Plan Review Details - Permit 01101812
Plan Review Stops For Permit 01101812
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-12-12 Cont ID  
Sent By lmartine Date 2001-12-12 Time 12:30 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By jwitmer Date 2001-11-26 Time 13:19 Rev Time 1.50
Received By jwitmer Date 2001-11-26 Time 13:19 Sent To  
Notes
2001-11-26 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01101812
 1925 S OLIVE AV
 CONT: IRONWOOD PROPERTIES
 TEL: (561) 279-8952
  
 SBC=1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
 FL ACC CODE= FLORIDA ACCESSIBILITY CODE
 FL S. S.= FLORIDA STATE STATUTE
  
 1)- FL S S 514.021 SHOW COMPLIANCE WITH
 FENCING & REQUIRED SECURE ENTRY AROUND
 THE POOL AREA.
  
 2)- THE PERMIT APPLICATION STATES THIS
 APPLICATION WILL BE FOR CABANAS, TRELLIS
 AND WALL, IS THE POOL DECK TO BE CONSID-
 ERED UNDER THIS PERMIT? IF SO THE PLANS
 NEED TO SHOW THE SLOPE AWAY FROM THE
 POOL, NOTE THE WALL ON THE BACK SIDE OF
 THE TRELLIS WILL NOT ALLOW FOR DRAIAGE?
  
 3)- SHEET A.63 DOESN'T HAVE ANY SECTIONS
 THROUGH THE CABANA SLABS, INDICATING THE
 FOUNDATION DESIGN, SOILS TERMITE TREAT-
 MENT OR VAPOR BARRIER. THERE IS NO INFOR
 MATION ON THE VERTICLAL NOR HORIZONTAL
 STEEL REINFORCING OR COLUMN BEAM DESIGN.
  
 4)- SBC 104.2.2* DISCREPANCY BETWEEN
 SHEETS A.62 & E.8/P.1 SEE STORAGE LAYOUT
  
 5)- PLUMBING DETAILS VENTING WILL RE-
 QUIRE 3" VENTS FOR EACH CABANA. THE DE-
 TAILS FOR THE BEAM ARE NOT INDICATED FOR
 THESE 2 BUILDINGS, IF CONCRETE BEAM SBC
 1907.3.5(1) PIPES EMBEDDED IN BEAMS
 SHALL NOT BE LARGER IN OUTSIDE DIMENSION
 THAN 1/3 THE OVERALL THICKNESS OF THE
 BEAM.
 IF BLOCK, A MASONRY APPLICATION,
 ACI530.(4.1.1.1) DESIGN SHALL NOT CONSID
 ER CONDUITS,PIPES OR SLEEVES AS
 STRUCURALLYREPLACING THE DISPLACED
 MASONARY.
  
 6)- SBC 1204.2 PUBLIC RESTROOMS, THE
 WALLS & FLOORS OF ALL PUBLIC RESTROOMS
 SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4 FT ABOVE THE
 FLOOR LINE.
  
 7)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 ALL GLAZED OPENINGS WILL REQUIRE PRODUCT
 TESTING, WINDOWS, DOORS & ROOFING ASSEM-
 BLIES.
  
 8)- SHEET A.62 BAR-B-Q GRILL, THERE
 ISN'T ACCESS TO THE BAR-B-Q GRILL AS
 REQUIRED UNDER THE FAIR HOUSING ACT.
 SEE 4.3 ACCESSIBLE ROUTE, & 4.5 GROUND
 AND FLOOR SURFACES.
  
 9)- SHEET A.64 DETAIL FOR HI RIB LATH,
 SBC2504.2.2 INSTALLATION OF EXTERIOR
 LATHING AND FRAMING SHALL COMPLY WITH
 ASTM 1063 C. ATTACHMENT OF HI-RIB METAL
 LATH TO HORIZONTAL FRAMING MEMBERS SHALL
 HAVE 1 3/4" PENETRATION INTO HORIZONTAL
 WOOD SUPPORTS.RIB LATH SHALL BE ATTACHED
 AT EACH RIB.
  
