Plan Review Details - Permit 01110620
Plan Review Stops For Permit 01110620
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-11-20 Cont ID  
Sent By mcarsill Date 2001-11-20 Time 10:50 Rev Time 0.00
Received By mcarsill Date 2001-11-20 Time 10:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-12-05 Cont ID  
Sent By mcarsill Date 2001-12-05 Time 16:56 Rev Time 0.00
Received By mcarsill Date 2001-12-05 Time 16:56 Sent To  
Notes
2001-12-05 00:00:00IF THE PARKING GARAGE IS THREE STORIES
 AND FIFTY FEET IN HEIGHT A STANDPIPE
 SYSTEM WILL BE REQUIRED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FS  
Rev No 1 Status N Date 2001-12-07 Cont ID  
Sent By mcarsill Date 2001-11-20 Time 10:50 Rev Time 0.00
Received By ydavis Date 2001-11-20 Time 10:50 Sent To  
Notes
2001-11-20 00:00:001) NO CUT-SHEETS PROVIDED FOR FIRE
 SPRINKLER HEADS PLANNED FOR USE. PLEASE
 PROVIDE CUT-SHEETS.
 2) PROVIDE DETAILS FOR FIRE SPRINKLER
 INSTALLATIONS FOR DUMBWAITER AND TRASH
 CHUTE(S).
 3) PLEASE INDICATE IF THE ONE FIRE
 DEPARTMENT CONNECTION WILL SERVICE ALL
 OF THE BUILDINGS LOCATED ON THE CAMPUS.
 4) NO FIRE SPRINKLER PROTECTION PROVIDED
 FOR IT EQUIPMENT ROOM. FM 200 SYSTEM
 IS NOTED BUT CANNOT BE USED IN LIEU OF
 REQUIRED FIRE SPRINKLER PROTECTION.
 5) HOW WILL PIPE PENETRATIONS BE SEALED
 THRU RATED FIRE WALLS, ETC. WHO'S
 RESPONSIBLE FOR IT.
 6) PLEASE CLEARLY INDICATE WHY NO
 FIRE STANDPIPE SYSTEM IS PRESENT IN THE
 GARAGE. IF THE GARAGE IS THREE STORIES
 AND MORE THAN FIFTY FEET IN HEIGHT A
 STANDPIPE SYSTEM WOULD BE REQUIRED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-12-05 Cont ID  
Sent By mcarsill Date 2001-12-05 Time 16:56 Rev Time 0.00
Received By mcarsill Date 2001-12-05 Time 16:55 Sent To  
Notes
***NONE***