Plan Review Details - Permit 01110755
Plan Review Stops For Permit 01110755
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-11-26 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 22:13 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-30 Cont ID  
Sent By dpalmer Date 2001-11-30 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2001-11-30 Time 14:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-20 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 22:13 Rev Time 0.00
Received By dpalmer Date 2001-11-20 Time 22:13 Sent To B
Notes
2001-11-20 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOET THAT THERE IS NO
 INDICATION ON HEATER SPECS WHICH ONE IS
 BEING INSTALLED?
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS.
 TO INCLUDE ALL NEW POOL EQUIPMENT AND
 EXSITING LOADS AND SIZE OF EXSITING
 SERVICE.215-5
  
 3)NOTE: PLEASE SHOW WIRING.CONDUITS ETC
 ON ELECTRICAL WIRING DIAGRAM. TO BE
 DONE BY ENGINEER OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-11-20 Cont ID  
Sent By kstevens Date 2001-11-20 Time 19:56 Rev Time 0.33
Received By kstevens Date 2001-11-20 Time 19:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-20 Cont ID  
Sent By sgraham Date 2001-11-20 Time 14:56 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***