Plan Review Stops For Permit 01110334 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-12-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-10 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-12-10 |
Time |
15:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-11-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-11-13 |
Time |
21:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-11-13 |
Time |
21:10 |
Sent To |
|
|
Notes |
2001-11-13 00:00:00 | ******************** UNSAT ********** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2) PLEASE NOTE MISSING OUTLET FOR A/C | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | MECHANICAL CODE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
|