROM METER
 TO MAIN DISC? PLEASE NOTE THAT THIS IS
 PARALLELING THE NEUTRAL.
  
 8) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50./FOOTER STEEL.
  
 9)NOTE: PLEASE NOTE PLANS STILL SHOW
 NOTE ON RIGHT THAT REFERENCES WRONG NEC
 ART FOR KITCHEN? PLEASE SEE 210-11-C-1
 NOT 210-52D(BATHS)
  
 10)NOTE: PLEASE NOTE MISSING HALLWAY
 OUTLET PER 210-52H
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-20 Cont ID  
Sent By dpalmer Date 2001-12-20 Time 10:42 Rev Time 0.00
Received By dpalmer Date 2001-12-20 Time 10:42 Sent To  
Notes
2001-12-20 00:00:00************* UNSAT ********************
  
 1)NOTE: PLEASE NOTE THAT SEPARATE PLANS
 NEED TO BE SUBMITTED FOR EACH SFH.
  
 2)NOTE: PLEASE NOTE LOAD SHOWN FOR MAIN
 PANEL ABOVE 200AMPS. MISPRINT FROM
 LOAD CALCAULTIONS.
  
 3)NOTE: PLEASE NOTE OCP FOR WATER HEATER
 AT 125% PER 422-13. CORRELATE OCP W/
 WIRE SIZE.
  
 4)NOTE: PLEASE NOTE MISSING EGRESS LIGHT
 -ING IN MANY LOCATIONS, PLEASE ALSO NOTE
 SOME AREAS(KITCHEN) SHOW LTS AS OPTS.
 WHEN REQ`D BY 210-70. OUTSIDE, HALL,
 ETC.
  
 5)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C COND UNIT PER 309.2 OF THE MECH CODE
  
  
 6)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW MAIN DISC NEXT TO METERCAN AS SHOWN
 ON RISER DIAGRAM.
  
 7) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 PLEASE NOTE THAT NOTES NEED TO NOTE
 CORRECT ART. NOTED AS 210-52D AND THAT
 ART IS FOR BATHS.
  
 8) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 PLEASE NOTE PLAN NOTES MENTION 210-52-D
 SHOULD ALSO READ 210-11-C-3. AS LONG
 AS CIRCUIT(S) IS SHOWN ON PANEL SCHEDULE
 THEN NOT NESS TO PLACE IN NOTES.
  
 9)NOTE: PLEASE CLARIFY MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN PANEL
 AND POOL PANEL./250-122
  
 10)NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING IN MANY LOCATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-03-21 Cont ID  
Sent By pkrauss Date 2002-03-14 Time 10:30 Rev Time 0.45
Received By pkrauss Date 2002-03-14 Time 10:30 Sent To E
Notes
2002-03-14 00:00:00 
 MECHANICAL PERMIT 01111083
  
