Plan Review Details - Permit 01101601
Plan Review Stops For Permit 01101601
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-02-07 Cont ID  
Sent By pkrauss Date 2002-02-07 Time 16:16 Rev Time 0.05
Received By pkrauss Date 2002-02-07 Time 16:16 Sent To  
Notes
2002-02-07 00:00:00APPROVED PER CAPT MIKE CARSILLO
 2-7-02.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-02-22 Cont ID  
Sent By pkrauss Date 2002-02-22 Time 13:16 Rev Time 0.30
Received By pkrauss Date 2002-02-22 Time 13:16 Sent To  
Notes
2002-02-22 00:00:00AS BUILTS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-01-23 Cont ID  
Sent By pkrauss Date 2002-01-23 Time 08:32 Rev Time 0.45
Received By pkrauss Date 2002-01-23 Time 08:31 Sent To  
Notes
2002-01-23 00:00:00 
  
 PROVISO:
  
 SECTIONS TO "BLANKED" OFF SHALL BE
 MARKED ACCORDINGLY AS TO NOT
 INADVERTENTLY MISPLACE THESE SECTIONS
 AFTER CLEANING/MAINTENANCE.
  
 PLEASE NOTE SECTIONS "BLANKED" OFF SHALL
 NOT HAVE EQUIPMENT THAT PRODUCE GREASE
 LADEN VAPORS INSTALLED BENEATH THESE
 AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-16 Cont ID  
Sent By pkrauss Date 2001-11-16 Time 07:30 Rev Time 0.35
Received By pkrauss Date 2001-11-16 Time 07:30 Sent To  
Notes
2001-11-16 00:00:00PROVISO ON PLAN- FAN SHUTDOWN BY DUCT
 SMOKE DETECTOR WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS.1997 SMC 406.1 AND NFPA 90A
 4-4.4.3.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date 2001-10-26 Cont ID  
Sent By pkrauss Date 2001-10-26 Time 09:37 Rev Time 0.40
Received By pkrauss Date 2001-10-26 Time 09:35 Sent To  
Notes
2001-11-01 00:00:00 
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 NOTE:PRIOR TO CONNECTING TO EXISTING
 AHU, AHU SHALL BE CLEANED AND
 SANITIZED.
  
 PLEASE PROVIDE TWO SETS OF
 PLANS WITH THE ABOVE INFORMATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT 8388.