Plan Review Details - Permit 01110345
Plan Review Stops For Permit 01110345
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-02-11 Cont ID  
Sent By jwitmer Date 2002-02-11 Time 16:06 Rev Time 0.75
Received By jwitmer Date 2002-02-11 Time 16:06 Sent To  
Notes
2002-02-11 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01110345
 1608 S DIXIE HWY
 CONT: CHEROKEE BUILDERS
 TELL: (561) 346-1346
  
 SBC= 1997 STANDARD BUILDING CODE
 FL ACC= FLORIDA ACCESSIBILITY CODE 1997
  
 1)- FLORIDA STATE STATUTE 481.229
 EXCEPTION 1-C: AN ARCHITECT SHALL BE RE-
 QUIRED FOR WORK IN EXCESS OF $25,000.00
 THE ELECTRICAL NOTE #3 INDICATES VALUE
 TO LOW. THE CALCULATED VALUE IS CLOSE TO
 $79,000.00.
  
 2)- SBC 1104.2.2 NOT ENOUDH INFORMATION
 MISSING DOOR INFO, ROOM DIMENSIONS &
 SCALE OF DRAWING,ETC.
  
 3)- THE OWNER INDICATED THERE TO BE
 EXISTING FIRE SPRINKLERS, NO INFORMATION
 SUPPLIED.
  
 4)- SBC TABLE 803.3 INTERIOR FINISH SCHE
 DULE NOT GIVEN.
  
 5)- THERE IS A DEAD END CORRIDOR NEXT TO
 STORAGE AREA #1.
  
 6)- HANDICAPPED RESTROOMS, THERE ISN'T
 A 5'-0" TURNING RADIUS, NO INFORMATION
 ON BACKING HAND RAILS NOR OTHER ELEMENTS
 THAT MAKE UP A HANDICAPPED RESTROOM.
  
 7)- FL ACC CODE 4.13.6 THE PLANS DO NOT
 HAVE THE MANEUVERING CLEARENCES AT
 DOORWAYS.
  
 8)- THE PLANS ARE MISSING TENANT SEPERAT
 ION, RATING, SEPERATION BETWEEN STORAGE
 AREA AND THE COMMON EXIT ACCESS CORRIDOR
  
 9)- MISSING FLOOR/ CEILING ASSEMBLY
 TENANT SEPERATION.
  
 10)- VENTILATION FOR RESTROOM?
  
 11)- PUBLIC RESTROOMS SBC1204.3
 TO BE LINED WITH AN NONABSORBANT MATER-
 IAL TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
 12)- THERE IS A ROOM BETWEEN RESTROOM
 B & C THAT HAS NO ENTRY?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By jwitmer Date 2001-11-19 Time 16:46 Rev Time 1.00
Received By jwitmer Date 2001-11-19 Time 16:46 Sent To  
Notes
2001-11-19 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01110345
 1608 S DIXIE /SUITE
 CONT: CHEROKEE BUILDERS
 TEL: (561) 346-1346
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SBC104.2.7.* PLANS SHALL BE DRAWN TO
 A MINIMUM OF 1/8TH INCH SCALE .
 2) TITLE BLOCK PERSON WHO IS RESPONSIBLE
 FOR DRAWING THE PLANS, TELEPHONE NUMBER
 3)- BUILDING INFORMATION: SBC TABLE 500
 FOR OCCUPANCY, TABLE 600 FOR MINIMUM
 BUILDING TYPE.
 4)- INDICATE THE AMOUNT OF SQ FT IN
 TENANT SPACE. SINGLE ENTRY?
 5)- PROPOSED RESTROOMS HANDICAPPED ACCES
 IBLE? SHOW DIMENSIONS, BACKING & INDI-
 CATE WALL AND FLOOR FINISHES.
 6) PLANS ARE INADEQUATE TO DO A THOROUGH
 PLAN REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-01-30 Cont ID  
Sent By dpalmer Date 2002-01-30 Time 19:08 Rev Time 0.00
Received By dpalmer Date 2002-01-30 Time 19:08 Sent To  
Notes
2002-01-30 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE COMMENTS FROM FIRE
 PLAN REVIEW WILL NEED TO BE ADDRESSED
 DUE TO POSSIBLE ELECTRICAL CHANGES TO
 BE MADE.
  
 2)NOTE: PLEASE NOTE/CLARIFY DEAD-END
 HALLWAY? LIGHTING? STORAGE? ECT.
  
 3)NOTE: PLEASE NOTE TOTAL VALUE OF JOB
 WILL NEED TO BE INCREASED. PLEASE NOTE
 THAT CONTRACT FOR ELECTRICAL ALONE IS
 MORETHAN HALF THE VALUE SUBMITTED AND
 NO PLUMB/BLDG OR A/C WORK ? PLEASE
 SUBMIT CONTRACTS FOR BLDG AND PLUMB
 TO VERIFY VALUE.PER 104.6.5 ADMIN CODE
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By pkrauss Date 2001-11-19 Time 13:22 Rev Time 0.00
Received By dpalmer Date 2001-11-19 Time 13:43 Sent To  
Notes
2001-11-19 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT ELECTRICAL PLANS
 FOR REVIEW SHOWING LAYOUT FOR ANY NEW
 OUTELTS AND LIGHTING??
  
 PLEASESUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PLAMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-01-24 Cont ID  
Sent By mcarsill Date 2002-01-24 Time 09:40 Rev Time 0.00
Received By mcarsill Date 2002-01-24 Time 09:40 Sent To  
Notes
2002-01-24 00:00:001) FLOOR PLAN DOES NOT INDICATE
 EMERGENCY LIGHTS OR EXIT SIGNS.
 2) FLOOR PLAN DOES NOT INDICATE DOOR
 SIZES.
 3) FLOOR PLAN DOES NOT INDICATE ANY
 INFORMATION REGARDING THE FIRE
 SPRINKLER SYSTEM.
 4) FLOOR PLAN DOES NOT INDICATE INTERIOR
 FINISH CLASSIFICATION INFORMATION FOR
 WALLS AND CEILINGS.
 5) FLOOR PLAN DOES NOT INDICATE ANY
 INFORMATION ON WHETHER THE INTERIOR
 STAIR IS RATED.
 6) PAPER INCLUDED WITH PERMIT
 APPLICATION SHOULD BE CORRELATED TO THE
 FLOOR PLAN SO ALL INFORMATION CAN
 BE CORRECTLY DETERMINED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By mcarsill Date 2001-11-19 Time 15:24 Rev Time 0.00
Received By mcarsill Date 2001-11-19 Time 15:24 Sent To  
Notes
2001-11-19 00:00:001) INSUFFICIENT INFORMATION PROVIDED
 TO REVIEW SUBJECT DRAWINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2002-02-13 Cont ID  
Sent By pkrauss Date 2002-02-13 Time 15:06 Rev Time 0.25
Received By pkrauss Date 2002-02-13 Time 15:05 Sent To  
Notes
2002-02-13 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By pkrauss Date 2001-11-19 Time 12:52 Rev Time 0.35
Received By pkrauss Date 2001-11-19 Time 12:47 Sent To E
Notes
2001-11-19 00:00:00 
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE THE FOLLOWING
 PLANS AND THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 1.INDICATE SIZE, MATERIAL, LAYOUT AND
 CFM OF ANY NEW DUCT WORK TO BE
 INSTALLED.
  
 2.SUBMIT MANUFACTURER DATA FOR EXHAUST
 FANS BEING INSTALLED. (1997 SMC
 503.3.1)
  
 3.SHOW COMPLIANCE WITH 1997 SMC 501.2.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.
  
  
 NO AIR SUPPLIED TO OFFICE OR RESTROOM.
  
 SHOW COMPLIANCE WITH 1997 SMC 501.2, AIR
 MAKE-UP FOR RESTROOM.
  
 PROVISO WRITTEN ON PLAN:
  
 1. NO COMBUSTIBLES ABOVE THE CEILING IN
 THE RETURN AIR PLENUM.
 1997 SMC 609.1.1.
  
 2. FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS.
 NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-02-11 Cont ID  
Sent By kstevens Date 2002-02-11 Time 08:34 Rev Time 1.50
Received By kstevens Date 2002-02-11 Time 08:34 Sent To  
Notes
2002-02-11 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLEASE PROVIDE A COPY OF THE CONTRACT
 SO SEC 4.1.6(2), 20 PERCENT OVER CONT.
 CAN BE ESTABLISHED.
 2) PLEASE SHOW CLEAR FLOOR SPACE FOR ALL
 PLUMBING FIXTURES.
 3) TURNING RADIUS REQUIRED TO BE 5"0",
 NOT 48" AS SHOWN.
 4) PLEASE SHOW DETAIL FOR BACKING FOR
 GRAB BARS.
 5) PLEASE GIVE MEASUREMENTS FOR TOILET
 ROOMS. GIVE FINISHED MEASURMENTS FOR ALL
 SHOWERS.
 6) PLEASE SUBMIT RISER DIAGRAMS THAT ARE
 CLEAR AND READABLE. PLEASE INDICATE
 WHICH BATHROOM IS WHICH ON RISER DIAGRAM
 3 NEW BATHROOMS BUT 4 SHOWN ON RISER DIA
 GRAM. HOW DOES 4TH BATHROOM TIE INTO THE
 REST OF THE RISER?
 7) SANITARY RISER SHOWS SLOP SINKS BUT
 FLOOR PLAN DOES NOT SHOW ANY.
 8) PLEASE GIVE AN ELEVATION FOR W/HEATER
 IS IT GOING TO BE ON THE FLOOR? IF ON
 SHELF A PERMINATE SHIPS LADDER WILL BE
 REQUIRED TO MAKE THE HEATER ACCESSIBLE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-09 Cont ID  
Sent By pschmitz Date 2001-11-09 Time 18:10 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-11-09 00:00:00PLUMBING PLAN REVIEW, DENIED.
 (1) CODE REFERENCES STD PLBG-94
 SEC 104.3 PROVIDE ISOMETRIC DRAWING OF
 THE DRAIN, WASTE & VENT SYSTEM; ALSO TH
 WATER PIPING, SHOW LOCATION OF THE WATER
 HEATERS. LIST TYPES OF MATERIALS,PIPE
 SIZES.
 (2) SHOW LOCATION OF THE WATER SERVICE
 BACK FLOW PREVENTER, LOCAL ORD #2853-95.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233