Plan Review Details - Permit 01101601
Plan Review Stops For Permit 01101601 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-02-07 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-07 |
Time |
16:16 |
Rev Time |
0.05 |
Received By |
pkrauss |
Date |
2002-02-07 |
Time |
16:16 |
Sent To |
|
|
Notes |
2002-02-07 00:00:00 | APPROVED PER CAPT MIKE CARSILLO | | 2-7-02. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2002-02-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-22 |
Time |
13:16 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2002-02-22 |
Time |
13:16 |
Sent To |
|
|
Notes |
2002-02-22 00:00:00 | AS BUILTS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-01-23 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-23 |
Time |
08:32 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2002-01-23 |
Time |
08:31 |
Sent To |
|
|
Notes |
2002-01-23 00:00:00 | | | | | PROVISO: | | | | SECTIONS TO "BLANKED" OFF SHALL BE | | MARKED ACCORDINGLY AS TO NOT | | INADVERTENTLY MISPLACE THESE SECTIONS | | AFTER CLEANING/MAINTENANCE. | | | | PLEASE NOTE SECTIONS "BLANKED" OFF SHALL | | NOT HAVE EQUIPMENT THAT PRODUCE GREASE | | LADEN VAPORS INSTALLED BENEATH THESE | | AREAS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-11-16 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-11-16 |
Time |
07:30 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-11-16 |
Time |
07:30 |
Sent To |
|
|
Notes |
2001-11-16 00:00:00 | PROVISO ON PLAN- FAN SHUTDOWN BY DUCT | | SMOKE DETECTOR WITH NOTIFICATION TO | | ALARM/STROBE IN NORMALLY OCCUPIED | | AREAS.1997 SMC 406.1 AND NFPA 90A | | 4-4.4.3. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
|
Date |
2001-10-26 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-10-26 |
Time |
09:37 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2001-10-26 |
Time |
09:35 |
Sent To |
|
|
Notes |
2001-11-01 00:00:00 | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW. | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | ASHRAE 62-89. | | | | 2.AIR BALANCE SCHEDULE SHOWING | | COMPLIANCE WITH 1997 SMC 501.2. | | | | NOTE:PRIOR TO CONNECTING TO EXISTING | | AHU, AHU SHALL BE CLEANED AND | | SANITIZED. | | | | PLEASE PROVIDE TWO SETS OF | | PLANS WITH THE ABOVE INFORMATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT 8388. |
|
|
|