Plan Review Details - Permit 01101545
Plan Review Stops For Permit 01101545
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-11-02 Cont ID  
Sent By jwitmer Date 2001-11-02 Time 07:17 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-14 Cont ID  
Sent By dpalmer Date 2002-01-14 Time 15:51 Rev Time 0.00
Received By dpalmer Date 2002-01-14 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2001-11-01 Cont ID  
Sent By dpalmer Date 2001-11-01 Time 12:11 Rev Time 0.00
Received By dpalmer Date 2001-11-01 Time 12:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-16 Cont ID  
Sent By mcarsill Date 2002-01-16 Time 13:50 Rev Time 0.00
Received By mcarsill Date 2002-01-16 Time 13:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-10-29 Cont ID  
Sent By mcarsill Date 2001-10-29 Time 14:09 Rev Time 0.00
Received By mcarsill Date 2001-10-29 Time 14:09 Sent To  
Notes
2001-10-29 00:00:001) STAIR PRESSURIZATION TO BE TIED
 INTO BUILDING'S EMERGENCY POWER
 SYSTEM.
 2) THE STAIR PRESSURIZATION SHALL
 PROVIDE 0.05 OF WATER COLUMN IN
 ADDITION TO STACK EFFECT EXPECTED.
 3) STAIR PRESSURIZATION SHALL ACTIVATE
 UPON ACTIVATION OF INITIATING DEVICES
 FOR THE FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-11 Cont ID  
Sent By pkrauss Date 2002-01-11 Time 07:19 Rev Time 0.40
Received By pkrauss Date 2002-01-11 Time 07:14 Sent To  
Notes
2002-01-11 00:00:00 
 PROVISO:
  
 TEST REQUIRED BY AN INDEPENDENT TEST AND
 BALANCE COMPANY IN THE PRESENCE OF
 MECHANICAL INSPECTOR AND FIRE INSPECTOR.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-01 Cont ID  
Sent By ndenmark Date 2001-11-01 Time 11:56 Rev Time 0.50
Received By ndenmark Date 2001-11-01 Time 11:56 Sent To  
Notes
2001-11-01 00:00:00PROVISO:
  
 ACCEPTANCE TEST OF STAIRWAY
 PRESSURIZATION REQUIRED FOR FINAL.
 CONTACT THE FIRE INSPECTOR AND MYSELF
 FOR COORDINATION OF TIME/DATE FOR TEST.
 INDEPENDANT TEST AND BALANCE COMPANY
 WILL BE REQUIRED TO CONDUCT TEST
 INCLUDING DOOR PULLS AND DIFFERENTIAL
 PRESSURE ACROSS STAIR WAY DOORS IN
 ACCORDANCE WITH NFPA 92A AND
 CONSTRUTION SERVICES MECHANICAL
 REQUIREMENTS.
 PRETEST OF SYSTEM EXPECTED PRIOR TO
 SCHEDULING TEST WITH CITY INSPECTORS
  
 ANY QUESTIONS ON TEST CRITERIA CONTACT
 NANCY DENMARK, CHIEF MECHANICAL
 INSPECTOR @ (561) 659-8096 EXT. 8221

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-01-10 Cont ID  
Sent By jwitmer Date 2002-01-10 Time 17:10 Rev Time 1.50
Received By jwitmer Date 2002-01-10 Time 17:10 Sent To  
Notes
2002-01-10 00:00:00REVISION # 1 01/02/01
 CEILING DETAIL TO FOLLOW MANUFACTURERS
 SPECIFICATION FOR INSTALLATION.JW