 PLANS SHALL BE TAKEN TO PALM BEACH
 COUNTY FOR IMPACT FEE ASSESSMENT.
  
 SBC 104.2.2 ADDITIONAL INFORMATION,
 THERE ARE STAIR DETAILS ON SHEET A.63 &
 S4.0 WHERE ARE THEY TO BE USED?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-04-01 Cont ID  
Sent By dpalmer Date 2002-04-01 Time 13:47 Rev Time 0.00
Received By dpalmer Date 2002-04-01 Time 13:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-12-11 Cont ID  
Sent By dpalmer Date 2001-12-11 Time 21:34 Rev Time 0.00
Received By dpalmer Date 2001-12-11 Time 21:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By dpalmer Date 2001-11-19 Time 20:24 Rev Time 0.00
Received By dpalmer Date 2001-11-19 Time 20:10 Sent To  
Notes
2001-11-19 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT CIRCUITS FOR
 LIGHTING ON BLDGS "E" AND "F" ARE
 SHOWN COMING FROM OTHER BLDGS.
 PLEASE NOTE MEANS OF DISCONNECT FOR
 THESE CIRCUITS PER 225-31. PLEASE SHOW.
  
 2)NOTE: PLEASE PROVIDE VOLTAGE DROP FOR
 LIGHTING FIXTURES "TYPE M" SCALE SHOWS
 FIXTURES AT WAY OVER 300`- 400` OF
 CONDUIT AND WIRE.
  
 3)NOTE: PLEASE PLACE NOTE ON PLANS THAT
 MEANS OF DISCONNECT SHALL BE PROPERLY
 LABELED.225-37
  
 4)NOTE: PLEASE NOTE THAT RISER SHOW A
 SINGLE PHASE SERVICE AND YET METER TO
 MAIN PANEL SHOWS A #1 BOND?? PLEASE NOTE
 THAT THIS SHOWN AS PARALLELING THE
 NEUTRAL.
  
 5)NOTE: PLEASE SHOW MEANS OF GROUNDING
 FOR EACH PANEL AT EACH BUILDING,250-50
 THIS IS SHOWN FOR PANEL"HP" BUT NOT FOR
 OTHERS.
  
 PLEASE NOTE THAT ALL PANELS AT EACH
 BLDG TO BE LABELED AS TO "MAIN" DISC.
 LOCATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-12-12 Cont ID  
Sent By lmartine Date 2001-12-12 Time 10:37 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 17:13 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 17:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-12-12 Cont ID  
Sent By pkrauss Date 2001-12-12 Time 10:51 Rev Time 0.30
Received By pkrauss Date 2001-12-12 Time 10:51 Sent To  
Notes
2001-12-12 00:00:00 
  
 MECHANICAL CONTRACTOR REQUIRED TO APPLY
 FOR PERMIT SEPARATELY.ADDITIONAL FEES
 WILL BE REQUIRED.
  
 PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-12-12 Cont ID  
Sent By pschmitz Date 2001-12-12 Time 08:51 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-12 00:00:00APPROVED, PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By kstevens Date 2001-11-19 Time 10:33 Rev Time 0.50
Received By kstevens Date 2001-11-19 Time 10:32 Sent To  
Notes
2001-11-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PER PLAN REVIEW FOR PERMIT #01030614,
 PALM BEACH COUNTY HEALTH DEPT. PLAN RE-
 VIEW AND COMMENTS PRIOR TO PLUMBING PLAN
 REVIEW.
  
 2) PER PLAN REVIEW FOR PERMIT #01030614,
 FULL IRRIGATION PLANS TO BE SUBMITTED
 FOR IRRIGATION PERMIT APPLICATION.
 SEPARATE PERMIT FOR BACKFLOW TO BE IN-
 STALLED BY PLUMBING CONTRACTOR.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-15 Cont ID  
Sent By sgraham Date 2001-11-15 Time 15:14 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***