Plan Review Details - Permit 01101533
Plan Review Stops For Permit 01101533
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-01-16 Cont ID  
Sent By hpiskura Date 2002-01-16 Time 09:23 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-01-16 00:00:00FOR REVISED PLANS W/2HR SEPARATION`

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-12-11 Cont ID  
Sent By hpiskura Date 2001-12-11 Time 10:12 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-12-11 00:00:00MIXED OCCUPANCY SEPARATION APPLIES TO
 BOTH SIDES OF THE TENANT SPACE.THE
 NOTES DATED 11/15/01 INDICATE ONLY ONE
 SIDE.SEE SBC 704.1.1.
  
 ALSO, SEE PREVIOUS NOTES RE: IMPACT FEES
  
 THERE ARE NOW FOUR SETS OF PLANS.
 PLEASE COLLATE THE DRAWINGS SO THAT ALL
 SETS ARE CURRENT AND IN AGREEMENT WITH
 THE INFORMATION CONTAINED IN EACH OF
 THEM.
  
 (ONLY TWO SETS ARE REQUIRED FOR PERMIT
 PURPOSES)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-13 Cont ID  
Sent By hpiskura Date 2001-11-13 Time 15:09 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2001-11-13 00:00:00VERIFY EXISTING OR PROVIDE NEW MINIMUM
 TWO HOUR FIRE RATED MIXED OCCUPANCY
 SEPARATION IN ACCORDANCE WITH SBC
 704.1.1.
  
 THE CHANGE OF USE IS SUBJECT TO IMPACT
 FEES COLLECTED BY THE COUNTY FOR THE
 CITY.THE PERMIT PLANS MUST BE STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR MORE
 INFORMATION.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-01-22 Cont ID  
Sent By dpalmer Date 2002-01-22 Time 14:51 Rev Time 0.00
Received By dpalmer Date 2002-01-22 Time 14:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-06 Cont ID  
Sent By dpalmer Date 2001-12-06 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2001-12-06 Time 12:55 Sent To P
Notes
2001-12-06 00:00:00****************** UNSAT ************
  
 1)NOTE: PLEASE NOTE WIRE SIZE FEEDING
 SIZE FEEDING X-RAY MACHINE SHOWN AT #4
 AND IS RATED FOR 85AMPS. NEXT SIZE OCP
 WOULD BE 90AMPS. PLEASE NOTE THAT
 PANEL SCHEDULE SHOWS 100A OCP.
  
 2)NOTE: PLEASE NOTE THAT CONDUCTOR SIZES
 FOR 125A SERVICE ARE TOO SMALL PER
 310-16. SHOWN AS #3.
  
 3)NOTE: PLEASE NOTE THAT NOW PLANS ARE
 NOW SHOWING A NEW 125A MAIN. PLEASE
 SUBMIT AIC FOR NEW MAIN. PER 110-9
  
 4)NOTE: PLEASE NOTE THAT ANY HANDDRAWN
 CHANGES ON PLANS, MUST BE DONE BY THE
 ENGINEER OF RECORD. PLEASE ALSO NOTE
 THAT PLANS NEED TO BE RE-PRINTED. PENCIL
 CHANGES ARE NOT PERMITTED EITHER.
 417.025/
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 22:09 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 22:09 Sent To  
Notes
2001-10-30 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT PLANS SHOW A
 NEW 100A SUB PANEL, BUT EXISTING MAIN
 PANEL DOES NOT LIST ON SCHEDULE??
  
 2)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED???215-5
 CONTINUOUS LOADS AT 125%.
  
 3)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN EXIST AND
 NEW PANEL.250-122
  
 4)NOTE: PLANS NEED TO SHOW ALL BRANCH
 CIRCUITING AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE.
  
