2002-01-18 00:00:00 | APPROVED WITH PROVISO: |
| 1-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| DOORS. PRODUCT APPROVAL SUBMITTED IS |
| FOR INSTALLATION IN A WOOD FRAME. SEE |
| PRODUCT APPROVAL FRONT PAGE. |
| -PROVIDE LEGIBLE DRAWINGS ALSO. |
| 2-TRUSS DRAWINGS: |
| NOTE: CONTRACTOR CHANGED TRUSS CO. |
| NOW, THERE ARE NEW COMMENTS FOR NEW |
| ENGINEERED TRUSS PACKAGE. |
| A)ENGINEER TO UPDATE ALL GENERAL TRUSS |
| DRAWINGS TO REFLECT ACTUAL CODES: |
| SBC 1997 FOR 110 MPH OR ASCE 7-95 FOR |
| 140 MPH WIND LOAD. REVISE AS REQUIRED. |
| B)THERE ARE TWO DIFFERENT ENGINEERS |
| SIGNING AND SEALING THESE DRAWINGS. |
| FOLLOW THE REQUIREMENTS OF CHAPTER |
| 471 FOR A CHANGE OF ENGINEER. |
| C)GENERAL TRUSS DRAWINGS ARE NOT LEGIBLE |
| D)ENGINEERED TRUSSES ARE DESIGNED USING |
| ASCE 7-98 FOR 110MPH. IF USING ASCE-98 |
| THEN, USE THE RIGHT WIND LOAD ZONE, |
| WHICH IS 140MPH ZONE. REVISE AS REQ'D. |
| E)CLARIFY WHAT IT MEANS ON ENGINEERED |
| TRUSS DRAWINGS WHEN REFERING TO 15' |
| ABOVE GROUND LEVEL. IS THIS THE MEAN |
| ROOF HEIGHT? OR WALL HEIGHT?. SPECIFY |
| AS REQUIRED AND REMEMBER THAT THIS |
| BUILDING HAS AN SLOPED ROOF, NOT FLAT |
| ROOF. REVISE AS REQUIRED. |
| 3-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| REVISE ORIGINAL PLANS TO AVOID DELAYS |
| OR UNNECESSARY RETURNS FOR FUTURE |
| SUBMITTALS. |
| |
| |
| |
| NOTE: THERE WILL BE A RESUBMITTAL FEE |
| FOR TRUSS DRAWINGS. THEY HAVE BEEN |
| REVIEWED/DENIED TWICE ALREADY. |