2001-12-01 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMENCEMENT. |
| 2-PROVIDE COMPLETE SECTION/DETAIL AT |
| INTERIOR BEARING WALL BETWEEN GARAGE |
| AND FOYER SHOWING RECESS AT GARAGE. |
| SEE SIZE OF FOOTING SPECIFIED. |
| SPECIFY ALL FASTENERS. |
| 3-REVISE ATTIC ACCESS SIZE AT MASTER |
| BEDRM. SEE PLANS & SEC. 2309.6 SBC/97. |
| ALSO, REVISE DETAIL D/2. |
| 4-SPECIFY CONNECTORS AT BOTTOM OF STEEL |
| COLUMNS AT REAR PORCH. SEC. 104.2.2 |
| CITY AMENDMENTS TO SBC 1997. |
| 5-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| SEE PLANS. SEC. 2405.2 SBC 1997. |
| 6-CLEARLY INDICATE ON PLANS THE OPTIONS |
| THAT ARE GOING TO BE BUILT. CROSS OUT |
| THE OTHERS. |
| 7-PROVIDE PRODUCT APPROVAL FOR: |
| A)FRENCH DOORS WITH SIDELITES SINGLE |
| ASSEMBLY IF OPTION IS SELECTED. |
| B)FIXED GLASS AT BREAKFAST AREA. SEE |
| SIZE SHOWN ON PLANS. |
| C)ENTRY DOORS PRODUCT APPROVAL EXPIRED. |
| 8-REVISE ENERGY CALCULATIONS: |
| -UNDER ATTIC AREA IS INCORRECT. SEE |
| SEC. 604.1.A.1 OF FL. ENERGY CODE,1997 |
| 9-CONNECTOR SPECIFIED FOR TRUSS H7B DOES |
| NOT RESIST THE UPLIFT LOADS. SEE |
| ENGINEERED TRUSSES. |
| 10-ROOF TRUSSES: |
| -UPDATE ALL GENERAL DETAILS. USE ASCE |
| 7-95 FOR 140MPH, NOT ASCE 7-93. SEE |
| COMMENTS ON REVIEWED SET. |
| 11-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| PLEASE RETURN REVIEWED SET AFTER |
| CORRECTIONS ARE DONE TO ORIGINAL DWGS |
| IN ORDER TO EXPEDITE THE REVIEW. |