 PLANS APPROVED 12-11-01 BY H. MOSER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-12-11 Cont ID  
Sent By dpalmer Date 2002-03-13 Time 18:17 Rev Time 0.33
Received By hmoser Date 2001-12-11 Time 18:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-03-22 Cont ID  
Sent By kstevens Date 2002-03-22 Time 11:25 Rev Time 1.00
Received By kstevens Date 2002-03-22 Time 11:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-03-12 Cont ID  
Sent By dpalmer Date 2002-03-22 Time 06:32 Rev Time 0.50
Received By kstevens Date 2002-03-12 Time 18:16 Sent To  
Notes
2002-03-12 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) FROM PREVIOUS REVIEW - FLOOR PLAN AND
 RISER DIAGRAM DO NOT MATCH. TUB VENTED
 ON RISER BUT NOT ON FLOOR PLAN.
 2) FROM PREVIOUS REVIEW - LAUNDRY SINK
 NOT VENTED.
 3) FROM PREVIOUS REVIEW - KITCHEN SINK,
 FLOOR PLAN AND RISER NOT SAME.
 4) FROM PREVIOUS REVIEW - MASTER BATH
 FLOOR PLAN AND RISER NOT THE SAME, AND
 HORIZONTAL DRY VENT NOT ALLOWED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-02-13 Cont ID  
Sent By kstevens Date 2002-02-13 Time 17:16 Rev Time 1.00
Received By kstevens Date 2002-02-14 Time 08:32 Sent To  
Notes
2002-02-13 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT A-02 PLUMBING RISER DIAGRAM DOES
 NOT MATCH FLOOR PLAN. BATH #2 SHOWS VTR
 ON FLOOR PLAN BUT NOT ON RISER.
 2) SHT A-02 RISER DIA. TUB BATH #2 NOT
 VENTED
 3) SHT A-02 LAVS IN M/BATH "S" TRAPPED,
 SED 1001.5.2
 4) SHT A-02 TUB NOT VENTED ON FLOOR PLAN
 AND SHOWS A HORIZONTAL DRY VENT ON RISER
 SPC SEC 906.2.1.
 5) SHT A-02 RISER DIAGRAM, LAUNDRY SINK
 NOT VENTED AND W/M SHOWS TRAP UNDER-
 GROUND. IS W/M TRAP GOING TO BE U/G?
 6) SHT A-02 DISHWASHER NOT TRAPPED ON
 RISER. D/W SHOULD DRAIN TO GARBAGE DISP.
 OR TAILPIECE AT KITCHEN SINK.
 7) SHT A-02 RISER DIA. TRAPS FOR KITCHEN
 SINK ARE UNDERGROUND. PLEASE SHOW TRAPS
 ON STACK ABOVE GROUND.
 8) SHT A-02 MASTER BATH HORIZONTAL DRY
 VENT NOT ALLOWED. SEC 906.2.1. 3" DOUBLE
 LAV NOT VENTED PROPERLY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-12-07 Cont ID  
Sent By kstevens Date 2001-12-07 Time 18:23 Rev Time 0.50
Received By kstevens Date 2001-12-07 Time 18:23 Sent To  
Notes
2001-12-07 00:00:00DENIED
 REFERENCE: SPC-94-SBC-97
  
 1) SHOWER NOT VENTED PROPERLY IN BATH 2.
 SPC SEC 913.2
  
 2) 3" VENT FOR MASTER BATH IS A DRY VENT
 WHICH IS NOT ALLOWED PER SPC SEC 906.2.1
  
 3) 3" VENT IS NOT ALLOWED TO PASS THRU
 A TIE BEAM AND SHALL NO BE ALLOWED TO
 BE IN BLOCK WALL PER SBC-97 SEC 1907.3.5
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2002-03-22 Cont ID  
Sent By rbrown Date 2002-03-22 Time 15:18 Rev Time 0.00
Received By rbrown Date 2002-03-22 Time 15:18 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2002-03-13 Cont ID  
Sent By rbrown Date 2002-03-13 Time 14:38 Rev Time 0.00
Received By rbrown Date 2002-03-13 Time 14:38 Sent To  
Notes
2002-03-13 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 **NOTE**
 THE COMMENTS BELOW ARE GENERAL COMMENTS
 WHICH APPLY TO MODELS B, C, D AND E
 EXCEPT AS NOTED.
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEWS OF 1/15/02 AND 2/14/02:
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) SOIL REPORT.THE 'FOUNDATION DESIGN'
 SECTION OF THE SUBMITTED SOIL REPORT
 STATES THAT "...CONTINUOUS FOOTINGS
 SHALL BE AT LEAST 18 INCHES WIDE".THE
 FOUNDATION PLANS AND FOOTING SCHEDULES
 SHOW 16 INCH WIDE FOOTINGS.AMEND THE
 PLANS TO SHOW 18 INCH WIDE FOOTINGS, OR
 JUSTIFY THIS DEVIATION FROM THE
 RECOMMENDATIONS OF THE SOIL REPORT.
  
 5) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THERE ARE STILL TWO DIFFERENT DRAWING
 SHEETS THAT ARE BOTH NUMBERED A10 AND
 TITLED 'GENERAL DETAILS' EVENTHOUGH THEY
 CONTAIN DIFFERENT DETAILS.AMEND THE
 SHEET NUMBERS/TITLES TO DIFFERENTIATE
 BETWEEN DRAWING SHEETS.
  
