Plan Review Details - Permit 01110873
Plan Review Stops For Permit 01110873
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-12-03 Cont ID  
Sent By dpalmer Date 2001-12-03 Time 07:54 Rev Time 0.00
Received By dpalmer Date 2001-12-03 Time 07:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-28 Cont ID  
Sent By dpalmer Date 2001-11-28 Time 19:28 Rev Time 0.00
Received By dpalmer Date 2001-11-28 Time 19:27 Sent To  
Notes
2001-11-28 00:00:00************** UNSAT ***********
  
 1)NOTE> PLEASE NOTE MISSING A/C WIRING
 MISSING FRONT AND REAR PER 210-52E
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3)NOTE: LOAD CALCS NOT CORRECT.
  
 4)NOTE: GROUNDING ELECTRODE NOT CORRECT.
  
  
 PLEASE NOTE, AS PER CONVERSATION WITH
 CONTRACTOR ON 11/28/01. MORE INFO
 TO BE FAXED AND CORRECTED PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372