Plan Review Details - Permit 01101538
Plan Review Stops For Permit 01101538
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-01 Cont ID  
Sent By pkrauss Date 2001-11-01 Time 11:19 Rev Time 0.30
Received By pkrauss Date 2001-11-01 Time 11:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-25 Cont ID  
Sent By pkrauss Date 2001-10-25 Time 13:45 Rev Time 0.35
Received By pkrauss Date 2001-10-25 Time 13:45 Sent To  
Notes
2001-10-25 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE PLANS THAT A LEGIBLE.
 CANNOT READ THE INFORMATION ON
 EQUIPMENT.
  
 1 1/2 TON IS INDICATED WHICH IS EQUAL TO
 APPROXIMATELY 600 CFM.PLANS INDICATE
 770 CFM.PLEASE LIST TOTAL BTU'S FOR
 THE EQUIPMENT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.