 12) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED IN RESPECT OF MODELS C OR E.
 ANNOTATE THE PLANS TO SHOW THE INTENTION
 FOR ALL OPENINGS, EXCEPT THE FRONT DOOR,
 TO BE PROVIDED WITH HURRICANE SHUTTERS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-02-15 Cont ID  
Sent By rbrown Date 2002-02-15 Time 10:09 Rev Time 0.00
Received By rbrown Date 2002-02-15 Time 10:09 Sent To  
Notes
2002-02-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FOR COMMENTS, REFER TO REVIEW STOP 'B'
 DATED 2/14/02.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-01-15 Cont ID  
Sent By rbrown Date 2002-01-15 Time 08:46 Rev Time 0.00
Received By rbrown Date 2002-01-15 Time 08:46 Sent To  
Notes
2002-01-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 **NOTE**
 MODELS B,C,D AND E HAVE BEEN REVIEWED
 UNDER THE STANDARD BUILDING CODE, ANY
 PERMIT APPLICATIONS, FOR THESE MODELS,
 RECEIVED ON OR AFTER MARCH 1, 2002 WILL
 BE REVIEWED UNDER THE FLORIDA BUILDING
 CODE 2001.
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SBC* 104.2.1&3ALL MODELS. SUBMITTED
 PLANS THAT INCLUDE AN ARCHITECT/ENGINEER
 TITLE BLOCK SHALL INCORPORATE AN
 EMBOSSED SEAL, DATE AND WET SIGNATURE OF
 THE DESIGNER (471.025 AND 481.221 F.S.)
  
 4) SBC* 1804.2ALL MODELS.SUBMIT A
 SOIL TEST REPORT.
  
 5) SHEET A10 GENERAL DETAILS. THIS SHEET
 NUMBER/TITLE COMBINATION IS USED FOR TWO
 SEPARATE SHEETS CONTAINING DIFFERENT
 DETAILS.THE TITLE/NUMBER SHALL BE
 AMENDED TO DIFFERENTIATE BETWEEN SHEETS
  
 6) SBC 705.1.3OPENING PROTECTIVES.
 TABLE 600 REQUIRES THE GLASS BLOCK
 WINDOWS ON 'COMMON PROPERTY LINES' TO BE
 HAVE 1 HOUR FIRE RESISTANCE RATING.
 SUBMIT ADDITIONAL INFORMATION TO JUSTIFY
 THE PROPOSED GLASS BLOCKS.
  
 7) SBC* 104.2.2MODEL B. THE ELEVATIONS
 SHALL INCLUDE VIEWS OF THE WINDOWS OVER-
 LOOKING THE ATRIUM.
  
 8) SBC 1005.4.4MODEL B.THE MINIMUM
 CLEAR WIDTH OF AN EMERGENCY EGRESS
 WINDOW IS 20".ON SHEET A-03, FLOOR
 LAYOUT, THE BED 2 WINDOW (TYPE D) TO THE
 ATRIUM IS SHOWN ON THE WINDOW SCHEDULE
 AS 62" WIDE.THIS IS TOO WIDE TO BE
 ACCOMMODATED IN THIS LENGTH OF WALL.
 REVISE TO DEMONSTRATE COMPLIANCE.
  
 9) SBC* 1005.4.2MODELS B AND D.THE
 ATRIUM GATE MUST ALLOW EMERGENCY ESCAPE,
 FROM BED 2, WITHOUT THE USE OF SEPARATE
 TOOLS OR KEYS.THE DOOR TYPE ELEVATION
 DOES NOT APPEAR TO SHOW THE SPECIFIED
 TYPE E DOOR AS BEING A GATE.AMEND THE
 DOOR SCHEDULE AS APPROPRIATE.
  
 10) MODEL B.SHEET A-06, ELEVATIONS,
 SHOWS A KITCHEN WINDOW AND LIVING ROOM
 PATIO DOORS THAT ARE NOT SHOWN ON THE
 FLOOR PLAN (SHEET A-03).SHOW CORRECT
 ARRANGEMENT.
  
 11) MODELS B AND C.WINDOWS AND
 EXTERIOR DOORS.SOME OF THE REFERENCES
 SHOWN ON THE ELEVATIONS DO NOT CORRELATE
 TO THOSE ON THE FLOOR PLANS AND/OR THE
 DOOR/WINDOW SCHEDULES. CORRECT THOSE
 REFERENCES CONCERNED, INCLUDING, BUT NOT
 LIMITED TO, MODEL B ATRUIM GATE, LIVING
 ROOM WINDOW, FAMILY ROOM PATIO DOOR AND
 FAMILY ROOM WINDOW, AND MODEL C MASTER
 BED WALK-IN CLOSET WINDOW.ALSO, THE
 MODEL B DOOR TYPE ELEVATION FOR THE
 ATRIUM GATE DOES NOT CORRELATE TO THE
 FLOOR PLAN OR LEFT ELEVATION.
  
