Plan Review Details - Permit 01110936
Plan Review Stops For Permit 01110936
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-30 Cont ID  
Sent By dpalmer Date 2001-11-30 Time 09:12 Rev Time 0.00
Received By dpalmer Date 2001-11-30 Time 09:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-28 Cont ID  
Sent By dpalmer Date 2001-11-28 Time 21:41 Rev Time 0.00
Received By dpalmer Date 2001-11-28 Time 21:41 Sent To  
Notes
2001-11-28 00:00:001)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.