Plan Review Details - Permit 01110498
Plan Review Stops For Permit 01110498
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-21 Cont ID  
Sent By pkrauss Date 2001-11-21 Time 12:30 Rev Time 0.35
Received By pkrauss Date 2001-11-21 Time 12:30 Sent To  
Notes
2001-11-21 00:00:00********************PROVISO*************
  
  
 ACCESS OPENING FOR AHU SHALL BE A
 MINIMUM OF 22" X 36" CONTINUOUS FROM
 THE OPENING TO EQUIPMENT AND ITS
 CONTROLS.
  
 ALL AHU INSTALLED IN ATTIC SHALL HAVE AN
 ACCESSIBLE DISCONNECT SWITCH AND A
 110-120 VOLT A/C GROUNDING TYPE
 CONVENIENCE OUTLET.A LIGHT SHALL BE
 LOCTED ON THE SERVICE SIDE OF THE
 EQUIPMENT WHICH IS CONTROLLED BY A
 SWITCH LOCATED AT THE ACCESS OPENING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.