Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-02-11 Cont ID  
Sent By pkrauss Date 2002-02-11 Time 14:01 Rev Time 0.40
Received By pkrauss Date 2002-02-11 Time 14:01 Sent To  
Notes
2002-02-11 00:00:00 
 PROVISO:
  
 ATTIC ACCESS FOR AHU #2 - OPENING SHALL
 BE NO LESS THAN 22" X 36" CONTINUOUS
 FROM THE OPENING TO THE EQUIPMENT AND
 ITS CONTROLS (1997 SMC 304.4.1).
  
 AUXILLIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED FOR AHU INSTALLED
 IN ATTIC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.