 12) PROVISO:PRODUCT APPROVAL (ACCEPT-
 ANCE NO 99-1110.04) FOR SERIES 6000
 ALUMINUM FIXED WINDOW.DRAWING NO 548,
 SHEET 2 OF 4 IS MISSING.
  
 13) PRODUCT APPROVALS.SUBMIT PRODUCT
 APPROVALS APPLICABLE TO EACH OF THE
 PROPOSED WINDOW AND EXTERIOR DOOR TYPES.
 THE MISSING PRODUCT APPROVALS INCLUDE,
 AMONG OTHERS, THE WOOD ENTRANCE DOORS
 AND THE HORIZONTAL SLIDING WINDOWS.
  
 14) ACCORDING TO THE DOOR SCHEDULES THE
 SUBMITTED PRODUCT APPROVAL (ACCEPTANCE
 NO 99-0311.01) FOR THE 'CONSTRUCTION
 SERIES FLUSH OUTSWING RESIDENTIAL STEEL
 DOOR-IMPACT' IS NOT APPLICABLE TO MODEL
 B, C, D OR E.
  
 15) THE SUBMITTED ROOF TILE PRODUCT
 APPROVAL FOR INTERLOCKING ROLL CONCRETE
 TILES DOES NOT CORRELATE TO THE
 ELEVATIONS WHICH SHOW "SPANISH S CEMENT
 TILE".SUBMIT AN APPROPRIATE PRODUCT
 APPROVAL.
  
 16) SBC 1606.2SPECIFY ROOF TILE
 FASTENINGS.
  
 17) MODEL B.ROOF TRUSS SHOP DRAWING
 01448 SHOWS A NARROW ROOF ARRANGEMENT
 OVER THE ENTRANCE FOYER THAT DOES NOT
 REFLECT THE ROOF ARRANGEMENT SHOWN ON
 THE ROOF FRAMING PLAN AND ELEVATIONS.
  
 18) ALL MODELS.TRUSS ANCHOR SCHEDULE.
 USP RT161T IS NOT A VALID USP REFERENCE.
 SIMPSON MTT27B IS NOT A VALID REFERENCE.
 SPECIFY FULL REFERENCE OF USP NFM.
  
 19) SHEET A-05, ROOF FRAMING PLAN.THE
 BEAM SCHEDULE DOES NOT GIVE DETAILS OF
 PATIO BEAMS REF 8F161B.REVISE TO SHOW
 BEAM TYPE.
  
 20) SBC 2309.7ALL MODELS.CROSS
 VENTILATION SHALL BE PROVIDED FOR EACH
 SEPERATE ATTIC SPACE.AT LEAST 50% OF
 THE REQUIRED VENTILATION AREA SHALL BE
 AT A LEVEL NO LESS THAN 3FT ABOVE THE
 EAVES VENTS.
  
 21) SBC 2405.1MODELS B,C,D AND E.THE
 GLASS IN THE MASTER BED SHOWER DOOR AND
 WALLS SHALL BE SAFETY GLASS IN
 COMPLIANCE WITH THE CONSUMER PRODUCT
 SAFETY COMMISSION 16-CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201)
  
 22) FL ENERGY CODE 103.1.2THE
 ARCHITECT, OWNER OR HIS/HER LEGALLY
 DESIGNATED AGENT SHALL SIGN THE ENERGY
 CODE COMPLIANCE CERTIFICATE.
  
 23) FL ENERGY CODE 603.1.ABC.1
 MODELS B, C, D AND E.THE GARAGE DOOR
 FALLS WITHIN THE DEFINITION OF AN
 'ADJACENT' DOOR (SECT. 202 DEFINITIONS)
 AND SHALL BE SOLID CORE OR INSULATED.
 THE DOOR SCHEDULE REFERENCE MARK GIVEN
 IS '8' WHICH IS SHOWN AS A TYPE F DOOR.
 THE DOOR TYPE ELEVATIONS SHOW TYPE F AS
 BEING A DOUBLE DOOR.CORRECTION REQ'D.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-03 Cont ID  
Sent By sgraham Date 2002-01-03 Time 09:12 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***