Plan Review Details - Permit 01110457
Plan Review Stops For Permit 01110457
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-12-26 Cont ID  
Sent By jwitmer Date 2001-12-26 Time 09:23 Rev Time 1.50
Received By jwitmer Date 2001-12-26 Time 09:23 Sent To  
Notes
2001-12-26 00:00:00PROVISO: THAT THE FENCING BEHIND THE
 RESTRAUNT WILL NOT BLOCK THE EMERGENCY
 EGRESS REQUIREMENTS TO THE EAST SIDE OF
 THE RESTRAUNT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-22 Cont ID  
Sent By jwitmer Date 2001-11-22 Time 14:02 Rev Time 1.25
Received By jwitmer Date 2001-11-22 Time 14:02 Sent To  
Notes
2001-11-22 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01110457
 6200 S DIXIE HWY
 CONT: DUANE THOMAS INCORP
 TEL: (561)575-0610
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
 FL ACC CODE= FLORIDA ACCESSIBILITY CODE
  
 1)- SBC104.2.2* PLEASE PROVIDE AN OVER
 ALL PLOT PLAN INDICATING THE LOCATION
 OF THE TENANT SPACE IN RELATIONSHIP TO
 THE BUILDING.
  
 2)- SBC1004.1.4 WHERE TWO OR MORE EXITS
 OR EXIT ACCESS DOORS ARE REQUIRED, AT
 LEAST (2) OF THE EXITS OR EXIT ACCESS
 DOORS SHALL BE PLACED A DISTANCE APART
 NOT LESS THAN ONE HALF OF THE LENGTH OF
 THE MAXIMUM OVERALL DIAGONAL DIMENSION
 OF THE BUILDINGOR AREA TO BE SERVED
 MEASURED IN A STRAIGHT LINE BETWEEN SUCH
 EXITS OR EXIT ACCESS DOORS.
  
 3)- SBC 1001.1.3 THE EXTERIOR DOORS
 LEADING FROM THE KITHEN CAN NOT BE CONSI
 DERED AS EXITDOORS FOR THE PUBLIC
 SINCE THIS CODE ARTICLE RESTRICTS IT.
  
 4)- THIS BUILDING IS A (2) STORY BUILD-
 ING. INDICATE HOW THE 2 HR ASSEMBLY
 TENNANT SEPERATION IS ACCOMPLISHED?
 (SBCTABLE 704.1.) FIRST FLOORCEILING ASS
 EMBLY TO SECOND FLOOR FLOOR?UL LISTING?
 INDICATE WHERE THE GREASE VENTS & CHASES
 ARE AND SEPERATION FROM THE SECOND FLOOR
 TENANT?
  
 5)- SBC 1204.2 THE WALLS & FLOORS OF ALL
 PUBLIC REST ROOMS SHALL BE LINED WITH
 NONABSORANT MATERIAL TO A HEIGTH OF 4'-0
 ABOVE THE FLOOR.
  
 6)- 1203.4.2 EVERY TOILET ROOM SHALL
 HAVE A WINDOW OR APPROVED MECHANICAL
 VENTILATION.
  
 7) FL ACC CODEFLOOR FINISHES:4.5
 FLOOR SURFACES ALONG ACCESSIBLE ROUTES
 AND IN ACCESSIBLE ROOMS AND SPACES
 INCLUDING FLOORS WALKS AND RAMPS SHALL
 BE STABLE, FIRM AND SLIP RESISTANT.
 ADDAAG A-5 A STATIC COEFFICIEENTOF FRIC-
 TION OF 0.6 FOR ACCESSIBLE ROUTES &
 0.8 FOR RAMPS.
  
 THESE PLANS ARE NOT THOROUGH ENOUGH TO
 DO A COMPLETE REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2002-01-04 Cont ID  
Sent By dpalmer Date 2002-01-04 Time 14:15 Rev Time 0.00
Received By dpalmer Date 2002-01-04 Time 14:15 Sent To  
Notes
2002-01-04 00:00:00ELECTRICAL PERMIT VOIDED PER GC.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-06 Cont ID  
Sent By dpalmer Date 2001-12-06 Time 07:41 Rev Time 0.00
Received By dpalmer Date 2001-12-06 Time 07:41 Sent To  
Notes
2001-12-06 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE, SAME NOTES AS FIRST
 REVIEW.
 PLEASE THAT PERMIT THAT IS EXISTING
 IS ONLY FOR SERVICE CHANGE AND A/C
 HOOK UP.
  
 PLEASE ADDRESS NOTES. PLEASE SUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By dpalmer Date 2001-11-19 Time 19:16 Rev Time 0.00
Received By dpalmer Date 2001-11-19 Time 19:16 Sent To  
Notes
2001-11-19 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE PLACE BRANCH CIRCUIT #`S
 ON PLANS, AND CORRELATE WITH PANEL
 SCHEDULE.
 PLEASE INCLUDE EM LTS AND EXIT LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-11-21 Cont ID  
Sent By mcarsill Date 2001-11-21 Time 11:34 Rev Time 0.00
Received By mcarsill Date 2001-11-21 Time 11:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-11-27 Cont ID  
Sent By pkrauss Date 2001-11-27 Time 14:44 Rev Time 0.40
Received By pkrauss Date 2001-11-27 Time 14:42 Sent To  
Notes
2001-11-27 00:00:00 
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-01-02 Cont ID  
Sent By kstevens Date 2002-01-02 Time 18:09 Rev Time 0.50
Received By kstevens Date 2002-01-02 Time 18:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By kstevens Date 2001-11-19 Time 18:42 Rev Time 1.00
Received By kstevens Date 2001-11-19 Time 18:42 Sent To  
Notes
2001-11-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE P-1 GENERAL NOTES #16, AIR
 CHAMBERS ARE QUICK FIX AND REQUIRE ACC-
 ESS PANELS AND SHALL BE RECHARGEABLE PER
 SPC 607.8.3. WATER HAMMER ARRESTORS
 SHOULD BE USED AND SHALL BE SIZED AND
 LOCATED CLOSE TO FIXTURES PER MANUFACT-
 URE INSTALLATION INSTRUCTIONS AND PDI-WH
 201.
 2) PAGE P-1 THREE COMPARTMENT COOLER IN
 BAR AREA SHALL INDIRECTLY DRAIN INTO A
 FLOOR SINK PER SPC SEC 804.1. PLEASE
 CHANGE DRAIN TO REFLECT INDIRECT DRAIN.
 SANITARY RISER DIAGRAM REQUIRED FOR PIP-
 ING IN BAR AREA.
 3) PAGE P-1 PLEASE SHOW LOCATION OF
 WATER HEATER FOR NEW RESTROOMS AND BAR
 SINK. IF LOCATED ON A SHELF OR ABOVE THE
 CEILING A PERMINANT SHIPS LADDER AND A
 WORKING PLATFORM MINIMUM 30"X30" SHALL
 BE REQUIRED AND DETAILS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377