 5)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW EQUIPMENT. 110-9
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-12-10 Cont ID  
Sent By mcarsill Date 2001-12-10 Time 11:21 Rev Time 0.00
Received By mcarsill Date 2001-12-10 Time 11:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-10-25 Cont ID  
Sent By mcarsill Date 2001-10-25 Time 13:58 Rev Time 0.00
Received By mcarsill Date 2001-10-25 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-01-25 Cont ID  
Sent By pkrauss Date 2002-01-25 Time 14:36 Rev Time 0.40
Received By pkrauss Date 2002-01-25 Time 14:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-11-26 Cont ID  
Sent By pkrauss Date 2001-11-26 Time 15:49 Rev Time 0.40
Received By pkrauss Date 2001-11-26 Time 15:17 Sent To P
Notes
2001-11-26 00:00:00******************DENIED****************
  
 PLEASE DESIGNATE OUTSIDE AIR DUCT SIZE,
 MATERIAL AND LOCATION ON PLAN.
  
 OUTSIDE AIR CALCULATIONS INDICATE THREE
 EMPLOYEES,NO INDICATION OF NUMBER OF
 PATIENTS.
  
 CLARIFY "DEVELOPER RM"- NO EXHAUST IS
 INDICATED FROM THIS AREA.SHOW
 COMPLIANCE WITH ASHRAE 62-1989 TABLE 2.
 PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-11-08 Cont ID  
Sent By pkrauss Date 2001-11-08 Time 11:42 Rev Time 0.40
Received By pkrauss Date 2001-11-08 Time 11:42 Sent To  
Notes
2001-11-08 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.INDICATE O.A ON
 PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-01-29 Cont ID  
Sent By kstevens Date 2002-01-29 Time 19:46 Rev Time 0.75
Received By kstevens Date 2002-01-29 Time 19:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-12-08 Cont ID  
Sent By kstevens Date 2001-12-08 Time 11:54 Rev Time 1.50
Received By kstevens Date 2001-12-08 Time 11:54 Sent To  
Notes
2001-12-08 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FLOOR DRAIN NOT SHOWN IN BATHROOM.
 PER SPC SEC 409.4.1.1 A FLOOR DRAIN IS
 REQUIRED WITH A TRAP PRIMER. SHT A-1
 2) SHT M-1, PLEASE ADD DRINKING FOUNTAIN
 TO RISER DIAGRAM. SHOW TIE IN AND VENT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-03 Cont ID  
Sent By dpalmer Date 2001-12-06 Time 13:07 Rev Time 0.75
Received By kstevens Date 2001-11-03 Time 13:11 Sent To  
Notes
2001-11-03 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) TOILET ROOM TO COMPLY WITH FACBC -
 SEC 4.22. PLEASE SUBMIT DETAILS SHOWING
 COMPLIANCE FOR ALL DETAILS OF THIS SECT-
 ION OF FACBC-97. W/C 4.16 - LAV 4.19 -
 CLEAR FLOOR SPACE - TURNING RADIUSECT.
 2) PAGE A-1 TOILET ROOM REQUIRED TO HAVE
 A FLOOR DRAIN WITH A TRAP PRIMER PER SPC
 SEC 409.4.1.1.
 3) PAGE A-1 DRINKING FOUNTAIN REQUIRED
 PER SPC TABLE 407. SUBMIT DETAILS FOR
 DRINKING SHOWING COMPLIANCE WITH FACBC
 SEC 4.15 AND SEC 4.1.3(10) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING IF A HI/LOW DRINKING FOUNTAIN
 IS NOT INSTALLED.
 4) PAGE A-1 PLEASE CLAIRFY WATER DETAIL
 AT WAITING ROOM
 5) PAGE A-1 DEVELOPER RM. PLEASE INDIC-
 ATE WHAT CHEMICALS IF ANY ARE USED FOR
 DEVELOPEMENT. SHOW IF CHEMICALS ARE BIO-
 DEGRADEABLE OR NOT.
 6) PAGE M-1 PLUMBING RISER NOT APPROVED.
 SINK NOT VENTED.
 7) RPZ BACKFLOW REQUIRED ON WATER
 SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-16 Cont ID  
Sent By hpiskura Date 2001-12-11 Time 10:05 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved