Plan Review Details - Permit 01110913
Plan Review Stops For Permit 01110913
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-30 Cont ID  
Sent By pkrauss Date 2001-11-30 Time 14:30 Rev Time 0.30
Received By pkrauss Date 2001-11-30 Time 14:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-11-30 Cont ID  
Sent By pkrauss Date 2001-11-30 Time 07:22 Rev Time 0.35
Received By pkrauss Date 2001-11-30 Time 07:22 Sent To  
Notes
2001-11-30 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-1989.
  
 2.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.PLEASE SUBMIT MANUFACTURER SUBMITTAL
 DATA FOR THE CONDENSER UNIT RACK.
 NOTE, 18" MINIMUM BETWEEN ROOF
 SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL. (COUNTYWIDE AMENDMENTS
 1997 SMC 304.2.5.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.